S7-1200 CPU1214C Download Failure: TIA Portal & Firmware Fix

David Krause21 min read
S7-1200SiemensTroubleshooting
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Problem Overview: S7-1200 CPU1214C Download Failure

The Siemens SIMATIC S7-1200 CPU 1214C (order numbers 6ES7214-1BE30-0XB0, 6ES7214-1AE30-0XB0, and 6ES7214-1HE30-0XB0) is one of the most widely deployed compact controllers in discrete automation. A recurring support failure mode is a complete inability to download a STEP 7 / TIA Portal project to the CPU even though the PROFINET interface responds to ping, the LINK/LEDs indicate link integrity, and the engineering station has physical Layer-2 connectivity to the controller.

Symptom set typically reported by maintenance engineers:

  • TIA Portal raises "Online: Cannot reach the partner", "Download to device failed", or "Firmware version is not supported by this version of TIA Portal".
  • ping <CPU IP> succeeds with sub-millisecond response on the same subnet.
  • The CPU's MAINT (yellow), RUN/STOP (green), and ERROR (red) LEDs cycle in a pattern that does not match a documented fault (see the S7-1200 System Manual, section on LED diagnostics).
  • Hardware detection in TIA Portal (Online → Accessible devices) does not list the CPU, or lists it with a red warning icon.
  • Previous project download worked; the controller was modified (firmware update, IP reassignment, or a program that left the CPU in a non-receptive state) and the failure is a regression.

This reference documents the field-proven diagnostic and recovery path: matching the TIA Portal version to the CPU firmware, executing a memory reset (MRES), performing a factory reset, recovering the IP with the SIMATIC Automation Tool / IPTool, and using an empty SIMATIC Memory Card (SMC) as a last-resort wipe. The recommended primary resolution is a firmware/TIA version match plus MRES, since the failure is overwhelmingly caused by an incompatible combination of STEP 7 build and CPU firmware revision.

Safety notice. MRES, factory reset, and SMC wipe erase the user program, all data blocks, retentive flags, and the IP configuration of the CPU. Document the offline project, IP, subnet mask, gateway, PROFINET device name, and any secured DB passwords before executing any of the procedures below. Disconnect the controller from the field I/O rack or switch outputs to a safe state before resetting; the CPU will reboot and outputs will follow the configured substitute value strategy.

Root Cause Analysis

Two failure mechanisms account for the majority of "cannot download" incidents on the CPU 1214C. Both are detectable without disassembly.

Mechanism 1: TIA Portal / STEP 7 Build vs. CPU Firmware Mismatch

Each TIA Portal major version (V10.5, V11, V11 SP2, V12, V13, V13 SP1, V14, V15, V15.1, V16, V17, V18, V19, V20) ships a defined set of CPU firmware descriptors. When a project built for firmware V2.x is downloaded from a TIA Portal V10.5 SP2 station, or a project for V4.x is downloaded from a V12 station, the TIA Portal aborts the download handshake during the S7 communication (S7COMM) bring-up. The CPU may be perfectly healthy; the engineering tool simply refuses to negotiate.

The most common mismatches encountered in the field:

  • CPU upgraded to V2.0 or later, but the TIA Portal installation is still V10.5 SP2. The controller is reachable via ping but TIA Portal Accessible devices shows "Cannot establish a connection".
  • CPU on V4.x firmware with TIA Portal V11 SP2 / V12 / V13. Download appears to start, then aborts at the "Compiling and downloading blocks" step with a red status bar and a generic error code.
  • CPU is a second-generation S7-1200 (article number suffix .XB0 or later) but TIA Portal is the V11 base release that does not include the V2 firmware descriptor patch.

Mechanism 2: CPU in a Non-Receptive State (Password, Crashed Program, Failed Online Update)

A bad download, an aborted firmware update, or a forgotten CPU password can leave the S7-1200 in a state where it will accept IP traffic and respond to PROFINET DCP identification but will not accept an S7 download connection. Symptom markers:

  • MAINT LED on solid, RUN/STOP LED off — indicates an unfinished online operation or a previous download that left an inconsistent project on the load memory.
  • CPU accepts Online → Go online but no blocks are listed; Online → Download to device fails with "The online configuration data differ from the offline project".
  • CPU is password-protected and the password has been lost — the password is bound to the configured CPU and cannot be retrieved; the only remedy is a reset to factory defaults which clears the password.

Prerequisites for Recovery

  • Known offline backup of the project: the .ap<version> file (e.g. .ap13, .ap15_1, .ap17) backed up to external media. Without this, a factory reset will permanently erase the program.
  • Physical access to the CPU: access to the front-panel MODE switch and SIMATIC Memory Card slot.
  • Original or compatible SIMATIC Memory Card (SMC) for the last-resort procedure: SIMATIC S7-1200 SMC, article group 6ES7954-8LFxx-0AA0 (24 MB) or larger. The card must be blank or contain only the hidden system files __LOG__ and crdinfo.bin; user project files (S7_JOB.S7S, SIMATIC.S7S, LOG\, etc.) must be removed.
  • Engineering station with administrator rights: the SIMATIC IPTool / SIMATIC Automation Tool requires local admin to install the WinPcap/Npcap capture driver and to bind the PROFINET interface.
  • Network cabling verified: PROFINET cable from CPU X1 port to engineering station NIC, with link LEDs lit on both ends. A direct crossover or 1:1 cable is acceptable for point-to-point commissioning.

Step 1 — Power Cycle and Connectivity Verification

The first field action is always a full power cycle. The S7-1200 retains volatile session state in its onboard work memory; a controlled reboot clears transient handshake errors and forces the S7COMM server to re-bind on its configured port (TCP/102).

  1. Switch off the 24 V DC supply to the CPU and any signal modules that source power through the backplane bus. Wait at least 10 seconds to allow bulk capacitors to discharge below the brown-out threshold.
  2. Restore power and observe the LED sequence: all LEDs on briefly → MAINT flashes → RUN/STOP solid green (or flashing green if in STOP). A CPU stuck in the "all LEDs on" state for more than ~5 s indicates a POST failure and is not recoverable in the field; replace the CPU.
  3. From a Windows command prompt on the engineering station, run ping -t <CPU IP>. A successful response confirms Layer-3 reachability but does not confirm S7 protocol availability.
  4. Open TIA Portal → Online → Accessible devices. If the CPU appears with a yellow warning icon and a message about a firmware-version mismatch, proceed to Step 2. If the CPU does not appear at all, proceed to Step 3.
Operating system note. TIA Portal V10.5 SP2 and V11 only support 32-bit Windows. On Windows 7, only the 32-bit edition is supported; on Windows XP, both 32-bit and 64-bit (XP x64) installations are supported by V11 SP2. On Windows 10 / 11, TIA Portal V10.5 SP2 and V11 are not supported and must be upgraded to at least V13 SP1 (Windows 7 SP1 / Server 2008 R2 minimum) or V15.1 (Windows 10 64-bit minimum). The TIA Portal Version Administrator is the only sanctioned method to install multiple TIA Portal versions side-by-side on a single engineering station.

Step 2 — Match TIA Portal Version to CPU Firmware

Verify the CPU's actual firmware before launching the recovery. With the CPU powered and reachable, open TIA Portal → Online → Accessible devices → Online → Diagnostics. The firmware version is shown in the diagnostics buffer and the device information pane.

S7-1200 / TIA Portal Firmware Compatibility Matrix

CPU Firmware Minimum TIA Portal Recommended TIA Portal Max TIA Portal (back-compatible) Released
V1.0 STEP 7 Basic V10.5 V10.5 SP2 V11 2009
V1.0.2 V10.5 SP2 V10.5 SP2 V11 2010
V2.0 V11 V11 SP2 / V12 V13 2011
V2.1 V11 SP2 V12 V13 SP1 2012
V2.2 V12 V12 SP1 V14 2013
V3.0 V13 V13 SP1 V15 2014
V4.0 V13 SP1 V14 V15.1 2015
V4.1 V14 V14 SP1 V15.1 2016
V4.2 V15 V15.1 V16 2017
V4.3 V15.1 V16 V17 2019
V4.4 V16 V17 V19 2020
V4.5 V17 V18 V20 2022
V4.6 V19 V19 / V20 V20 2024

If the engineering station does not have a TIA Portal version that matches the CPU firmware, three options exist:

  1. Install a matching TIA Portal version using the TIA Administrator. The TIA Portal Version Administrator supports side-by-side installations of multiple major versions on the same Windows host; refer to the TIA Administrator help for installation sequencing rules.
  2. Downgrade the CPU firmware to a revision supported by the existing TIA Portal. Firmware downgrades on the S7-1200 are supported via a SIMATIC Memory Card; the S7-1200 will boot the older firmware on the next restart. This is the recommended path when the engineering station cannot be upgraded.
  3. Upgrade TIA Portal to a release that supports the CPU firmware and re-establish the project. This is the recommended path when firmware V2.0 or higher is mandated by new program features.
Important. A TIA Portal V10.5 SP2 installation can establish a basic online connection to a CPU running V2.0 firmware — the limitation is the project download, not the diagnostic connection. The diagnostics buffer, online block view, and forcing work, but the download will be rejected by the TIA Portal as the V2 firmware descriptor is not present in V10.5 SP2. The correct remediation is a project matching the firmware, not a forced download.

Step 3 — Memory Reset (MRES) via the Front-Panel MODE Switch

MRES clears work memory, all data blocks, and the system data block. The IP address, subnet mask, and PROFINET device name are preserved (these live in the system area, not user memory). The program, all DBs, and any active forces are removed.

  1. Place the MODE switch in the STOP position. Confirm by the RUN/STOP LED showing solid yellow (older firmware) or solid orange (firmware V4+).
  2. Toggle the switch to MRES and hold for approximately 3 seconds until the MAINT LED begins to flash at 2 Hz. Release the switch.
  3. Within 3 seconds of release, toggle the switch back to MRES and hold for approximately 3 seconds until the MAINT LED stops flashing. Release.
  4. Wait for the CPU to perform its restart cycle. The RUN/STOP LED returns to solid yellow/orange when the reset is complete and the CPU is in STOP with empty user memory.

After MRES, attempt the download again. If the engineering station has the correct TIA Portal version, the CPU will accept the project without further intervention.

Tip. If the CPU firmware is V2.0 or later and the engineering station is TIA Portal V10.5 SP2, MRES alone will not enable the download. TIA Portal V10.5 SP2 does not contain the V2 firmware descriptor, and the handshake will be refused even on an empty CPU. In this specific case, downgrade the firmware to V1.0.2 (Step 4) or upgrade TIA Portal (Step 2, option 3).

Step 4 — Factory Reset (Reset to Factory Defaults)

Factory reset clears the IP configuration, the PROFINET device name, the program, all data blocks, all retentive flags, and the CPU password (if set). It is used when the IP address is unknown, the password is lost, or MRES does not clear a corrupted system data block.

  1. Open TIA Portal on the engineering station. Online → Accessible devices → select CPU → Online → Reset to factory settings. Confirm the dialog.
  2. Alternatively, use the front-panel MRES sequence with a SIMATIC Memory Card inserted (the CPU will copy the card's image to internal load memory and then perform a full reset).
  3. On completion the CPU will restart with the default IP 192.168.0.1 (CPU 1214C default subnet mask 255.255.255.0), no PROFINET device name, and an empty user program.
  4. Re-assign the IP from the engineering station using the SIMATIC Automation Tool, IPTool, or TIA Portal Online → Accessible devices → Assign IP address.

Step 5 — Firmware Downgrade Using a SIMATIC Memory Card (SMC)

A firmware downgrade is sometimes the only way to make an "orphaned" CPU (V2.x firmware, only V10.5 SP2 TIA Portal) communicable. The S7-1200 supports firmware delivery via SMC, a method documented in the S7-1200 System Manual.

  1. Obtain the firmware .upd file from the Siemens support portal, article group matching the CPU. The V1.0.2 update file for the CPU 1214C is published under article ID 6ES7214-1BE30-0XB0.
  2. Insert the SMC into a card reader on the engineering station.
  3. Format the SMC if it has been used previously. Place exactly two files at the root: the firmware .upd file and a S7_JOB.S7S text file containing the single line Firmware_Update.
  4. Insert the SMC into the powered-off CPU. Power on the CPU. The MAINT LED will flash rapidly during the firmware write; this takes 1–3 minutes. Do not remove power during the write.
  5. When the write completes, the CPU restarts. Remove the SMC; the firmware is now V1.0.2 (or whichever target was placed on the card). The CPU is reachable at default IP 192.168.0.1 via TIA Portal V10.5 SP2.

Empty SMC as a Last-Resort Wipe

If the CPU will not perform a factory reset through the engineering tool (TIA Portal returns a connection error before the reset command is sent), an empty SMC can be used to wipe the load memory. Prepare the card with only the two hidden/system files:

  • __LOG__
  • crdinfo.bin

These two files exist on every shipped SMC and are required by the S7-1200 firmware to recognize the card as valid. The presence of any user project files (e.g. SIMATIC.S7S, LOG\ subdirectory contents, S7_JOB.S7S) on the SMC will cause the CPU to load them into work memory on the next restart. The wipe procedure is:

  1. Insert the empty SMC into the powered-off CPU.
  2. Power on. The CPU will detect the card, copy the (empty) image to internal load memory, and restart with the previous project structure preserved in the internal flash.
  3. If the goal is a true wipe, follow up with MRES (Step 3) and then factory reset (Step 4) from TIA Portal.

Step 6 — IP Recovery with the SIMATIC IPTool

The SIMATIC IPTool is a legacy utility (the modern replacement is the SIMATIC Automation Tool, which ships with TIA Portal and can be installed standalone) that uses PROFINET DCP to discover and re-assign IP addresses to S7-1200 CPUs on the local subnet. It is invoked when the IP has been lost or set to an unreachable subnet.

  1. Launch the SIMATIC IPTool from Start → Siemens Automation → SIMATIC → IPTool. The tool enumerates the local network adapters; select the NIC connected to the PROFINET segment.
  2. Click Search. The IPTool broadcasts a DCP IdentifyAll on the local subnet; any S7-1200 reachable via Layer-2 is listed with its MAC address, current IP, device name, and device type.
  3. Select the target CPU, set the new IP address, subnet mask, and router address, and click Assign. The IPTool writes the new address via DCP Set; the CPU stores the address in its retentive system area.
  4. Power-cycle the CPU to confirm the new IP persists. The CPU will now respond to ping on the assigned address.
Security note. PROFINET DCP is an unauthenticated Layer-2 protocol. The IPTool will work on any reachable S7-1200, including one in a different plant, when the engineering station is connected to the same broadcast domain. In OT environments the PROFINET interface should be segmented, and DCP write should be restricted by managed switch configuration.

Network Topology Reference

The diagram below shows the recommended commissioning topology for an S7-1200 CPU 1214C during a recovery operation. The engineering station is on the same subnet as the CPU X1 PROFINET port; the field I/O (PROFINET IO devices or DP slaves) is isolated from the recovery segment to prevent unintended IO updates during the reset.

S7-1200 CPU1214C Recovery Topology Engineering Station TIA Portal Vxx IPTool / SIMATIC AT S7-1200 CPU 1214C Firmware V?.?.? PROFINET X1 Managed Switch PROFINET segment DCP filtered CAT5/6 CAT5/6 Field I/O isolated disabled Subnet: 192.168.0.0/24 (default) or project-defined DCP = Discovery and Configuration Protocol (PROFINET Layer-2)

CPU 1214C Reference Specifications

Parameter Value
Order numbers 6ES7214-1BE30-0XB0 (DC/DC/DC) · 6ES7214-1AE30-0XB0 (AC/DC/RLY) · 6ES7214-1HE30-0XB0 (DC/DC/RLY)
Work memory (program + data) 50 KB + 50 KB (V1.x) · 75 KB + 100 KB (V2.x) · 100 KB + 150 KB (V4.x)
Bit memory (M) 8192 bytes
Load memory 2 MB internal, expandable via SMC (up to 24 MB)
Retentive memory Configurable: M, DB, IEC timers/counters
Digital inputs / outputs 14 DI / 10 DO onboard
Analog inputs 2 AI onboard (0–10 V, ±10 V, 0–20 mA on V4+)
High-speed counters 4 (max 100 kHz / 30 kHz depending on firmware)
Pulse outputs 2 (PTO, up to 100 kHz)
Communication interfaces 1 × PROFINET (X1, 2-port switch on V4), RS485 optional via CM/CP
Cycle time / bit 0.1 µs (V1) · 0.08 µs (V2) · 0.04 µs (V4)
Real-time clock Buffered, typical 20 days at 25 °C
Supply voltage 24 V DC (DC variants) or 120/230 V AC (AC variants)

Recovery Procedure State Machine

The diagnostic/recovery path is best modelled as a decision tree. The SVG below illustrates the recommended progression; each node corresponds to a numbered step in the article.

S7-1200 Download Recovery State Machine Power cycle + ping TIA version match MRES via MODE switch Factory reset (TIA) IPTool / SIMATIC AT SMC firmware update SMC empty-card wipe Download OK Edges: try upper path first; descend on failure

Verification Steps

After the recovery procedure, verify success with the following checklist before handing the controller back to production.

  1. Online connection: TIA Portal → Online → Go online completes without error and shows the correct device name and IP in the status bar.
  2. Firmware check: Online → Diagnostics → Device information shows the expected firmware version and the expected article number (e.g. 6ES7214-1BE30-0XB0).
  3. Project download: Online → Download to device completes with a green status; the consistency check passes.
  4. CPU state: Place the MODE switch in RUN. The RUN/STOP LED shows solid green; MAINT and ERROR are off. The diagnostics buffer shows the start-up OB executed without errors.
  5. PROFINET IO: If the CPU is a PROFINET IO controller, all configured IO devices come online and report OK status in the Online → Diagnostics → PROFINET topology view.
  6. Forcing and watch tables: a representative watch table is created and online values update within the configured update time (default 1000 ms).

Troubleshooting Matrix

Symptom Most Likely Cause First Action Second Action Last-Resort
Ping OK, TIA Accessible devices lists CPU with warning icon TIA Portal version < CPU firmware support Match TIA Portal version (Step 2) Downgrade firmware via SMC (Step 5) Upgrade TIA Portal
Ping OK, TIA does not list CPU Subnet mismatch, firewall, or CPU in non-receptive state Disable Windows firewall on the PROFINET profile IPTool to verify IP (Step 6) Factory reset (Step 4)
Ping OK, online handshake fails immediately CPU in non-receptive state (corrupt project) MRES via MODE switch (Step 3) Factory reset (Step 4) SMC empty-card wipe (Step 5 alt)
MAINT solid on, RUN/STOP off Inconsistent project on load memory MRES (Step 3) SMC empty-card wipe (Step 5 alt) Replace CPU
All LEDs on > 10 s after power-up POST failure or missing firmware SMC firmware update (Step 5) SMC empty-card wipe Replace CPU
Password forgotten CPU password bound to configuration Factory reset (Step 4) clears password Restore project from offline backup None (password cannot be retrieved)
MAINT flashes rapidly after SMC insertion Firmware write in progress Wait 1–3 min, do not remove power Restart after write completes Verify SMC contents
TIA Portal reports "Firmware V4.x not supported" TIA Portal major version too old Install matching TIA Portal via Administrator Downgrade CPU firmware Replace CPU with compatible revision

Preventive Recommendations

  • Document the firmware/TIA pairing in the project cover sheet. Each project should declare the target CPU article number and firmware version. A simple spreadsheet maintained in the project library is sufficient for small fleets; an asset-management database is recommended for fleets above 50 controllers.
  • Maintain a hot-spare engineering station with the same TIA Portal versions as production, kept under version control. The TIA Administrator allows multiple TIA Portal major versions to coexist on a single Windows host; the recommended approach is one TIA Portal per project major version.
  • Configure the PROFINET device name at commissioning, not at first program download. The device name persists across MRES; an empty device name will prevent PROFINET IO from coming up after a reset.
  • Use the SIMATIC Automation Tool (the modern replacement for IPTool) for batch firmware updates and IP provisioning. The Automation Tool is documented at SIMATIC Automation Tool entry page and is the sanctioned bulk-configuration tool for S7-1200 and S7-1500 fleets.
  • Keep at least one blank SMC in the maintenance kit. The card is required for the firmware-downgrade and empty-card-wipe procedures and is the only way to recover a CPU that will not respond to TIA Portal at all.
  • Use the Siemens compatibility tool at TIA Portal & CPU firmware compatibility to verify any pairing before commissioning.

Edge Cases and Field Notes

Several edge cases observed in industrial deployments of the CPU 1214C are not covered in the basic flow above.

  • Third-party firewalls on the engineering station: Windows Defender Firewall is not the only firewall on a modern engineering station. Trend Micro, Symantec Endpoint Protection, and other enterprise security products inject NDIS filters that block DCP and S7COMM even when the Windows firewall is disabled. Whitelist the PROFINET interface or temporarily disable the third-party firewall during commissioning.
  • USB PROFINET adapters: a USB-to-PROFINET adapter (e.g. Siemens 6GK1161-2AA01) may enumerate as a different network interface than the wired NIC and is not always visible to TIA Portal. Use the wired NIC for the recovery to avoid the IPTool / TIA Portal "adapter not found" condition.
  • Virtual machines: TIA Portal running in a VM with bridged networking usually works for the recovery; TIA Portal running with NAT networking cannot reach the CPU at all because the VM's NAT adapter does not bridge DCP. Use bridged mode in the VM network editor.
  • VPN access: S7COMM and DCP do not traverse a standard IPsec / SSL VPN. Recovery must be performed on the local PROFINET segment; do not attempt to recover a CPU across a corporate VPN.
  • Multiple CPUs with default IP 192.168.0.1: the SIMATIC IPTool and SIMATIC Automation Tool can disambiguate by MAC address, but only one CPU at a time should be powered on the segment during IP recovery. A second CPU on the same IP will cause silent packet drops and unreliable download.
  • Retentive data loss: MRES and factory reset clear all retentive M, DB, and timer/counter values. If the process is safety-critical and the recipe/state is not stored in a non-volatile DB, schedule the reset during a planned outage.
  • CPU 1212C vs. CPU 1214C: the procedures are identical for the CPU 1212C (article group 6ES7212-1BE30-0XB0); the only practical difference is the smaller I/O count and work memory. The firmware version determines TIA Portal compatibility, not the CPU variant.
  • STEP 7 Professional vs. STEP 7 Basic: TIA Portal V10.5 SP2 was available only as STEP 7 Basic for S7-1200. STEP 7 Professional is required for S7-300/S7-400 and is delivered in a separate DVD image; the V10.5 SP2 Basic DVD does not include the S7-300/S7-400 project editor. If a project is built with V11 Professional, the engineering station must be upgraded to V11.

Related Siemens Documentation

Frequently Asked Questions

Why can I ping the CPU 1214C but not download from TIA Portal?

A successful ping only confirms Layer-3 reachability on the configured IP. The TIA Portal download requires a higher-layer S7COMM handshake on TCP/102 that is gated by the CPU firmware descriptor in the TIA Portal installation. If the TIA Portal major version is older than the CPU firmware, the handshake is refused. Verify the firmware version under Online → Accessible devices → Diagnostics and match the TIA Portal version per the compatibility matrix in Step 2.

What is the minimum TIA Portal version for a CPU 1214C on firmware V2.0?

Firmware V2.0 requires TIA Portal V11 or higher. TIA Portal V10.5 SP2 can establish a basic online diagnostic connection to a V2.0 CPU but cannot perform a project download. For production use with V2.0 firmware, install at least TIA Portal V11 SP2 (recommended) or V12.

How do I reset a CPU 1214C to factory defaults when I have forgotten the IP?

Use the SIMATIC IPTool or SIMATIC Automation Tool to discover the CPU on the local PROFINET segment by MAC address (DCP IdentifyAll). Once located, assign a reachable IP. Then perform the factory reset from TIA Portal under Online → Accessible devices → Reset to factory settings. If the CPU will not respond to TIA Portal, insert an empty SIMATIC Memory Card (containing only __LOG__ and crdinfo.bin) and power cycle; then complete the reset with MRES via the MODE switch.

Does a factory reset clear the CPU password?

Yes. A factory reset (MRES + SMC wipe, or TIA Portal Reset to factory settings) clears the CPU password, IP address, PROFINET device name, program, and all data blocks. The reset is irreversible; the original program must be restored from an offline backup. There is no Siemens-supported method to recover a forgotten password without a reset.

Can I downgrade the CPU 1214C firmware from V2.0 to V1.0.2 using only TIA Portal?

No. Firmware downgrades on the S7-1200 are performed exclusively via a SIMATIC Memory Card. Prepare the SMC with the target firmware .upd file and a S7_JOB.S7S text file containing the single line Firmware_Update, insert the card into the powered-off CPU, and power on. The downgrade takes 1–3 minutes; do not remove power during the write. After the downgrade the CPU responds to TIA Portal V10.5 SP2 with the V1.0.2 firmware descriptor.

What Windows versions are supported for TIA Portal V10.5 SP2 and V11?

TIA Portal V10.5 SP2 and V11 support only 32-bit Windows. Windows 7 must be 32-bit; Windows XP (including XP Professional x64) is supported. TIA Portal V10.5 SP2 and V11 are not supported on Windows 10 or Windows 11. For those operating systems, install at least TIA Portal V15.1 (Windows 10 64-bit minimum) or V16 (Windows 10 / Server 2019).

Back to blog