Quadriga S5 PLC Programming: Implementing Counters Using COMP
Quadriga is a DOS-based programming environment sold in the United Kingdom by Pantek for use with Siemens S5 series programmable logic controllers. The package is menu-driven and function-key driven, giving engineers a structured workflow for creating, editing, and documenting S5 programs. Unlike modern Siemens tooling such as TIA Portal or the historical STEP 7, Quadriga was designed for an era of monochrome monitors, keyboard shortcuts, and direct keyboard entry rather than graphical drag-and-drop. Engineers moving onto S5 machinery from platforms such as Mitsubishi GX Works, GX Developer, or Medoc typically find Quadriga austere but predictable once the menu structure is mapped out.
This reference covers the practical knowledge needed to make minor modifications to existing S5 programs in Quadriga, with a specific focus on counter implementation. The source-of-truth for this article is the workflow used by engineers who have kept S5 systems in production long after the platform was officially superseded by the S7 family, together with the documented counter and timer behavior of the S5 CPU firmware itself.
Overview of Quadriga and the S5 Environment
Quadriga is one of several third-party S5 programming packages that circulated in the United Kingdom during the 1990s. Pantek, the distributor referenced in field discussions, was also the company marketing Wonderware InTouch in the UK at the time, which is why Quadriga installations are often found on the same engineering benches as early Wonderware HMI nodes. The two product lines were sold through the same channel but were never technically integrated at the PLC programming level.
Quadriga's primary value proposition is offline S5 program development and documentation. It can edit the same program files that Siemens' own STEP 5 tools produce, and it can communicate with the PLC through the standard Siemens programming cable (typically the AS511 protocol over a serial COM port). Engineers using Quadriga can:
- Open and edit existing S5 program files (DOT, S5D, or SEQ blocks depending on version)
- Insert, delete, and modify ladder network elements using either the menu bar or function keys
- Document I/O assignments, symbol names, and operator comments in a project file
- Transfer compiled programs to and from the CPU over the programming port
- Use a watch/status view to monitor flag, input, output, timer, and counter values online
Siemens S5 PLC Family Context
Before working with Quadriga, it helps to understand the CPU families it targets. The Siemens SIMATIC S5 range spanned roughly 1979 through the late 1990s and was organized by increasing capability:
| Family | Typical Use | Counter Word Range | Timer Word Range |
|---|---|---|---|
| S5-90U / S5-95U | Compact, small machines | C0–C31 (32 counters) | T0–T31 (32 timers) |
| S5-100U | Modular, small I/O | C0–C31 | T0–T31 |
| S5-115U | Mid-range, the most common surviving platform | C0–C127 | T0–T127 |
| S5-135U / S5-155U | Large process and infrastructure | C0–C255 | T0–T255 |
All S5 counters store a 16-bit BCD value in the range 0–999 in their assigned counter word. All S5 timers store a 16-bit BCD time value in the same 0–999 numeric range, interpreted as either hundredths of a second (0.01 s base) or tenths of a second (0.1 s base) depending on the timer function block selected. The exact set of available counter and timer words depends on the CPU type and the configured area allocation in the system data word.
Three programming representations are supported in S5: Ladder Diagram (LAD/KOP), Control System Flowchart (CSF/FUP), and Statement List (STL/AWL). Quadriga supports all three, with the editor switching between representations only where the underlying logic allows it.
Quadriga Interface and Navigation Model
Quadriga is invoked from a DOS command line, typically with the program name and a project file argument. Once running, the user interacts through a top menu bar and a row of function-key shortcuts at the bottom of the screen. The most common key conventions are:
- F1 / Shift-F1 – context-sensitive help, also lists the available operations in the current program block type
- F2 – open file / load program from disk
- F3 – save the current program to disk
- F4 – begin a new ladder segment / network
- F5 – insert an element at the cursor (contact, coil, function block)
- F6 – delete the element at the cursor
- F7 – transfer program to PLC (PC → AG)
- F8 – transfer program from PLC (AG → PC)
- F9 – start online status / watch view
Function-key assignments can vary between Quadriga versions, so always confirm by pressing F1 at the top-level menu. If F1 lists the available functions, the version is consistent with the convention above. If the assignment is different, follow the on-screen F-key labels rather than assuming the defaults from memory.
Counter Programming: The COMP Pattern
The single most important behavior difference between timers and counters in S5 that catches new users coming from Mitsubishi is this: timer function blocks accept a preset (TW) value, but counter function blocks do not. A counter word (C) only ever holds the current count. It has no internal setpoint register.
To implement a counter with a preset in S5 you therefore combine two operations:
- A counter function block (CU, CD, or C) that increments or decrements the counter word on each input pulse
- A COMP (comparison) function block that watches the counter word and produces a boolean result when the count crosses the threshold you want
The COMP function is the standard S5 comparator. It evaluates two operands and outputs a logical 1 (signal state 1) when the comparison is true. The output of COMP is wired into a coil, a flag, or another operation just like any contact result.
Why the COMP pattern exists
This is not a Quadriga limitation. It is the underlying STEP 5 language. The S5 instruction set deliberately separates counting from comparison so that a single counter can drive multiple threshold outputs — e.g., one coil at 10 counts, another at 50 counts, a third at 100 counts — by simply duplicating the COMP block with different thresholds. If the counter had an internal preset, you would be limited to a single threshold per counter word.
Comparison Operators in Quadriga
The COMP function supports the standard set of S5 relational operators. In Quadriga, these are selected from a menu prompt or typed directly into the COMP block’s operand entry:
| Operator | Quadriga Symbol | Meaning | Result True When |
|---|---|---|---|
| == | = = | Equal | Operand A = Operand B |
| <> | >< | Not equal | Operand A ≠ Operand B |
| > | > | Greater than | Operand A > Operand B |
| >= | >= | Greater than or equal | Operand A ≥ Operand B |
| < | < | Less than | Operand A < Operand B |
| <= | <= | Less than or equal | Operand A ≤ Operand B |
Note the use of >< (two separate characters) as the display form of the not-equal operator in the S5 text representation. This convention is preserved in Quadriga menus and in any printed program documentation.
Step-by-Step: Adding a Counter with COMP in Quadriga
The following procedure assumes you are editing an existing program in Quadriga and want to add a counted-event output that activates once a counter has accumulated 10 pulses on an input.
Prerequisites
- Quadriga installed and configured for the COM port your S5 CPU is wired to (COM1 or COM2, 9600 baud, AS511 protocol)
- Working copy of the project file (.S5D or directory structure, depending on version)
- Verified current backup of the CPU program (F8 / read from PLC, save as a dated filename)
- Symbol table open with the inputs, outputs, counters, and flags you plan to use already named
Procedure
- Open the project. Press F2, navigate to the project directory, and load the program file. If you are working with a multi-block S5 program, identify the OB, PB, or FB block where the new counter logic will live — typically the same block that contains related I/O, or a free PB if you want to keep the change isolated.
- Navigate to an empty network. Use the page keys or the menu-driven Go To dialog to reach a network with free space at the right-hand rail. Press F4 to start a new network if needed.
-
Place the count input contact. Press F5 to insert, select a normally-open contact (NO / —|—), and assign it to the input bit that produces the pulse you want to count. For example, assign the contact to
I 0.1(input byte 0, bit 1) or to its symbolic name if one exists. -
Insert the counter function block. Press F5 again and select the counter function. In Quadriga the function is labeled simply as CU (count up), CD (count down), or C (count, with separate up/down inputs). Select CU for the common case. Assign the counter word to an unused counter, e.g.,
C 10. -
Place the COMP block. Press F5 and select the COMP function from the comparator list. Quadriga will prompt for the comparison operator; select
>=if you want the output to assert at the threshold and stay asserted, or==if you want a single-count pulse at exactly the target value. -
Enter the COMP operands. The COMP block has two operand fields. Fill them as:
- Operand 1: the counter word you used, e.g.,
C 10 - Operand 2: the threshold constant, e.g.,
KF +10(KF denotes a fixed-point constant in STEP 5)
- Operand 1: the counter word you used, e.g.,
-
Wire the COMP output. Place a coil (
—( )—) at the right-hand power rail and assign it to the output you want to drive, e.g.,Q 1.0or its symbol. Optionally also drive a flag (e.g.,F 20.0) so other networks can react to the threshold. -
Add a reset for the counter. Counters latch in S5; they hold their count value even after the count input stops. Add a separate network with a normally-open contact tied to your reset condition (a manual pushbutton input, a startup flag, or an end-of-cycle flag) wired into the CR (counter reset) function on
C 10. Without a reset path the counter will accumulate forever and your threshold logic will only ever fire once. - Document the network. Use the network comment field (typically Shift-F4 or the menu → Edit → Comment) to record what this network does, the counter number, the threshold, and the date of the change. The S5 is famously under-documented, and the engineer who maintains the machine next will thank you.
- Save the file. Press F3 to save. Then compile the block (the menu path is typically Program → Compile, or the shortcut Ctrl-F9 in some Quadriga versions) to produce the machine code that the CPU understands.
- Transfer to the CPU. Connect the programming cable, ensure the CPU is in STOP with the key switch, and press F7 (or the equivalent PC → AG menu item) to download the modified block. Watch the transfer log for errors.
- Switch to RUN and test. Turn the key switch to RUN. Use F9 / status view to watch the counter word increment on each input pulse, and verify the output energizes at the threshold value.
KF +10 constant format is correct for STEP 5 / Quadriga. KF is the fixed-point (16-bit signed) constant prefix. Do not use KFx notation — Quadriga expects a space between the prefix and the value. A common typo, KF+10 without the space, is silently accepted but is bad practice and trips up syntax-aware STEP 5 compilers.Working with Timers vs Counters
If you arrived at counter logic by first building a timer-based solution (a common workaround when the counter/preset pattern is not yet understood), the following table summarises the behavioral differences you will need to address when migrating to the proper counter+COMP pattern.
| Aspect | S5 Timer (SP, SE, SD, SS, SF, SA) | S5 Counter (CU/CD) + COMP |
|---|---|---|
| Preset support | Built into the timer block via the TW operand | No built-in preset; implemented via COMP against KF constant |
| Trigger source | Time base (0.1 s or 0.01 s) multiplied by TW | Any boolean signal edge wired to the CU/CD input |
| Reset | Automatic when input goes low (for SP pulse timer); or R input for retentive timers | CR function must be wired explicitly; counter holds its value otherwise |
| Retention across power cycle | Not retained by default (timer word clears on STOP/RUN transition) | Retained if the counter word is configured as retentive in the system data; otherwise also cleared |
| Output behavior | Output of timer block is its Q (done) bit | Output is the COMP result wired to your coil |
| Best used for | Time-based delays, watchdog timeouts, debounce | Event counting, batch totals, position pulses, batch-out triggers |
Rule of thumb: if the parameter you are comparing is a number of events (parts, cycles, pulses, button presses), use a counter. If the parameter is a duration, use a timer. Do not try to fake a count with a slow timer pulse — the substitution is fragile, drifts with CPU scan time, and is hard to read in code review.
Verification and Commissioning
Once the modified block has been transferred to the CPU, verify the logic in a controlled sequence before restoring production. The recommended order is:
- Force the count input manually. Use the machine’s manual/jog controls to produce one pulse at a time, or use Quadriga’s status view to force the input bit high and low. Watch the counter word increment by exactly one per pulse. If it increments by more than one per pulse, the input is not debounced — add a timer-based debounce network feeding the CU input.
-
Confirm the threshold trip. Pulse the input until the counter crosses the threshold you configured in COMP. Verify that the target output or flag transitions to 1 at exactly the right count. For a
>=comparison, the output should assert at the threshold count and stay asserted on subsequent counts. - Test the reset path. Activate your reset condition. Confirm that the counter word returns to 0 and that any output driven by the COMP result drops off appropriately. If the output remains stuck on after reset, the COMP block is being driven by a flag that was latched separately — add a reset network for that flag as well.
-
Test the boundary cases.
- Threshold = 1: confirm the output asserts on the first pulse and resets on reset.
- Threshold = 999 (max BCD): confirm the counter does not roll over silently — S5 counters saturate at 999, they do not wrap to 0, but the COMP result will be permanently true above 999 and any reset network becomes critical.
- Threshold = 0: this is technically valid but trivially true at all times after the first pulse. Use it deliberately (e.g., to flag “any count has occurred”) or rewrite as a direct input edge detector.
- Cycle the CPU. Stop and restart the CPU. If the counter is configured as retentive, the value should survive; if not, it should reset to 0. Verify the behavior matches the machine’s operational expectations. If retention is desired and missing, change the system data word to flag the counter word as retentive, then re-transfer the system data block.
- Run a full operational cycle. Put the machine through one complete production cycle under normal operator control. Confirm that the counter logic interacts correctly with the surrounding program — in particular, that no other network is also writing to the same counter word, and that no other network is also writing to the output you are now driving.
Common Issues and Field Notes
The following matrix captures the most frequent failure modes encountered when adding a counter to an S5 program in Quadriga, with the underlying cause and the recommended corrective action.
| Symptom | Likely Cause | Corrective Action |
|---|---|---|
| Counter never increments | CU input is wired to a constant 1 instead of the actual input bit | Rewire the contact to the correct input operand, or to a flag that follows the input |
| Counter increments by 2 or more per pulse | Input is not debounced; mechanical contact bounce is producing multiple edges | Add a 50–100 ms SE (pulse-extended timer) debounce network feeding the CU input |
| Counter increments in STOP | Counter is being driven by a flag that is also being set somewhere else on every scan | Audit the symbol table; identify all writers to the driving flag and gate the count input |
| Output never asserts even though counter reaches the threshold | COMP operator is the wrong direction (e.g., < instead of >=) | Open the COMP block and re-select the operator; the choice is shown at the top of the block |
| Output asserts briefly then drops | COMP operator is == (equal) and the counter is being incremented past the target by another part of the program | Switch the operator to >= so the output latches as long as the threshold is met |
| Counter holds its value forever; never resets | CR (counter reset) function is not wired in the program | Add a CR network driven by the appropriate reset condition (cycle end, manual button, homing flag) |
| Quadriga reports syntax error on COMP operand | Missing KF prefix on the constant, or typo in the constant (e.g., comma instead of space) | Re-enter as KF +10 with a single space between prefix and value |
| Download to CPU fails with “Block not in AG” | The block was not compiled before transfer, or was compiled against a different CPU type | Re-compile (Ctrl-F9) and re-transfer; confirm the CPU type matches the project’s target |
| Counter value is 0 after every power cycle | Counter word is not configured as retentive in the system data | Edit the system data block, set the counter word’s retention flag, and re-download system data |
| Counter value freezes partway through scan | Some other OB/PB/FB is writing to the same counter word, overwriting your value | Search the project for all references to the counter word; consolidate to a single writer |
Migrating Away from Quadriga
Quadriga is a maintenance tool, not a development platform for new machinery. If the S5 systems you are maintaining will be in service for more than another 2–3 years, plan a migration to the S7-300 / S7-400 family (using STEP 7 V5.5) or to the S7-1500 (using TIA Portal). The Siemens S5 to S7 migration guide, available through the Siemens Industry Online Support portal, documents the symbol mapping and program conversion utility. When migrating a counter+COMP pattern, the S7 equivalent is a single CTU (count up) IEC timer/counter block with a PV (preset value) input — the behavior you have been emulating in S5 with two separate blocks is native to a single S7 block.
For documentation purposes, when handing over a system that is about to be migrated, ensure the Quadriga project includes:
- A printed symbol table with all inputs, outputs, flags, timers, and counters named
- Network comments on every network added or modified
- A change log recording the date, the engineer, and the purpose of each modification
- A backup of the compiled block on the engineering PC and on a separate media (USB, CD, network share)
This is the difference between an S5 program that can be converted in an afternoon and one that requires a full week of reverse engineering to understand.
What is Quadriga and who sells it?
Quadriga is a DOS-based programming environment for Siemens S5 PLCs, distributed in the United Kingdom by Pantek — the same channel that marketed Wonderware InTouch at the time. It is a third-party maintenance tool, not a Siemens product, and is best treated as an editor for existing S5 program files rather than a primary development environment.
Why do S5 counters not have a preset like timers do?
Counters in STEP 5 (and therefore in Quadriga) store only the current count in the counter word; they have no internal setpoint register. A preset must be implemented externally with a COMP (compare) function block, which evaluates the counter word against a KF constant and produces a boolean result. This design lets a single counter drive multiple thresholds, each via its own COMP block.
Which comparison operators does the COMP function support in Quadriga?
Six relational operators: == (equal), >< (not equal), > (greater than), >= (greater than or equal), < (less than), and <= (less than or equal). The >< display form is the STEP 5 text representation of not-equal, preserved in Quadriga menus and printed documentation.
Can Quadriga program Siemens S7 PLCs?
No. Quadriga targets the S5 family only. For S7-300 and S7-400 use STEP 7 V5.5; for S7-1200 and S7-1500 use TIA Portal. If you need to migrate an S5 program to S7, Siemens provides a conversion utility and a migration guide through the Industry Online Support portal.
How do I reset a counter in S5 after it has reached its threshold?
Add a CR (counter reset) function block wired to a contact that reflects your reset condition — a manual pushbutton, a cycle-end flag, or a startup flag. S5 counters hold their value once the count input stops, so without an explicit CR network the counter will accumulate indefinitely and any threshold driven by COMP will only ever fire once.