Resetting SIMATIC MP 177 6" Touch HMI to Factory Defaults

David Krause11 min read
HMI / SCADASiemensTutorial / How-to
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Overview

The SIMATIC MP 177 6" Touch is a multi-panel operator interface from the Siemens HMI product line that was originally commissioned with WinCC flexible 2008 and is supported for backup/restore operations through the ProSave service tool. When the runtime project becomes corrupted, the password is lost, or the panel is being redeployed to a different machine, performing a factory reset via ProSave is the cleanest way to return the device to its as-shipped state without physical disassembly.

This procedure documents the full reset workflow for the 6" Touch variant, including image file location, Ethernet/serial prerequisites, ProSave configuration parameters, and the commissioning verification steps that confirm a clean restore. The instructions are valid for both WinCC flexible 2008 SP5 and earlier service packs, and apply whether ProSave is launched standalone or from inside the WinCC flexible engineering environment.

Variant identification is critical. The Siemens MLFB (order number) printed on the rear label determines which image package is required. The user's panel carries MLFB 6AV6642-5EA10-0CG0, which is distinct from the catalog number 6AV6642-0EA01-3AX0 listed on the manufacturer product support page. Both are SIMATIC MP 177 6" Touch units, but they are configured with different firmware/feature sets, and the image file must match the exact variant in use. Verify the MLFB on the rating plate (back of the unit) before proceeding.

Identifying Your MP 177 Variant

Siemens released the MP 177 family in several sub-variants differentiated by display size, touch vs. key operation, and firmware feature set. The 6" Touch version is identified by an MLFB beginning with 6AV6642. The two catalog numbers relevant to this procedure are:

MLFB Designation Notes
6AV6642-5EA10-0CG0 SIMATIC MP 177 6" Touch (user's unit) Color TFT, touch screen, WinCC flexible 2008 SP2+ compatible
6AV6642-0EA01-3AX0 SIMATIC MP 177 6" Touch (alternate catalog) Listed on the official Siemens product support entry; image package bundled with WinCC flexible

The full Siemens product support entry for the MP 177 6" Touch is located at the Siemens Industry Online Support product page. Cross-reference the MLFB on your rating plate to the product tree to confirm firmware revision and image compatibility before initiating a restore.

Prerequisites

Before initiating a factory reset on the MP 177 6" Touch, verify that the following hardware, software, and cabling prerequisites are satisfied.

  1. ProSave installation. ProSave is shipped with every WinCC flexible DVD or download package. If WinCC flexible is not installed, ProSave can be installed standalone from the WinCC flexible installation media under Additional Products > ProSave. The version of ProSave must be at least the same major release as the image package (typically 2008 SPx).
  2. Image file (*.img). The factory image for the MP 177 6" Touch is named MP177.img and is bundled inside the WinCC flexible install directory. The default location for a standard WinCC flexible 2008 SP5 installation is: C:\Program Files (x86)\SIEMENS\SIMATIC WinCC flexible\WinCC flexible Images\MP177\ If the directory is empty, the image is not installed; rerun the WinCC flexible setup and select the MP 177 option under the device package list.
  3. Ethernet or RS232 connection. ProSave can transfer the image over Ethernet (recommended) or over an RS232 point-to-point link. For Ethernet, use a standard Cat5/Cat6 patch cable connected to the MP 177's RJ45 port and to the engineering PC. For RS232, use a Siemens 6ES7 901-1BF00-0XA0 PC/PPI cable (or compatible) wired into the panel's IF1B port.
  4. Network configuration. If transferring over Ethernet, both the PC and the MP 177 must reside on the same subnet. The MP 177's default transfer mode is Ethernet with DHCP disabled; assign a static IP through the panel's Control Panel before the restore.
  5. Administrative rights. ProSave must be run with Windows administrator privileges to open raw sockets and bind to low-numbered ports required for the transfer protocol.
  6. Power supply. The panel must have a stable 24 V DC supply; a brownout during image write will brick the device. Verify supply voltage at the terminals is between 20.4 V and 28.8 V DC before starting.

Configuring the MP 177 for Restore

ProSave requires the panel to be in Transfer mode. On the MP 177, transfer mode is invoked from the Control Panel.

  1. Power on the panel and wait for the runtime to finish loading. If the runtime is corrupted and the panel hangs at boot, hold the Hold key combination described in the device manual until the loader appears, or cycle power three times in succession to force the loader menu.
  2. Press the Control Panel button on the desktop, or call the loader from a serial-console boot if the touchscreen is unresponsive.
  3. Open OP (Operator Panel) Properties > Transfer.
  4. Set the channel to Ethernet (or Serial if using RS232). Note the assigned IP address. If no IP is set, configure a static address, for example 192.168.1.1, with subnet mask 255.255.255.0.
  5. Confirm the change. The panel will prompt to restart; allow the restart so transfer mode is active before launching ProSave.
If the panel displays a "Transfer not permitted" message, the runtime project has the transfer channel locked. Factory-resetting the image is the only way to clear this flag, so proceed directly to the ProSave step below.

Locating the Factory Image File

The factory image is the bit-for-bit snapshot of the MP 177's flash, including bootloader, firmware, and default runtime. ProSave writes this image to the panel during a restore operation. The image is not a download from the Siemens support site by default; it is shipped with the WinCC flexible installation media.

Standard Windows installation path

For a default installation of WinCC flexible 2008 SP5 on Windows 7 / Windows 10 (x86 compatibility layer), the image is located at:

C:\Program Files (x86)\SIEMENS\SIMATIC WinCC flexible\WinCC flexible Images\MP177\MP177.img

For 64-bit systems where the legacy installer was redirected, check:

C:\Program Files\SIEMENS\SIMATIC WinCC flexible\WinCC flexible Images\MP177\MP177.img

Verifying the image

Confirm the file size matches the expected factory image. For the MP 177 6" Touch the image is typically between 12 MB and 18 MB depending on the service pack revision. If the file is smaller than 5 MB or zero bytes, the install was incomplete and must be re-run with the MP 177 device package selected.

Extracting the image from the WinCC flexible DVD

  1. Insert the WinCC flexible 2008 installation DVD.
  2. Browse to ImagePackages\MP177.
  3. Copy MP177.img to a local working directory, e.g. C:\Restore\MP177\.

Exporting from a TIA Portal configuration

The official Siemens entry 109746530 describes a tool to export graphics from the "Graphics Collection" of a WinCC (TIA Portal) configuration for editing with an image processing program. This tool does not produce the panel's factory image; it produces bitmap assets embedded in a TIA Portal project. To restore the panel firmware, use the WinCC flexible-bundled image as described above.

Restoring the Image with ProSave

With the panel in transfer mode and the image file located, launch ProSave and execute the restore.

  1. Start ProSave from Start > Siemens Automation > SIMATIC > ProSave. Run as administrator.
  2. In the General tab, set Device type to MP 177 Touch (or the specific sub-variant if listed). Set Connection to Ethernet (or Serial).
  3. For Ethernet, enter the panel's IP address in the IP address / Name field. Leave the port at default 2305 unless a firewall has remapped it.
  4. Click Connect. ProSave will report "Connection established" once the panel handshake completes. If the connection fails, see the troubleshooting matrix below.
  5. Switch to the OS Update tab (also labeled Operating System Update in older builds).
  6. Browse to the image file path, e.g. C:\Program Files (x86)\SIEMENS\SIMATIC WinCC flexible\WinCC flexible Images\MP177\MP177.img.
  7. Confirm the dialog "Image <MP177.img> will be written to the panel. All data on the panel will be overwritten. Continue?".
  8. Click Update OS. The transfer takes 3 to 8 minutes depending on connection type and image size. Do not cycle power.
  9. ProSave reports "Operating system update successful" when the write is complete.
  10. Reboot the panel from the loader menu or by cycling 24 V DC power.

Command-line alternative

ProSave supports a scripted / silent mode for fleet rollouts. The relevant parameters are:

ProSave.exe /Connect /Device="MP 177 Touch" /IP=192.168.1.1 /Restore /Image="C:\Restore\MP177\MP177.img" /Reboot

The /Reboot switch forces a panel restart at the end of the transfer. Wrap the call in a batch file for repeated deployments.

Alternative Method: TIA Portal

WinCC flexible and ProSave are the supported path for the MP 177 6" Touch. TIA Portal can be used in some scenarios, but with significant caveats.

Siemens support article 109746530 covers TIA Portal-based management of legacy panels. However, TIA Portal V15 and later do not support the MP 177 panel family; the device is excluded from the TIA Portal device catalog starting with V15. For users on TIA Portal V13 SP2 or V14, the panel can be migrated to a TIA Portal project and deployed via TIA Portal's built-in transfer, which uses the same ProSave engine under the hood.

Use TIA Portal only when the engineering environment is already standardized on TIA Portal and the project has been migrated. For a pure factory reset to the original WinCC flexible image, ProSave is the authoritative tool.

Verification

After the restore completes and the panel reboots, perform the following verification checks to confirm the reset is clean.

  1. Loader screen. The panel should boot directly to the WinCC flexible loader desktop (blue header) rather than the corrupted runtime.
  2. Control Panel > OP Properties > Device. Verify the device name, MLFB, and firmware version match the rating plate. A clean restore shows the original firmware string (e.g. WinCC flexible 2008 SP5).
  3. Transfer settings. Confirm the transfer channel and IP address are as configured in the prior step. The default after a factory reset is transfer enabled on Ethernet.
  4. Runtime launch test. Load a known-good WinCC flexible project via ProSave > Transfer and confirm the project starts without error.
  5. Touch calibration. From the Control Panel, run OP Properties > Touch > Calibrate and verify all four corner targets respond accurately.
  6. System event log. Check Control Panel > Diagnostics > System Log for any post-restore errors. A clean restore produces no entries during boot.

Troubleshooting Matrix

Symptom Likely Cause Corrective Action
ProSave reports "Device not found" Panel not in transfer mode, or wrong IP Confirm Control Panel > Transfer is set to Ethernet with the correct IP. Ping the panel from the PC.
ProSave reports "Connection refused" on port 2305 Windows firewall blocking transfer port Allow ProSave through Windows Defender Firewall on private networks. Add inbound rule for TCP 2305.
OS Update fails at 5% with timeout Image file corrupt or wrong variant Verify MLFB on the panel label. Re-copy image from the WinCC flexible install media. Compare MD5 against a known-good source.
Panel stuck at white screen after reboot Power interruption during flash write Repeat the ProSave OS Update. The loader persists even if the runtime partition is corrupted.
Touch response offset or rotated 90° Touchscreen calibration lost Recalibrate from Control Panel > Touch > Calibrate. If the loader is inaccessible, perform another restore with ProSave to reset the touch parameters to defaults.
Image directory empty after WinCC flexible install Device package not selected during setup Rerun WinCC flexible setup, choose Modify, and select the MP 177 device package under HMI Devices.
WinCC flexible 2008 install fails on Windows 10 32-bit only installer; compatibility mode needed Run setup in Windows 7 compatibility mode as administrator, or install on a Windows 7 / Windows Server 2008 R2 host.

Field-Proven Tips

When performing the restore in a production environment, the following practices reduce the risk of bricking a panel or losing the only copy of a project.

  • Back up before reset. Always perform a ProSave Backup of the existing image before running the OS Update. The backup file is the only way to recover a project that has not been saved elsewhere.
  • Stage the image locally. Copy the MP177.img to a local SSD rather than reading it from an optical drive or network share. A flaky read mid-write will produce a bricked panel.
  • Document the MLFB on the panel. Photograph the rating plate before the reset. The 6AV6642 family has multiple sub-variants and the image must match.
  • Validate the 24 V supply. Measure supply voltage at the panel terminals with a multimeter before the update. A sagging supply during flash write is the single most common cause of post-restore boot failures.
  • Keep the loader reachable. If the touchscreen is non-responsive, the loader can be invoked from the loader menu after a triple power cycle (on/off/on/off/on) on most MP 177 firmware revisions.

Documentation References

The following Siemens Industry Online Support resources are authoritative for this procedure:

Where is the factory image file for the MP 177 6" Touch located?

On a default installation of WinCC flexible 2008 SP5, the image MP177.img is located at C:\Program Files (x86)\SIEMENS\SIMATIC WinCC flexible\WinCC flexible Images\MP177\. If the directory is empty, rerun the WinCC flexible setup and select the MP 177 device package to install the image.

Which ProSave connection mode should I use, Ethernet or RS232?

Ethernet is recommended for speed and reliability. Use a static IP (for example 192.168.1.1 on the panel and 192.168.1.10 on the PC) with subnet mask 255.255.255.0, and ensure Windows firewall allows ProSave on TCP port 2305. Use RS232 only when the panel's Ethernet port is damaged or the panel will not boot into the loader over Ethernet.

Can I use TIA Portal to factory reset the MP 177?

No, TIA Portal V15 and later do not support the MP 177 panel family. Use ProSave with the WinCC flexible 2008-bundled MP177.img for a clean factory reset. TIA Portal V13 SP2 and V14 can deploy to a migrated MP 177 project, but the underlying transfer still uses the same ProSave engine.

What should I do if the panel is stuck at boot and the touchscreen is unresponsive?

Cycle power three times in succession to invoke the loader menu. From the loader you can enable transfer mode and run ProSave against the panel over Ethernet or RS232 without needing touchscreen input.

How long does a factory image restore take on the MP 177?

Over Ethernet a full OS update typically completes in 3 to 5 minutes. Over RS232 the same transfer can take 8 to 12 minutes. Do not cycle power during the write; a brownout during flash programming will corrupt the panel firmware.