Problem Overview
A SIMATIC ET 200SP distributed I/O station equipped with a CM PtP communication module (order number 6ES7137-6AA00-0BA0, or the -0CA0 / -0DA0 variants for RS-232/422/485) appears to accept the Modbus_Comm_Load and Modbus_Master programming blocks without generating any hardware fault, but the Modbus link to the RTU slave (in this case a LUMEL energy meter) never establishes. Two distinct return codes are observed on the STATUS output:
- Modbus_Comm_Load.STATUS = 7000 (hex 0x1B58) persistently, even when the block is called in the startup OB (OB100) on the first cycle.
- Modbus_Master.STATUS = 7000 when BUSY = FALSE, and STATUS = 7002 (hex 0x1B5A) while BUSY = TRUE during a transmission attempt.
External verification with a MOXA USB-to-RS-485 converter and Modbus Poll confirms that the slave itself is healthy and the 2-wire RS-485 bus is wired correctly. The CM PtP is the only suspect. The root cause is almost always a physical-layer mismatch: the module is driving the socket in RS-232 mode while the user is wiring it as RS-485, or vice versa. The user-side fix is to commit the correct physical mode by writing the MODE input of Modbus_Comm_Load and re-triggering REQ.
Affected Components and Firmware
| Component | Order Number / Designation | Relevant FW |
|---|---|---|
| ET 200SP CM PtP (RS-232/422/485) | 6ES7137-6AA00-0BA0 | FW V2.0 and later |
| ET 200SP CM PtP (RS-232) | 6ES7137-6AA01-0BA0 | FW V1.0+ |
| ET 200SP interface module | 6ES7155-6AUxx / 6ES7155-6BUxx (PROFINET / PROFIBUS) | n/a |
| CPU used as PROFINET IO controller | S7-1200 (CPU 121x) or S7-1500 (CPU 15xx) | FW V4.2+ (S7-1200), V2.0+ (S7-1500) |
| TIA Portal | V16 / V17 / V18 | Modbus RTU library >= V4.0 |
The condition has been observed on TIA Portal V15.1 through V18 with the Modbus RTU instruction library "MB_RTU" / "MB_CLIENT" variants. The exact return code values (decimal) are stable across the listed firmware revisions because they are part of the PtP block status list defined in the Siemens Modbus_Comm_Load instruction reference.
Decoding Status 7000 and 7002
The Modbus_Comm_Load and Modbus_Master return a hex-coded status. Always inspect them in HEX, because the decimal form is misleading at first glance.
| Code (dec) | Code (hex) | Meaning in PtP context | Likely cause |
|---|---|---|---|
| 7000 | 0x1B58 | No job currently active / port not yet parameterised | Modbus_Comm_Load has never been called successfully, or REQ has never been edge-detected. Physical layer not committed. |
| 7001 | 0x1B59 | Modbus_Comm_Load is processing the request | Normal transient state. Should clear within one scan. |
| 7002 | 0x1B5A | Modbus_Master waiting for response, or Modbus_Comm_Load finished with a non-fatal condition (CTS not asserted, DCD not ready) | Hardware handshake issue, or RS-232 physical layer still selected while RS-485 is wired (or vice versa). |
| 80C8 / 80C9 | 0x80C8 / 0x80C9 | Block ID / instance DB length invalid | Instance DB was regenerated to a different length after a library swap. |
STATUS = 7000 on Modbus_Comm_Load after OB100, the port configuration was never written to the CM PtP. Do not troubleshoot the slave until the load block returns 7001 (DONE = TRUE) at least once.
Root Cause: Default RS-232 Physical Layer
Out of the box, the ET 200SP CM PtP is shipped with the device configuration parameter "Operating mode" set to RS-232 full duplex. This is also the default that the engineering tool writes when you first drop the module into the device view. Pin 1 (TxD) and pin 2 (RxD) of the sub-D socket carry voltage, while pins 12 / 14 (the RS-485 data pair on this family) are held at the line-idle bias but no driver is enabled.
Symptoms that confirm this is the failure mode:
- MOXA or any USB-to-RS-485 tap on pins 12 / 14 shows no traffic LEDs when the CM PtP runs the load block.
- Probing pins 1 / 2 on an oscilloscope reveals the expected Modbus RTU frames.
- When you short the CM PtP side to the MOXA side, the MOXA RX/TX LEDs flash because it is receiving and echoing RS-232, not RS-485.
- Modbus_Master
STATUSswings to 7002 the moment REQ is pulsed, because the transmitter is enabled but the receiver never sees a return frame (because the LUMEL meter is on a 2-wire RS-485 bus and the CM is driving TxD/RxD separately).
The configuration page in TIA Portal that is normally expected to switch the physical layer is Properties > Port configuration > Operating mode / Protocol. In some TIA Portal / library combinations (specifically Modbus RTU library V4.x for CM PtP), this checkbox does not propagate to the load block. The block carries its own copy of the mode, and the block wins.
CM PtP Module Hardware Reference
The CM PtP front connector is a 15-pin D-sub male. Pinout for the RS-232 / RS-422 / RS-485 modes:
| Pin | RS-232 | RS-422 (4-wire full duplex) | RS-485 (2-wire half duplex) |
|---|---|---|---|
| 1 | TxD (out) | TxD+ (B) | Data+ (B) driver / receiver combined |
| 2 | RxD (in) | RxD+ (B) | (internally tied to pin 1 in 2-wire) |
| 5 | RTS (out) | RTS+ (B) | n.c. |
| 6 | CTS (in) | CTS+ (B) | n.c. |
| 9 | DCD (in) | CTS- (A) | n.c. |
| 11 | DTR (out) | RTS- (A) | n.c. |
| 12 | n.c. | TxD- (A) | Data- (A) driver / receiver combined |
| 14 | n.c. | RxD- (A) | (internally tied to pin 12 in 2-wire) |
| 4, 8, 13 | GND | GND | GND |
For a LUMEL ND10 / N14 / N30 energy meter (or any 2-wire RS-485 slave), the only signal pins that matter are 1/2 and 12/14 in 2-wire mode, plus GND. Verify with a multimeter in continuity mode: pin 1 short to pin 2 and pin 12 short to pin 14 will appear when the module is correctly configured for 2-wire RS-485.
Modbus_Comm_Load Configuration Parameters
The complete input pin map for the Modbus_Comm_Load block when targeting a CM PtP under PROFINET is given in the TIA Portal Modbus_Comm_Load manual page:
| Input | Type | Meaning |
|---|---|---|
| REQ | BOOL | Edge-triggered: a rising edge writes the configuration to the port. |
| PORT | HW_PORT / UINT | Hardware identifier of the CM PtP sub-module. |
| BAUD | DINT | Baud rate as numeric value: 9600, 19200, 38400, 115200, etc. |
| PARITY | DINT | 0 = None, 1 = Odd, 2 = Even. |
| FLOW_CTRL | DINT | 0 = None, 1 = XON/XOFF (RS-232 only), 2 = Hardware RTS/CTS (RS-232 only). |
| RTS_ON_DLY | DINT | RTS pre-delay in ms; typically 0 for RS-485. |
| RTS_OFF_DLY | DINT | RTS post-delay in ms; typically 0 for RS-485. |
| RESP_TO | DINT | Response timeout in ms (e.g. 1000). |
| MODE | DINT / UINT | Physical-layer / role selector (see below). |
The MODE parameter is the only one that is unintuitively named. For the ET 200SP CM PtP it carries the following semantics, in the Modbus RTU instruction library variants V3.x and V4.x:
| MODE value | Function |
|---|---|
| 1 | RS-232 full duplex (the default after cold start). |
| 2 | RS-422 full duplex, 4-wire. |
| 3 | RS-485 half duplex, 2-wire, Modbus RTU master. |
| 4 | RS-485 half duplex, 2-wire, Modbus RTU slave. |
Step-by-Step Resolution
- Open the S7 CPU program in TIA Portal and locate the instance DB of
Modbus_Comm_Loadin the project tree. - Set
PORTto the hardware identifier of the CM PtP. In the project navigation, open Device view > CM PtP > Properties > System constants and copy the symbolic name (e.g."CM_PtP_1~PORT_1"). - Set the MODE input explicitly. For a 2-wire RS-485 link to a LUMEL energy meter where the CM PtP is the Modbus RTU master, use:
If the original symptom was 7000/7002 and the user found relief with MODE = 4, verify the actual role: in some field installations the CM PtP is a slave to a higher-level gateway and the LUMEL is a passive listener. In that case:Modbus_Comm_Load.MODE := 3; // RS-485 half duplex, master roleModbus_Comm_Load.MODE := 4; // RS-485 half duplex, slave role - Keep the remaining parameters at safe values:
Modbus_Comm_Load.BAUD := 9600; Modbus_Comm_Load.PARITY := 2; // Even, matches most LUMEL defaults Modbus_Comm_Load.FLOW_CTRL := 0; // No hardware handshake on RS-485 Modbus_Comm_Load.RESP_TO := 1000; // 1 second, generous for slow meters - Force a positive edge on
REQ. In SCL:IF "FirstScan" THEN Modbus_Comm_Load_Instance.REQ := TRUE; END_IF; // In OB1 or a cyclic OB, drop REQ after DONE is seen: IF Modbus_Comm_Load_Instance.DONE OR Modbus_Comm_Load_Instance.ERROR THEN Modbus_Comm_Load_Instance.REQ := FALSE; END_IF; - Download the program to the CPU. Cold-restart the CPU (MRES) so the CM PtP re-initialises with the new MODE. A warm restart will keep the previously latched physical layer if the configuration was already committed once.
- Watch the
STATUSoutput. After a single scan,STATUSmust transition 7000 -> 7001 -> 7000 withDONE = TRUE. If 7000 persists, the REQ edge was lost (the block is edge-triggered, not level-triggered) or the PORT identifier is wrong. - Now trigger the Modbus_Master block. The first valid poll will return 7000/7001, and within
RESP_TOms the slave reply will setDONE = TRUEwith the requested register values in the output buffer.
Verification Procedure
- Open the online watch table for the Modbus_Master instance DB. Confirm:
-
BUSYtoggles TRUE for the duration of the request. -
DONEpulses TRUE one cycle after the reply arrives. -
ERRORstays FALSE.
-
- Compare the received holding-register payload (e.g. the 32-bit floating-point value of kWh) with a hand-held reading from the LUMEL meter's local display. The two must match to within the resolution declared by the meter's datasheet.
- Capture the bus on a scope or an inexpensive USB tap. Verify the voltage swing on pins 12/14 is at least +/- 1.5 V differential (RS-485 spec allows +/- 200 mV receiver threshold, +/- 1.5 V driver minimum, with the CM PtP at +/- 3.3 V typical). A flat line or inverting-only signal indicates the line is still in RS-232 mode.
- Power-cycle the entire station (CPU + IM + CM PtP + slave). The link must come up automatically after the cold start. If it does not, the Modbus_Comm_Load call is missing from OB100.
Diagnostic Matrix
| Symptom | Likely cause | Fix |
|---|---|---|
| STATUS 7000 permanently on Modbus_Comm_Load | REQ never edge-detected, or PORT identifier wrong, or MODE invalid | Edge-trigger REQ in OB100; double-check HW identifier; set MODE to 3 or 4 explicitly. |
| STATUS 7000 -> 7001, but 7002 on Modbus_Master | Physical layer mismatch; CTS/RTS handshake expected on RS-485; slave not on the bus | Set FLOW_CTRL = 0; verify the differential pair polarity (A on pin 12 / 14, B on pin 1 / 2); check terminator resistor (120 ohm) at both ends. |
| STATUS 80C8 / 80C9 | Instance DB overwritten by a different library version | Recompile the block; delete the instance DB; recreate it from the new block version. |
| STATUS 80C4 (timeout) | Slaves never respond | Check RESP_TO > 3.5 character time; verify slave address in the Master request matches the meter. |
| Pin 1 and pin 2 active, pin 12 and pin 14 silent | Module is in RS-232 mode | Set MODE = 3 (master) / 4 (slave) per the table above and re-issue REQ. |
| Both pairs active but inverting polarity | A / B swapped at the slave | Swap the data wires at the LUMEL terminal; do not swap at the CM PtP, since internal bias is referenced. |
Wiring and Termination Best Practices
- Use a twisted pair for the 2-wire RS-485 link. Shielded cable is recommended in panels with VFDs or servo drives within 200 mm of the run.
- Install a 120 ohm terminator at both ends of the bus. The CM PtP does not provide internal termination; add it at the D-sub connector backshell or at the LUMEL terminal block.
- Add a 10 kohm pull-up on the B line (pin 1) to +5 V and a 10 kohm pull-down on the A line (pin 12) to GND, at the master end only, if the meter is known to be a passive listener (no fail-safe bias).
- Ground the shield at one end only to avoid ground loops. CM PtP backshell must be metallically bonded to the DIN-rail grounding bar.
- Maximum stub length: 0.3 m from the trunk to the meter. The LUMEL energy meters are usually daisy-chained; do not branch into a star.
Common Pitfalls and Counter-Intuitive Behaviour
- The device configuration checkbox does not always win. In TIA Portal, the Operating mode dropdown in Properties > Port configuration writes the default that survives a project re-download. The runtime MODE input on Modbus_Comm_Load, however, overrides it after the first call. If you set the dropdown to RS-485 and still see RS-232 traffic, the runtime MODE has been left at its default (1) and is overriding the project setting.
- Cold restart is mandatory after changing MODE. A simple STOP -> RUN transition does not reset the port register inside the CM PtP. Use MRES or power-cycle.
- REQ must be edge-triggered. Holding REQ = TRUE continuously does not re-parameterise the port every cycle; it only writes once. After a parameter change, you must drop REQ to FALSE and bring it back to TRUE.
- Two-wire and four-wire share pins. On the CM PtP socket, pin 1 and pin 12 are the "A" side and pin 2 and pin 14 are the "B" side. Modbus RTU uses pins 12 and 14 as the differential pair. Do not assume pin 1/2 are always the right place to land a wire just because they are labelled in the diagram.
- The slave address must be set on the meter. A Modbus poll for unit 1 against a meter addressed to unit 2 will return 7002 + ERROR with no slave reply; the port is functioning correctly, but the meter is silently ignoring the frame.
What does Modbus_Comm_Load STATUS 7000 mean on the ET 200SP CM PtP?
STATUS 7000 (hex 0x1B58) means the load block has never successfully written a configuration to the CM PtP. The most common cause is a missing rising edge on REQ or an uninitialised MODE input. Force a one-shot REQ in OB100, set MODE = 3 (master) or MODE = 4 (slave) explicitly, and cold-restart the CPU.
Why does the CM PtP default to RS-232 even though I selected RS-485 in TIA Portal?
On first project creation, the CM PtP physical layer defaults to RS-232 full duplex (MODE = 1). TIA Portal writes the dropdown selection to the device configuration, but the Modbus_Comm_Load block carries its own MODE register that overrides the engineering setting at runtime. Set the MODE input of Modbus_Comm_Load to 3 (RS-485 master) or 4 (RS-485 slave) and re-trigger REQ.
Should I use MODE = 3 or MODE = 4 for a LUMEL energy meter?
Use MODE = 3 when the CM PtP is the Modbus RTU master polling the LUMEL meter as a slave. Use MODE = 4 only when the CM PtP is itself a slave to another master on the bus. Mixing the roles results in the CM PtP either transmitting frames that the LUMEL cannot answer (master wrong) or staying silent on a polled bus (slave wrong).
My CM PtP shows 7002 on Modbus_Master but 7000 on Modbus_Comm_Load. Is the load block failing?
No. STATUS 7000 on Modbus_Comm_Load with DONE = TRUE is the normal "idle" state, indicating the port is correctly parameterised. STATUS 7002 on Modbus_Master with BUSY = TRUE is the normal "waiting for reply" state. The combination means the bus is live but the slave is not yet answering. Verify slave address, parity, baud rate, and differential pair polarity at the meter terminal.
Do I need a 120 ohm terminator on the CM PtP RS-485 bus?
Yes, at both ends. The CM PtP does not provide internal RS-485 termination. Place 120 ohm between pins 12 and 14 (A and B) at the D-sub connector backshell and at the last LUMEL meter on the trunk. Add a 10 kohm fail-safe bias (B pulled to +5 V, A pulled to GND) at the master end if the meter does not include bias internally.