Resolving LOGO! 8 FS4 (0BA8) HMI Simulation Communication Failure

David Krause14 min read
HMI ProgrammingSiemensTroubleshooting
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Resolving LOGO! 8 FS4 (0BA8) HMI Simulation Communication Failure

1. Problem Overview

Engineers integrating a Siemens LOGO! 8 (order suffix 0BA8, firmware feature set 04) with a SIMATIC KTP400 Basic Panel frequently encounter a scenario in which the physical HMI is unavailable during early commissioning, yet project validation must proceed. The standard fallback is to use the WinCC Runtime Advanced / WinCC Basic integrated simulation (RT Simulator) on the engineering PC. With a LOGO! 8 FS04 device, this path fails: HMI tags read back as #### placeholders, and no S7 connection establishes between the simulation runtime and the LOGO! base module.

The LOGO! base module remains responsive on the LAN (Modbus TCP/IP polls from WinCC 7.4 still succeed against memory registers VW, MW, and DB-style areas exposed via the LOGO! Modbus map). The failure is specific to the S7-200 SMART-compatible S7ONLINE transport used by the WinCC simulator when talking to a LOGO! 8 FS04 target. This is a documented Siemens firmware defect, not a project wiring or IP configuration error.

2. Affected Systems and Firmware Versions

Component Affected Versions Fixed Version Notes
LOGO! 8 (6ED1052-xxx08-0BA8) FS04 (FW < V1.81.x) FS05 (V1.81.x) and FS06 (V1.82.x) Defect specifically affects S7 communication from WinCC Basic/Comfort Simulator
LOGO! 8 (0BA8) variants FS04 and FS05 reported affected FS06 recommended FS05 is an interim fix; FS06 closes remaining edge cases
LOGO! Soft Comfort V8.x and earlier V8.1+ recommended for FS06 deployment Required for PC-LAN routing setup
WinCC Basic / Comfort / Advanced (Simulator) All TIA Portal versions up to V16 All TIA Portal versions Simulator behavior is independent of TIA version; firmware on LOGO! is the root cause
WinCC 7.4 / 7.5 (Modbus TCP) All versions All versions Modbus TCP path is unaffected by the S7 communication defect
KTP400 Basic (6AV2 123-2DB03) Firmware ≤ V16 Any Physical panel works without firmware update on LOGO!; only the simulator is impacted
Critical: Only the integrated WinCC simulation is broken on FS04/FS05. The physical KTP400 communicates correctly. If the panel is on the bench, the project can be validated live and the simulator can be skipped. If the simulator is mandatory (FAT, classroom, remote engineering), the firmware update is the only supported path.

3. Root Cause Analysis

The LOGO! 8 (0BA8) base module exposes two distinct communication endpoints on its Ethernet port (default IP 192.168.0.3/24, configurable up to 16 connections):

  1. S7-compatible connection (port 102, ISO-on-TCP / S7ONLINE) — used by TIA Portal, WinCC Basic, WinCC Comfort, WinCC Advanced, LOGO! Soft Comfort (online mode), and the S7-PCT / SINAMICS tools.
  2. Modbus TCP server (port 502) — used by WinCC 7.x, third-party SCADA, and most non-Siemens HMI platforms.

On firmware feature sets FS04 and FS05, the S7 endpoint incorrectly negotiates the S7 communication parameters when the client is a WinCC Runtime Simulator. The simulator establishes a connection handshake but never receives the response PDU required to populate tag values, so the HMI renders the #### status placeholder (WinCC tag status = "Connection failure / no value").

The same simulation client talking to a S7-1200 / S7-1500 / ET200S CPU works without modification. The fault is therefore isolated to LOGO! 8 (0BA8) firmware revisions prior to FS06. Siemens documented the fix in the LOGO! 8 firmware release notes; the upgrade is delivered as a binary firmware update package (LWE file) and is deployed via LOGO! Soft Comfort or an SD card.

An independent, secondary failure mode also observed in the field is a wrong network adapter selection in the PG/PC interface (Windows Control Panel → "Set PG/PC Interface"). When multiple NICs are present (Wi-Fi + LAN + Hyper-V virtual switch + VPN TAP), the S7ONLINE access point may bind to the wrong interface, producing the same #### symptom. Always resolve the firmware first; if the symptom persists, then inspect the PG/PC assignment.

4. Prerequisites for the Fix

Item Specification Source
LOGO! Soft Comfort (engineering) V8.1 or later (V8.2 for FS06 OTA deployment) Siemens support download (free)
LOGO! 8 firmware FS06 update package 109750845 entry — LOGO! 8 (0BA8) Update V1.82.x Siemens Support Entry 109750845
Micro SD card (optional, for offline update) ≤ 32 GB, FAT32, empty SanDisk / Kingston industrial grade recommended
Ethernet patch cable Cat5e or better, crossover not required Standard
Engineering PC Windows 10 / 11, TIA Portal V13 SP2 or later, static IP on the LOGO! subnet (e.g., 192.168.0.10/24) Local IT
Network access to the LOGO! Same subnet, no managed switch with port-security blocking ISO-on-TCP Local network

5. Updating LOGO! 8 from FS04 / FS05 to FS06

Two methods are supported: online update via LOGO! Soft Comfort (recommended, preserves program memory) and offline update via micro SD card (used when the LOGO! is in a remote cabinet with no PC attached).

5.1 Online Update (preferred)

  1. Close all TIA Portal / WinCC / LOGO! Soft Comfort instances that hold an online connection.
  2. Download the firmware package (entry ID 109750845) and extract the ZIP to a local folder.
  3. Launch LOGO! Soft Comfort and open the existing project (or "File → New" for an empty test project).
  4. From the menu bar, choose Tools → Transfer → Firmware Update (path may vary slightly by Soft Comfort version: Tools → Update Firmware).
  5. In the "Firmware Update" dialog, browse to the extracted .lwe firmware file and select the target LOGO! base module from the "Accessible Nodes" list.
  6. Confirm the dialog. The transfer takes approximately 90–180 seconds; do not power-cycle the LOGO! during this window.
  7. When the progress dialog reports success, the LOGO! reboots automatically. Re-establish the connection from LOGO! Soft Comfort (Tools → Transfer → PC → LOGO!) and verify the firmware revision in the device information banner (should read FS:06 / V1.82.x or later).
  8. Transfer the project circuit back to the LOGO! (the firmware update erases program memory on most revisions; the project must be re-sent after the firmware upgrade).

5.2 Offline Update via Micro SD Card

  1. Format a micro SD card as FAT32 (32 GB max; cards larger than 32 GB require third-party partitioning tools).
  2. Copy the extracted firmware files (typically logo_fs06.lwe and an associated logo_fs06.bin) to the SD card root directory.
  3. Power down the LOGO! base module.
  4. Insert the SD card into the slot behind the removable display / on the side of the module.
  5. Power the LOGO!. The display first shows UPDATE FW; press OK to acknowledge, then YES to confirm.
  6. Wait for the progress bar to complete and the LOGO! to reboot (typically 2–4 minutes).
  7. Remove the SD card. The LOGO! defaults to factory IP 192.168.0.3; reapply any custom network configuration from LOGO! Soft Comfort before reconnecting.
Warning: The micro SD card update procedure erases the circuit program, all VM parameter values, and any data log on the card. Always export the LOGO! project as an .lsc file from LOGO! Soft Comfort before performing an SD-based update.

6. PG/PC Interface Verification

If the firmware upgrade completes successfully but the WinCC simulator still shows ####, the next item to inspect is the S7ONLINE access point binding.

  1. Open the Windows Control Panel → Set PG/PC Interface applet (search for "Set PG/PC" in the Start menu on Windows 10 / 11).
  2. In the "Access Point of the Application" table, locate the entry S7ONLINE (used by TIA Portal) and S7ONLINE_STEP7 (used by legacy STEP 7 / WinCC flexible). Both should point to the same physical Ethernet adapter.
  3. If the system lists multiple network adapters (e.g., Intel I219-V for the LAN, Intel Wi-Fi 6 AX201 for wireless, Hyper-V Virtual Ethernet Adapter for VM traffic), select the wired LAN adapter that is physically connected to the LOGO! subnet.
  4. Avoid selecting virtual adapters (Hyper-V, VirtualBox host-only, VPN TAP, VMware VMnet) unless the LOGO! is intentionally inside a virtualized segment.
  5. Click OK and restart TIA Portal / WinCC so the access point change is re-read.

To confirm the binding took effect, in TIA Portal open Online → Accessible Nodes after the change. The LOGO! must appear at its IP address (e.g., 192.168.0.3). If it is still not visible, the issue is at the IP / subnet / firewall layer, not the access-point layer.

7. Configuring the WinCC Runtime Simulator

  1. Open the TIA Portal project containing the KTP400 configuration.
  2. In the project tree, right-click the HMI device (KTP400) and choose Start Runtime. This launches the WinCC Runtime Simulator with the compiled project.
  3. Verify that the project was compiled for the correct HMI type (KTP400 Basic mono or KTP400 Basic color, depending on the physical panel). A mismatch is the most common reason for "tags unavailable" status.
  4. In the simulator, observe the connection status indicator (bottom right). A green "connected" indicator means the S7 path is healthy. Yellow / red indicates a fault.
  5. If the connection fails, open Project → HMI Device Configuration → Connections and confirm:
    • Connection name is unambiguous (avoid spaces and special characters).
    • Partner (PLC) IP = LOGO! IP (192.168.0.3 by default).
    • Access point resolves to S7ONLINE.
    • The connection is "Active" in the runtime settings.
  6. Re-compile the project (Project tree → HMI device → right-click → Compile → Software (rebuild all)).
  7. Re-launch the simulator. Tags should now resolve and the #### placeholders disappear.

8. LOGO! Soft Comfort Multi-Connection Configuration

The LOGO! 8 supports up to 16 simultaneous S7/Modbus connections. When the same LOGO! base module is targeted by the WinCC simulator, the LOGO! Soft Comfort online view, and a Modbus master at the same time, the connections must be enumerated explicitly so the LOGO! accepts each on its own slot. The procedure is described in the Siemens LOGO! Ethernet PLC Connection Guide.

  1. In LOGO! Soft Comfort, open the project and select File → Properties → Communication.
  2. Enable "Allow multiple connections" (sometimes labeled "LOGO! is accessible from PC"). This is mandatory when more than one client must coexist.
  3. For each client, define a connection record with the remote IP, the slot index (0–15), and the access type (read-only or read-write).
  4. Save the project and transfer to the LOGO!. The LOGO! stores the connection table in non-volatile memory.
  5. Verify the active connections from the LOGO! display: navigate to Menu → Diagnostics → Connections. Each live client appears with its IP, slot, and connection age.

9. Modbus TCP/IP Readback with WinCC 7.4 (Parallel Validation Path)

While the firmware update is being applied, the existing Modbus TCP path to the LOGO! can be used to confirm network connectivity and I/O state. The LOGO! 8 Modbus map is documented in the LOGO! 8 system manual (Siemens entry ID 109751054). Key registers:

Modbus Address Type Symbolic Tag Description
00001–00024 Coil (R/W) Q1–Q24 Digital outputs
10001–10024 Discrete Input (R) I1–I24 Digital inputs
30001–30096 Input Register (R) VW0–VW94 (words) VM variable memory (read)
40001–40096 Holding Register (R/W) VW0–VW94 (words) VM variable memory (read/write)
40097–40648 Holding Register (R/W) Network inputs / outputs S7 network mapping area

In WinCC 7.4, configure the "SIMATIC S7 / S5-PLC" driver as a "Modbus TCP/IP" connection pointing to 192.168.0.3:502. Poll the holding registers using a 1-second cycle. The values seen in WinCC 7.4 must match the values shown on the LOGO! display; if they do, the LAN is healthy and only the S7 layer is broken.

10. Physical KTP400 Integration (Reference)

If a physical KTP400 is available for parallel validation, the connection setup is straightforward:

  1. Set the KTP400 to "Transfer" mode (Control Panel → Transfer → enable transfer).
  2. Configure the HMI IP on the LOGO! subnet (e.g., 192.168.0.10), mask 255.255.255.0, gateway optional.
  3. Configure the S7 connection on the HMI: Partner IP = LOGO! IP, Access Point = S7ONLINE, Rack = 0, Slot = 1 (LOGO! always reports as rack 0, slot 1 regardless of physical base / extension modules).
  4. Compile and transfer the HMI project via Ethernet or USB.
  5. Confirm the connection icon on the KTP400 status bar turns green within 5 seconds.

11. Verification Checklist

  1. LOGO! display reports firmware feature set FS:06 (or later).
  2. LOGO! Soft Comfort Online → Accessible Nodes shows the LOGO! IP.
  3. PC LAN adapter has a static IP in the same subnet (e.g., 192.168.0.10/24).
  4. Set PG/PC Interface assigns S7ONLINE to the LAN adapter.
  5. WinCC simulator launches and shows green connection indicator.
  6. All HMI tags resolve from #### to numeric values.
  7. Bit-mapped alarm window, trend view, and recipe view all populate correctly.
  8. Modbus TCP master (WinCC 7.4 or third-party) reads the same VM values as the S7 simulator.
  9. Disabling the S7 connection in the HMI does not break the Modbus path (proving independence of the two transports).

12. Troubleshooting Matrix

Symptom Likely Cause Resolution
Simulator shows ####, physical HMI works LOGO! FS04/FS05 firmware defect Upgrade to FS06 via Siemens entry 109750845
Both simulator and physical HMI show #### Wrong PG/PC interface adapter selected Bind S7ONLINE to the correct LAN adapter
No device in "Accessible Nodes" Subnet mismatch / firewall / NIC disabled Verify IP, mask, gateway; disable Windows firewall for the LOGO! subnet
Accessible Nodes shows device, simulator still #### HMI compiled for wrong panel variant Re-compile targeting the exact KTP400 PN type
LOGO! unreachable after firmware update Network settings erased during update Re-import IP configuration via LOGO! Soft Comfort
Intermittent disconnects every 30–60 s Managed switch blocking ISO-on-TCP (TSAP filtering) Enable multicast / disable IGMP snooping on the LOGO! port
WinCC 7.4 Modbus works, S7 path fails Firmware not updated Proceed with firmware update
"Connection failed: partner not reachable" LOGO! has more than 16 active connections Close unused clients, reduce connection count in Soft Comfort
Firmware update dialog does not list the LOGO! LOGO! in STOP / display in menu mode Press ESC on the LOGO! to return to base display, retry
Tags intermittently show quality code "bad" VM address outside LOGO! address range (VW0–VW94) Clamp tag addresses to documented LOGO! range

13. Field-Proven Caveats

  • VM address range: The LOGO! 8 supports VM0–VM958 (byte-level) but Modbus exposes only the first 96 words (VW0–VW94). TIA Portal HMI tag mappings beyond this range fail silently with quality "bad".
  • Connection table persistence: Custom multi-connection entries written through LOGO! Soft Comfort survive power-cycle but are lost when an SD-card firmware update is performed without first exporting the project.
  • Subnet routing: If the LOGO! is behind a Layer-3 device (router, firewall), the S7 connection requires the router to pass TCP port 102 with TSAP preservation. Many consumer routers drop ISO-on-TCP sessions within seconds.
  • LOGO! BM (basic module) vs AM (add-on module): Only the BM exposes Ethernet. The AM variants are non-networked digital / analog extension modules and never appear in "Accessible Nodes".
  • Power-on reset on FS06 update: Retentive flags and VM values are preserved across firmware updates (battery-backed RAM), but the LOGO! does not preserve active timers / counters in RUN-STOP-RUN transitions triggered by the update.
  • Hot-swapping SD card: Do not remove the SD card while the LOGO! is reading or writing to it (data log active). Corruption of the data log and, in rare cases, of the firmware region has been reported.

14. Related Documentation

Frequently Asked Questions

Why does my WinCC simulator show #### values while my physical KTP400 works fine on the same LOGO! 8 FS04?

The physical HMI and the integrated WinCC simulator use slightly different S7 handshake PDUs. LOGO! 8 firmware feature sets FS04 and FS05 contain a defect that mishandles the simulator's specific handshake, while accepting the panel's handshake. Upgrading to LOGO! 8 FS06 (V1.82.x) closes this defect. The physical panel does not require any firmware change.

Which firmware file do I download from Siemens entry 109750845?

Extract the ZIP and use the .lwe firmware file inside. In LOGO! Soft Comfort, navigate to Tools → Transfer → Firmware Update (or Tools → Update Firmware, depending on Soft Comfort version), browse to the .lwe, select the LOGO! 0BA8 base module from the "Accessible Nodes" list, and confirm. The transfer takes 90–180 seconds.

Will the firmware update erase my LOGO! circuit program?

Online firmware updates via LOGO! Soft Comfort generally preserve program memory, but you should still re-transfer the project after the update as a safety measure. Offline SD-card firmware updates always erase the circuit program, all VM parameter values, and any data log on the card — export the project to an .lsc file from LOGO! Soft Comfort first.

Can I read LOGO! variables via Modbus TCP while the S7 connection is broken?

Yes. The Modbus TCP server (port 502) is independent of the S7 layer and remains fully functional on FS04, FS05, and FS06 firmware. WinCC 7.x, third-party SCADA, and most non-Siemens HMI platforms can poll VM variables through holding registers 40001–40096. The S7 defect only affects WinCC Basic / Comfort / Advanced Simulator clients.

After upgrading to FS06, why is my LOGO! still unreachable from "Accessible Nodes"?

The most common cause is that the firmware update reset the LOGO! IP configuration to the factory default (192.168.0.3). Set your PC LAN adapter to 192.168.0.10 / 255.255.255.0, open LOGO! Soft Comfort, and re-apply the original IP address via Tools → Transfer → Configure Network. Alternatively, verify the S7ONLINE access point is bound to the correct Ethernet adapter in the Windows "Set PG/PC Interface" applet.

How many simultaneous S7 / Modbus connections does LOGO! 8 (0BA8) support?

LOGO! 8 supports up to 16 simultaneous connections on its Ethernet port, shared across S7 (port 102) and Modbus TCP (port 502). When multiple clients must coexist, enable "Allow multiple connections" in LOGO! Soft Comfort under File → Properties → Communication and define each connection record explicitly.

Back to blog