PDU-I.Exd: Verifying Availability and HART Support

Jason IP2 min read
Other ManufacturerSensor IntegrationTechnical Reference
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

The available evidence does not establish that the explosion-protected PDU-I.Exd float level transmitter is commercially available. It appears as a new product on page 306 of the 2018 catalog, but the referenced official level-sensor product section lists only PDU-I. Treat the explosion-protected version as unconfirmed until the manufacturer supplies current ordering and certification data.

Availability Evidence

Evidence What it confirms What remains unknown
2018 catalog, page 306 PDU-I.Exd was presented as a new product. Current production status, stock, lead time, and orderability.
Referenced official level-sensor section PDU-I is listed. Whether omission of PDU-I.Exd means withdrawal, delayed release, or incomplete web documentation.
Project requirement An explosion-protected version is required. Explosion-protection marking, certificate, permitted installation area, and approved configuration.
Customer preference HART communication is desired. Whether any PDU-I.Exd configuration supports HART.

Unconfirmed Selection Data

The evidence identifies a float level sensor with a 4–20 mA output, but it provides no ordering code, electrical ratings, process connection, materials, measuring range, explosion-protection marking, certificate, or HART capability. Do not transfer specifications from the listed PDU-I to PDU-I.Exd unless the manufacturer explicitly confirms that they apply.

HART is a requested feature, not a documented product function. Keep the control-system interface defined as 4–20 mA only until the manufacturer identifies a HART-capable configuration and supplies its corresponding technical documentation.

Procurement Decision Procedure

  1. Send the manufacturer the exact PDU-I.Exd designation and reference the 2018 catalog entry on page 306. Request written confirmation of current production and sale status.
  2. Request the complete ordering code, current datasheet, explosion-protection certificate, protection marking, installation restrictions, and commercial lead time.
  3. Ask whether HART is supported on the offered configuration. If supported, require that capability to appear in the ordering data and technical documentation.
  4. Compare the returned documentation with the project hazardous-area and instrumentation requirements before releasing the device for purchase.

Submittal Verification

Accept the selection only when the quotation, ordering code, datasheet, and explosion-protection documentation identify the same device configuration. Separately verify that the signal interface is documented as 4–20 mA and that HART appears explicitly if the project requires it. A catalog entry or the presence of the non-Ex PDU-I on a website does not resolve these checks.

FAQ

Is the PDU-I.Exd level sensor currently available?

The evidence does not confirm current availability. It appeared as a new product on page 306 of the 2018 catalog, while the referenced official product section lists only PDU-I.

Does the PDU-I.Exd support HART communication?

HART support is not confirmed by the available material. Require written confirmation and configuration-specific documentation before including HART in the project design.

What documents are required before specifying PDU-I.Exd?

Obtain the current datasheet, complete ordering code, explosion-protection certificate and marking, installation restrictions, production status, and confirmation of the 4–20 mA and any required HART interface.