Programming Omron CP1L Analog Input with RS232 Setpoint

James Nishida14 min read
CJ/CP SeriesOmronTutorial / How-to
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Application Overview

The control task is a classic position/level follower. The PLC receives a numeric setpoint over RS232 (typically a hex or BCD code from a host controller, HMI, or instrument), reads an analog feedback value from a potentiometer or transducer, and energises an output (or a pair of raise/lower outputs) until the feedback equals the setpoint. The architecture fits any Omron CP1L, CP1E, CP1H, CJ2M, or CS1 platform. This guide uses the CP1L-M30/M40DR-A as the reference CPU because it integrates two 12-bit analog inputs directly on the unit, removing the need for an expansion module for small machines.

The four logical steps from the source specification map cleanly onto the standard Omron instruction set:

  1. Receive a hex value from a remote device into DM area — use the RXD instruction on serial port 1 (built-in RS-232C) or port 2 (option board CP1W-CIF01).
  2. Read a hex value from an analog input — the CP1L-M resolves the voltage across the analog terminal to a 12-bit word in CIO 200/CIO 201 (raw 0x0000–0x0FFF).
  3. Compute the deviation — use signed subtraction (- or CLS) and a deadband comparator.
  4. Drive the output — use OUT, SET/RSET, or a full PID block to command a relay, transistor, or analog output until the deviation is inside the deadband.
Engineering note. "Hex value from RS232" and "hex value from analog input" in the source are independent numeric representations. The setpoint word is a binary integer (0–65535) carried as ASCII hex bytes on the wire, while the analog word is a binary 12-bit ADC count (0–4095). The PLC unifies them in DM (D) area after the receive completes, so a single compare against the scaled feedback is sufficient.

Prerequisites

  • CP1L-M30DR-A (or CP1L-M40DR-A) with built-in analog. For external I/O, an CP1W-AD041 (4 AI, 1/6000 resolution) or CP1W-AD042 (4 AI, 1/12000 resolution) module on a CP1L-L or CP1E base.
  • CX-Programmer 9.x or Sysmac Studio 1.4x with CP1L support (firmware 1.0 or later is sufficient for these instructions).
  • RS-232C option board CP1W-CIF01 if the host uses a DB-9 (PC-style) cable and the CPU only has RS-485. The built-in port on CP1L-EM/EL is RS-485; CP1L-M/CP1H-Y have a built-in RS-232C.
  • 10 kΩ linear potentiometer (or 4–20 mA transducer) wired to the analog input terminals as described below.
  • A reference document: the CP1L CPU Unit Operation Manual (Cat. No. W462-E1), section 4 (I/O Memory) and section 5 (Built-in Analog).

Hardware Selection and Wiring

The CP1L-M30DR-A exposes a two-channel analog sub-assembly on the top-left of the unit. Pinout from the CPU manual:

Terminal Signal Description
L1 / L2 / L3 VIN0 / IIN0 / COM Analog input 0 — voltage (0–10 V), current (0–20 mA or 4–20 mA), shared common
L4 / L5 / L6 VIN1 / IIN1 / COM Analog input 1 — second channel, independent range
L7 / L8 VOUT0 / IOUT0 Analog output 0 (used by PID or as a manual command signal)

Wiring rules that prevent the most common field failures:

  1. Use shielded twisted pair for any cable longer than 0.5 m. Ground the shield at the PLC end only.
  2. For a potentiometer: connect one end of the track to V+, the wiper to VIN0, and the other end to COM. On the CP1L-M, the +24 VDC terminal cannot source enough current for a 10 kΩ pot; use an external 24 V supply referenced to the CPU's functional earth (FE) terminal.
  3. For 4–20 mA transducers: the current input is a sinking loop. Connect the transducer positive to the +24 V external supply, the negative to IIN0, and COM to the same supply's 0 V.
  4. Set the channel range DIP switch on the side of the CP1L-M to "V" or "I" as appropriate. The PLC Setup range code must match the switch; mismatches force the channel to 0000 hex with no error bit.

For more details on shielding and signal conditioning, the National Instruments primer on field wiring and noise considerations for analog signals covers the general principles. Microchip's application note "Maximizing the Signal" discusses the input-impedance and settling-time factors that also apply to PLC ADCs.

Analog Input Module Configuration

The CP1L-M's built-in analog resolves to 12 bits (0–4095 decimal) for 0–10 V and 0–20 mA ranges. Enable and configure the channels through PLC Setup → Built-in AD in CX-Programmer (or the equivalent tab in Sysmac Studio). The relevant default parameters:

Setup word Function Typical value
DM 6602 (channel 0) / DM 6603 (channel 1) Enable and range 0000 hex (0–10 V, 12-bit, 0–4095). 0100 hex for 0–20 mA, 0200 hex for 4–20 mA
DM 6617 / DM 6618 Averaging filter (samples) 0001 = moving average of 1 (no filter); 0008 is a good field default for noisy pots

For external CP1W-AD041 modules, the address allocation is shifted by the unit number (U). A CP1W-AD041 mounted as unit 1 occupies CIO 200–CIO 203 (4 channels, 0000–1770 hex for 0–10 V at 1/6000 resolution) and writes the engineering-scaled value to D200–D203 after SCL2 processing is performed in the ladder.

Resolution mismatch trap. CP1W-AD041 is 6000-count; CP1W-AD042 is 12000-count. The same SCL2 scaling factor will saturate at the wrong span on the higher-resolution module. Always verify the part number printed on the front label before commissioning.

RS232 Communication Setup

The CP1L serial port (built-in RS-232C on the M/EM types, or the CP1W-CIF01 option board on the L/EL types) is configured in PLC Setup → Serial Port 1 (or 2). The two key parameters for the setpoint stream:

Parameter Default Recommended for ASCII hex setpoint
Baud rate 9 600 9 600 or 19 200 depending on host
Data bits 7 8 (binary hex, two ASCII chars per byte are not needed; the host sends raw 0x00–0xFF)
Parity Even None for binary protocols; Even for Modbus RTU master-style framing
Stop bits 2 1
Start code / End code None STX (0x02) / CR (0x0D) when the host appends a terminator; otherwise disable

When the host sends a fixed frame such as <STX> 0x12 0x34 <CR> (setpoint 0x1234), the PLC's RXD instruction will deposit the two payload bytes into consecutive DM words beginning at the destination. The format is:

RXD(235) D C N

  • D — first destination word (e.g., D100). The raw bytes land low-byte-first because Omron stores words little-endian in the DM area.
  • C — control word: 0000 for port 1, 0001 for port 2, 0100 for port 1 with no start/end code match (i.e., accept any byte).
  • N — number of bytes to receive (0–256). Setting N=2 for the example above reads exactly the setpoint payload.

The RXD instruction is edge-triggered; in practice the application ties it to a periodic pulse from a 50 ms or 100 ms timer (TIM 0 #50) or to a host-issued "ready" handshake bit mapped to a CIO input.

Memory Map and Variable Allocation

Use a clean allocation so that the receive buffer, scaling, and PID block do not collide. A typical layout for the CP1L-M reference design:

Address Symbol Type Purpose
D0 SP_RAW UINT Setpoint as received over RS232 (0–65535)
D1 PV_RAW UINT Analog input raw ADC count (0–4095)
D2 PV_EU UINT Analog input scaled to engineering units (0–1000 = 0.0–100.0 %)
D3 DEV INT Signed deviation = SP_RAW − PV_EU
D4 DEADBAND UINT Acceptable error magnitude (e.g., 5 EU)
D10–D41 PID_xxx PID working area (32 words per loop)
W0.00 OUT_UP BOOL "Increase" output (e.g., open valve / drive CW)
W0.01 OUT_DN BOOL "Decrease" output
W0.02 AT_SETPOINT BOOL TRUE while |DEV| ≤ DEADBAND
CIO 200 AD0_RAW WORD Channel 0 raw value, 0x0000–0x0FFF

The Working (W) area is preferred for derived boolean flags because it is non-retentive; on power-up all W bits clear automatically, which is the correct default for a follower that must re-acquire the setpoint before driving outputs.

Analog Signal Conditioning and Scaling

The raw ADC count from CIO 200 is not the engineering value the user needs to compare against the setpoint. Two stages of conditioning are typical:

Stage 1: Linear scaling with SCL2

SCL2(486) S D1 D2 R converts a binary source word to a BCD result over an arbitrary span:

  • S = D1 (PV_RAW)
  • D1, D2 = control block of three words: D100 (input min = 0), D101 (input max = 4095), D102 (output min = 0)
  • The fourth word of the control block is implicit; CX-Programmer allocates D100–D103 for one SCL2 invocation.
  • R = D2 (PV_EU). With output range 0–1000 the result represents 0.0–100.0 % of pot travel.

The instruction works on unsigned binary. If the application uses 4–20 mA and treats 4 mA as live zero, perform the offset in a separate MOV to subtract 819 (which is 4 mA at 4095/20 mA) and clamp negative results to zero with a LIMIT block.

Stage 2: Moving-average filtering

The CP1L-M averaging filter set in DM 6617 already provides a 1-to-128 sample moving average. For most mechanical potentiometers, 8 samples is enough to clean 50/60 Hz pickup while keeping loop latency under 50 ms. If a faster response is required, set the filter to 1 and add a software filter in ladder:

PV_RAW_FILT = (7 × PV_RAW_FILT_PREV + PV_RAW) / 8

Implement with MOV and *// using the BSET scratch area in W. Avoid integer divide-by-zero by always dividing the running total first, then adding the new sample.

Comparison and Output Control Logic

Three control strategies are common. Choose based on the actuator (relay, proportional valve, or VFD).

Strategy A — On/Off with deadband (simplest, matches the source spec)

Use two unsigned compares plus the absolute-value trick. The ladder:

 |--[ LD  W0.02 ]--[ OUT W0.00 ]   ; if AT_SETPOINT, latch UP OFF
 |--[ CMP  D3  D4 ]                 ; D3 − D4
 |--[ >  ]--[ OUT W0.00 ]           ; DEV > +deadband → OUT_UP ON
 |--[ < -]--[ OUT W0.01 ]           ; DEV < −deadband → OUT_DN ON
 |--[ ABS D3 ]--[ CMP D10 D4 ]      ; |DEV| ≤ DEADBAND → W0.02 ON

The ABS instruction on CP1L is not present in every firmware revision; an equivalent is to test both DEV > 0 and -DEV > 0 in two parallel rungs. CPS (signed compare) reads cleanly:

 |--[ CPS D3 D4 ]--[ P_GT ]--[ OUT W0.00 ]
 |--[ CPS D3 D4 ]--[ P_LT ]--[ OUT W0.01 ]
 |--[ CPS D3 D4 ]--[ P_EQ ]--[ OR  W0.02 ]--[ OUT W0.02 ]

Strategy B — Incremental (stepper / pulse train)

Replace the boolean outputs with a pulse-rate proportional to |DEV|. Multiply by a gain and drive SPED or PULS on a high-speed output. This is the standard approach for a stepper-driven potentiometer on a CP1H-Y, which exposes 100 kHz pulse outputs on CIO 100.00/CIO 100.01.

Strategy C — PID control (analog actuator)

For proportional valves, the CP1L's PID(190) block gives full PID with auto-tuning. Configure D10–D41 as the working area:

 |--[ P_First_Cycle ]--[ PID D0 D10 D50 ]   ; SP, work, output (0–1000 EU)

The PID output is a 0–1000 integer that maps directly to the analog output DA0 at CIO 210 by MOV. Set the proportional band to roughly 20 % of the pot travel, the integral time to 5 s, and the derivative time to 0 s for a slow hydraulic or pneumatic follower; tighten the proportional band and shorten Ti for fast electromechanical actuators.

Anti-windup. CP1L PID has built-in input/output range limiting in the work words. Always set the input range (word +1) and output range (word +2) to match your scaling, or the loop will saturate the analog output during the initial seek.

Complete Ladder Implementation

The full sequence below ties all stages together. Rung numbers are for reference; the actual implementation in CX-Programmer is a single POUs.

Rung 1: Receive the setpoint each cycle (50 ms tick)
 |--[ TIM 0 #50 ]--[ RXD D100 #0000 #0002 ]
After successful RXD, swap the two bytes if the host sends big-endian:
 |--[ MOVB D101.0 D0.8 #8 ]--[ SWAP D0 ]
Or, in most protocols the host already sends little-endian and the swap is unnecessary.

Rung 2: Read built-in analog channel 0
 |--[ MOV CIO200 D1 ]                 ; raw ADC count

Rung 3: Scale raw to 0–1000 EU
 |--[ SCL2 D1 D100 D2 ]               ; D100–D103 are the SCL2 control block

Rung 4: Signed deviation
 |--[ -  D0 D2 D3 ]                   ; D3 = SP − PV (signed)

Rung 5: Drive outputs
 |--[ CPS D3 D4 ]--[ P_GT ]--[ OUT W0.00 ]
 |--[ CPS D3 D4 ]--[ P_LT ]--[ OUT W0.01 ]
 |--[ CPS D3 D4 ]--[ P_EQ ]--[ OR W0.02 ]--[ OUT W0.02 ]

Rung 6: Re-trigger on first scan and clear latches on E-STOP
 |--[ P_First_Cycle ]--[ RSET W0.00 ]--[ RSET W0.01 ]
 |--[ CIO 0.00 ]--[ RSET W0.00 ]--[ RSET W0.01 ]

The hardware outputs 100.00 (UP) and 100.01 (DN) on the CP1L-M30DR-A are wired to the actuator contactor. Internal relays W0.00/W0.01 drive the physical outputs through OUT 100.00 and OUT 100.01 on dedicated rungs to keep the logic and wiring decoupled.

Verification and Commissioning

  1. Power the CPU with no field wiring. In CX-Programmer, open the I/O Monitor and confirm CIO 200 reads a stable 0x0000–0x0FFF when you ground VIN0 (should be near 0x0000) and when you apply 10.0 V (should be ≥ 0x0F00). If the read stays at 0000, check the DIP switch range and DM 6602 setting.
  2. Connect a terminal emulator (Tera Term, PuTTY) to the CP1L serial port at 9 600-8-N-1. Send STX 0x12 0x34 CR. Watch D0 in the watch window — it should show 0x1234 after the next RXD scan.
  3. Force D0 to 500 (50.0 %) and rotate the pot. The UP output should energise below 50 % and the DN output above 50 %; both should release between, say, 49.5 % and 50.5 % if DEADBAND is 5.
  4. Disconnect the host and verify that the PLC does not latch the last good setpoint into a new motion. CP1L DM area is retained through power cycle, so add a watchdog that clears D0 if no valid RXD has been received within 5 s.
  5. Document the scaling constants in the PLC Setup comments so the next engineer can reverse-engineer the scaling without running the math.

Troubleshooting Matrix

Symptom First check Resolution
CIO 200 stuck at 0000 DIP switch, DM 6602 range code Set the range code to match the physical input; CP1L will not error-flag a misconfigured range
D0 always zero A392.13 (port 1 reception complete flag) Confirm the RXD control word and the host's start/end code; some hosts use LF only, not CR
Output chatters around setpoint DEADBAND too small, no filter Set DM 6617 averaging to 8 samples; increase DEADBAND to 1 % of full scale
PID oscillates Sample time, derivative Set PID sample period to ≥ 4× the actuator stroke time; set D = 0 for slow systems
Setpoint drifts after power cycle D0 is retentive DM Use a CIO work word for SP and move from D0 to CIO on a one-shot, or clear D0 in the first-scan routine
Analog reads negative when pot is at mid-scale Wiring to wrong VIN/IIN terminal CP1L-M L1 is voltage input, L2 is current input — they are not interchangeable pins
RXD never completes Frame format mismatch Disable the start/end code match in PLC Setup if the host does not send STX/CR; the control word bit 8 toggles this
Field practice. Always separate the scaling constants (D100–D103) from the working values (D0–D4) by at least 16 words. When the day comes to retune, only the scaling block needs to change; the rest of the ladder is untouched.

FAQ

What is the resolution of the CP1L-M built-in analog input?

The built-in analog on CP1L-M30/M40DR-A is 12-bit, giving 0–4095 counts (0x0000–0x0FFF) for a 0–10 V or 0–20 mA range. For higher resolution, add a CP1W-AD042 expansion module (1/12000, 0–10 V) or a CP1W-AD081 (1/8000).

Which instruction receives a hex setpoint over RS232 on CP1L?

Use the RXD (Network Receive) instruction. The format is RXD D C N where D is the destination word (DM area), C is the control word selecting the port and start/end code matching, and N is the number of bytes to receive (0–256). The destination receives bytes low-byte-first.

How do I scale a 0–4095 raw ADC count to 0–1000 engineering units?

Use the SCL2 (Scaling 2) instruction with a 4-word control block: input minimum, input maximum, output minimum, output maximum. Set input min = 0, input max = 4095, output min = 0, output max = 1000. The result in the destination word is a BCD value representing the scaled engineering unit.

Can I use PID instead of a simple on/off comparator?

Yes. The CP1L supports the PID(190) instruction. Allocate 32 words of working memory (D10–D41) and call PID with the setpoint in D0, the work pointer in D10, and the output in D50. Map D50 to the analog output (CIO 210) for a proportional actuator.

How do I add a deadband so the output does not chatter near the setpoint?

Use the signed compare instruction CPS to test the deviation against +DEADBAND and −DEADBAND, and set the "at setpoint" bit when both conditions are false. A deadband of 1–2 % of full scale is typical for on/off output control, while a proportional loop rarely needs more than 0.1 %.

Why does the built-in analog read 0 even with a live signal?

The most common causes are: (1) the channel is not enabled in DM 6602/DM 6603, (2) the range DIP switch is in the wrong position relative to the PLC Setup, or (3) the input is wired to the wrong terminal (VIN vs IIN). The CP1L will not flag an error for any of these conditions; you must verify each independently.

What is the maximum RXD buffer size on CP1L?

Up to 256 bytes per RXD invocation. For larger frames, chain multiple RXD instructions or use the protocol macro option board (CP1W-CIF01-V1 with PMCR instruction).

Back to blog