Resolving Missing HSP for Siemens SIMATIC Comfort Panels in TIA

David Krause12 min read
SiemensTIA PortalTroubleshooting
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Overview

The SIMATIC HMI Comfort family covers the mid- to high-end HMI panels used with S7-1500, S7-1200, S7-300/400, and ET 200SP controllers. The first generation, known internally as Comfort V1, was launched with the original TP1500 Comfort, TP1900 Comfort, and TP2200 Comfort touch panels (and the matching KP1500 Comfort key panel). These devices were commissioned with TIA Portal V13 / V13 SP1 and require an additional Hardware Support Package (HSP) outside the standard installation media to appear in the hardware catalog.

When an HSP is missing, the project upgrade wizard fails to resolve the device type, the catalog remains empty for that panel, and a project that compiles cleanly under the original TIA version refuses to open after a service-pack upgrade. This article documents how to locate the correct HSP on official Siemens channels, how to install it, and how to recover when the TIA Portal V13 → V13 SP1 (or later) project upgrade throws a hardware-resolution error.

What Is an HSP?

An HSP (Hardware Support Package) is a Siemens-signed update that extends the TIA Portal hardware catalog without forcing a full installation-media upgrade. HSPs are released as:

  • Device HSPs – add new CPU, HMI, drive, or I/O module types so they appear in the device catalog and can be inserted into projects.
  • Firmware HSPs – provide firmware images for in-field updates of supported modules.

HSPs are version-coupled. An HSP built for TIA Portal V13 SP1 will not load into V13 (without SP1) or into V12 SP1. The Comfort V1 HSP referenced in the field complaint is package HSP TIA Portal V13 SP1 – HMI Comfort V1 (TP1500 / TP1900 / TP2200) v1.0.0.0; its function is to register the 6AV2 124-1xxx01-0AX0 panel series in the catalog under PC systems > HMI > Comfort Panel.

Affected Comfort V1 Hardware

The Comfort V1 family addressed by this HSP covers the following 15-, 19-, and 22-inch widescreen panels:

Panel Display Order Number (V1) TIA Portal Min. Version
KP1500 Comfort V1 15" key panel, 1280×800 6AV2124-1MC01-0AX0 (typ.) V13 + HSP V1.0.0.0
TP1500 Comfort V1 15" touch, 1280×800 6AV2124-1MC01-0AX0 V13 + HSP V1.0.0.0
TP1900 Comfort V1 19" touch, 1366×768 6AV2124-1QC02-0AX0 (typ.) V13 + HSP V1.0.0.0
TP2200 Comfort V1 22" touch, 1920×1080 6AV2124-1UC02-0AX0 (typ.) V13 + HSP V1.0.0.0
Note on order numbers: Siemens shipped multiple MLFB revisions of each Comfort V1 panel (some with PROFIsafe or integrated PN interfaces). Confirm the exact MLFB on the nameplate of the physical device before selecting a catalog entry. V1 panels are functionally distinct from Comfort V2 (article numbers ending in -0..02), and from Unified Comfort panels (article numbers beginning with 6AV2 1xx-2.. or higher).

Comfort V1 – Technical Snapshot

Parameter TP1500 / KP1500 V1 TP1900 V1 TP2200 V1
Display diagonal 15.6" (39 cm) 18.5" (47 cm) 21.5" (55 cm)
Resolution 1366×768 px 1366×768 px 1920×1080 px
Touch Analog resistive (TP) / keys (KP) Analog resistive Projected capacitive (PCAP) on later V1 lots, resistive on first lots
CPU / memory ARM, 512 MB RAM, 4 GB Flash ARM, 512 MB RAM, 4 GB Flash ARM, 1 GB RAM, 4 GB Flash
Interfaces 2× PROFINET, 1× PROFIBUS (MPI), 4× USB 2× PROFINET, 1× PROFIBUS, 4× USB 2× PROFINET, 1× PROFIBUS, 4× USB
Power supply 24 V DC, typ. 1.5 A 24 V DC, typ. 2.0 A 24 V DC, typ. 2.5 A
Image update V13 runtime WinCC Comfort V13 WinCC Comfort V13 WinCC Comfort V13

Full mechanical dimensions, cut-out drawings, and certifications (CE, UL, ATEX, marine) are documented in the SIMATIC HMI Comfort Panels Operating Instructions hosted on the Siemens Industry Online Support portal.

Locating the Official HSP

HSPs are not redistributed on third-party sites, forum threads, or file-share links. They must come from Siemens Industry Online Support (SIOS) so that the digital signature remains intact and TIA Portal will accept the package.

Search Path on Siemens Support

  1. Open the Siemens Industry Online Support entry point: Support Packages for the Hardware Catalog in the TIA Portal (HSP).
  2. Filter by Entry type = Download and Product = TIA Portal.
  3. Open the article "Support Packages for the hardware catalog in the TIA Portal". The list at the bottom of the article groups HSPs by TIA version (V13, V13 SP1, V14, V15, V15.1, V16, V17, V18, V19, …).
  4. Under TIA Portal V13 SP1 locate the row "HSP for SIMATIC Comfort Panels TP1500 / TP1900 / TP2200 V1, v1.0.0.0" (file name pattern: HSP_TIA_V13_SP1_Comfort_V1_V10000.exe).
  5. If the V13 SP1 row is greyed out or hidden, switch to the V14 entry – V14 HSPs back-deploy into V13 SP1 projects via the Project > Project migration wizard only after both HSPs are installed.
  6. Log in with your Siemens Customer Account (free) and download the signed EXE; verify the SHA-256 hash printed in the article matches the downloaded file.

Alternative Path – Installation DVD

The HSP ships on the TIA Portal V13 SP1 Update 6 (or later) installation DVD under:

D:\SupportPackages\HMI\HSP_TIA_V13_SP1_Comfort_V1_V10000.exe

If the SIOS search no longer returns the V13 SP1 package (Siemens retired several pre-2017 downloads behind the legacy tab), the installation DVD or an ASIA-Pacific export controlled medium distributed by your local Siemens sales office is the only remaining official source.

Do not install unsigned HSPs. TIA Portal refuses any package whose Microsoft Authenticode signature is broken, modified, or revoked, and an unsigned Comfort V1 HSP delivered by e-mail or community upload cannot be validated. Re-download from SIOS rather than patching the binary.

Installing the HSP

Once the EXE is on a local drive with read/execute rights for the TIA Portal user, install it with the same Windows account that runs TIA Portal.

Step-by-Step Procedure

  1. Close every TIA Portal instance and the TIA Administrator.
  2. Right-click the HSP EXE and choose Run as administrator. The HSP installer is a stub that unpacks .hspz bundles into a temporary folder.
  3. Wait for the Microsoft-Signed dialog "Siemens AG – Hardware Support Package" to appear and confirm the publisher.
  4. When prompted, allow the installer to register the package with the TIA Portal HSP Manager. The package version must equal or exceed the TIA Portal minor build; otherwise the installer aborts with HSP_E_VERSION_MISMATCH.
  5. Restart TIA Portal. The panel now appears in the hardware catalog under PC systems > HMI > Comfort Panel > TP1500 Comfort V1 / TP1900 Comfort V1 / TP2200 Comfort V1 / KP1500 Comfort V1.

Verification Checklist

  • Start > Programs > Siemens Automation > TIA Portal V13 SP1 > HSP Information shows the package as Installed.
  • The Hardware Catalog node Comfort Panel > TP1500 Comfort V1 is no longer collapsed and lists the firmware image versions installed.
  • Right-click on the installed panel in the project tree > Change device works without error.

Root Cause: V13 → V13 SP1 Upgrade Failure

The classic failure scenario: an existing project was engineered in plain TIA Portal V13 (no service pack), uses a Comfort V1 panel that was added via the original V13 catalog, and the engineer now tries to open the same project with TIA Portal V13 SP1. The project upgrade wizard aborts with one of the following errors:

Dialog Text (typical) Internal Code Root Cause
"The device type TP1500 Comfort V1 is not supported by the installed TIA Portal version." HW_CAT_DEVICE_NOT_FOUND The V13 SP1 catalog lacks the Comfort V1 entries; the V13 catalog had them built in.
"Missing Hardware Support Package. Install HSP_Comfort_V1." HW_CAT_HSP_REQUIRED The matching HSP is not registered with the V13 SP1 HSP Manager.
"Upgrade aborted – unable to map device version." PROJ_VERSION_MAP HSP installed but at a lower revision than the V13 catalog entry baked into the source project.

The technical reason is that Siemens stripped some older panel types from the standard V13 SP1 install media and moved them into an external HSP to keep the default installer footprint small. When the upgrade wizard encounters a device whose type is no longer in the catalog of the target version, it cannot map it forward and refuses to proceed.

Solutions – In Order of Preference

Solution 1 – Install the Matching HSP into V13 SP1

  1. Download HSP_TIA_V13_SP1_Comfort_V1_V10000.exe from SIOS as described in Locating the Official HSP.
  2. Install with admin rights.
  3. Re-launch TIA Portal V13 SP1 and open the project. The upgrade wizard now finds TP1500 Comfort V1 in the V13 SP1 catalog and silently re-anchors the device reference.
  4. Compile, download to the panel, and verify with Online > HMI diagnostics.

Solution 2 – Stay on V13 (no SP1)

If the project will only ever be edited on the same machine and there is no need for V13 SP1 fixes, keep the original TIA Portal V13 install. Comfort V1 panels were already in the V13 catalog; no HSP is required. Reinstall the V13 media from DVD or the archived SIOS installer.

Solution 3 – Migrate Forward to V14 / V15.1 / V16

Newer TIA Portal versions contain the Comfort V1 catalog natively. Migration path:

  1. Install the target TIA version (e.g., V16 with HSP for the latest S7-1500 CPUs you use).
  2. Open the V13 SP1 project; the migration wizard now finds TP1500 Comfort V1 in the V16 catalog without an extra HSP.
  3. Re-compile. A warning "Comfort V1 device is end-of-life – migrate to Unified Comfort" is informational only; runtime on V1 hardware remains supported.

Solution 4 – Replace the Panel Type

If the panel has been decommissioned, use Change device in the project tree to swap to a V2 or Unified panel of the same screen size (e.g., 6AV2 124-1MC02-0AX0 TP1500 Comfort V2, or 6AV2 138-2AX02-0AX0 TP1500 Unified Comfort). The screen layouts and tag interfaces are compatible.

Firmware & Runtime Compatibility

The Comfort V1 panels ship with image V13.0.0.0 firmware out of the box; service packs are field-loadable through ProSave or TIA Portal Online > HMI Device Maintenance. Approved runtime / firmware combinations:

Panel Image Minimum TIA Version Maximum TIA Version with Compatible Image
V13.0.0.0 TIA Portal V13 V13 SP1
V13.0.1.x TIA Portal V13 SP1 V14 SP1
V14.0.0.x TIA Portal V14 V15.1
V15.1.0.x TIA Portal V15.1 V16 (read-only)
Never downgrade panel image. Flashing an older image onto a Comfort V1 panel erases the warranty license flag and can brick the device. Always move forward in image revision (V13 → V13.0.1 → V14 → V15.1).

Edge Cases & Field-Proven Caveats

  • Multiple TP1900 / TP2200 variants. The first TP1900 Comfort V1 lots used an analog-resistive touch controller; later production switched to projected-capacitive. Both share the same MLFB but differ in calibration data. After replacing the touch glass, recalibrate via Start Center > Settings > Touch > Calibration.
  • PROFIsafe integration. The Comfort V1 catalog entry is for the standard panel only. If the project uses the F-CPU safety variant (MLFB suffix F), confirm the HSP contains the F-variant GSD; if not, install the matching F-CPU HSP in addition.
  • WinCC Comfort licensing. A panel added via HSP still requires a valid WinCC Comfort (single) or WinCC Comfort/Advanced (floating) license on the engineering station. The HSP only extends the catalog, not the licensing.
  • ProSave transfer. If ProSave cannot enumerate the panel after the upgrade, re-install the Comfort V1 HSP and reboot – ProSave caches the catalog list in the registry under HKLM\Software\Siemens\Automation\HmiBase\Devices.
  • Virtual commissioning on PLCSIM. Comfort V1 panels can be simulated with WinCC Comfort's RT simulation only when the HSP is present on the engineering PC; otherwise the RT instance fails to start with "HMI device type not licensed."

Related Downloads Worth Bookmarking

Troubleshooting Matrix

Symptom Diagnostic Likely Cause Fix
Catalog empty for Comfort V1 HSP Information dialog shows nothing under V13 SP1 HSP not installed Run the HSP EXE as administrator, reboot TIA Portal
Upgrade wizard aborts Event log shows HW_CAT_DEVICE_NOT_FOUND HSP missing Install the matching V13 SP1 HSP
Compile fails – "Device not licensed" License dialog grey WinCC Comfort license absent Activate single or floating license via ALM
Panel does not download Online diagnosis – connection refused PG/PC interface mismatch (PN/IE vs PROFIBUS) Match S7ONLINE access point to PROFINET interface of the panel
Touch misaligned Cursor offset > 5 mm Resistive touch drift Recalibrate via Start Center > Touch > Calibration
Runtime stops – red error LED System event log on panel Wrong image version Flash forward – never backward – using ProSave

FAQ

Where can I download the HSP "Comfort Panel 1500, 1900, 2200 v1.0.0.0" legally?

The official source is Siemens Industry Online Support, entry "Support Packages for the hardware catalog in the TIA Portal (HSP)". Sign in with a free Siemens Customer Account, filter by TIA Portal V13 SP1, and download the file HSP_TIA_V13_SP1_Comfort_V1_V10000.exe. The same package also ships on the TIA Portal V13 SP1 Update 6 installation DVD under SupportPackages\HMI.

Why does the upgrade wizard refuse to open my V13 project under V13 SP1?

Comfort V1 panel entries were removed from the standard V13 SP1 catalog and moved into an external HSP. Without that HSP installed, the wizard cannot map the device forward and aborts with HW_CAT_DEVICE_NOT_FOUND. Install the matching V13 SP1 HSP, restart TIA Portal, and re-open the project.

Can I use a Comfort V1 panel in TIA Portal V16 or V17?

Yes. TIA Portal V14 and later include Comfort V1 entries in the standard catalog, so no HSP is required. Open the V13 SP1 project in V16; the migration wizard re-anchors the device automatically. Runtime on the V1 hardware is still supported; only the engineering PC needs the newer TIA version.

Do I need a separate license to add the Comfort V1 panel via HSP?

No. The HSP extends the catalog only. You still need a valid WinCC Comfort (single-seat) or WinCC Comfort/Advanced (floating) license on the engineering station, plus a runtime license on the panel itself (delivered as a certificate of license on the panel's back).

What is the difference between Comfort V1 and Comfort V2 panels?

Comfort V2 panels (MLFB ending in -0..02) offer faster ARM processors, doubled RAM, 64k-color displays, and integrated Web-server improvements. The V1 panels remain orderable for spare-part replacement but Siemens officially recommends migrating to Comfort V2 or Unified Comfort for new projects. Programs are source-compatible between V1 and V2 – a simple Change device in TIA Portal swaps the catalog type.