1. Problem Description
When using the Siemens library block FB "MB_REDCL" (Redundant Modbus/TCP Client) on an S7-400H station with two CP 443-1 communications processors, the function block returns persistent error statuses W#16#8304 and/or W#16#A083 on the STATUS_0A / STATUS_1A outputs, the ERROR output is set, the DONE output never goes TRUE, and the error counter increments continuously even though the block is called cyclically in OB35 (for example, 50 ms cycle).
Typical symptoms reported in the field:
-
DONEnever becomes TRUE. -
ERRORis set immediately on the first call. -
STATUS_0A=W#16#8304(no connection to the partner). -
STATUS_0A=W#16#A083(TCP error during send/receive). - Error counter (
COUNT_ERROR) increments every OB35 cycle, Done counter stays at 0. - Reducing the OB35 period (e.g., 20 ms or 100 ms) does not change the behavior.
Almost all such incidents share a common root cause category: the TCP connection between the S7-400H CP 443-1 and the Modbus/TCP server is not actively established from the SIMATIC side, and/or the rising-edge trigger at ENQ is re-asserted while a previous job is still active. A secondary cluster of issues involves misuse of the WRITE_READ, DATA_TYPE, and LENGTH parameters.
MB_CLIENT in TIA Portal. Both blocks implement Modbus/TCP client behavior, but MB_REDCL is intended for redundant CP paths and is licensed via the REG_KEY input. See the official library manual: SIMATIC Modbus/TCP - Redundant Communication via CP 443-1 in H-Systems.
2. MB_REDCL Block Architecture and Parameters
MB_REDCL is a function block (FB) that wraps a single Modbus/TCP transaction against a configured server. The block supports two physical connections (path A and path B), each of which can be associated with one of the two H-CPUs through dedicated connection IDs (id_0_a / id_1_a for path A; id_0_b / id_1_b for path B). The UNIT input selects which path is used for the next transaction.
2.1 Formal interface (STEP 7 / STL view)
| I/O | Name | Type | Meaning |
|---|---|---|---|
| IN | ENQ | BOOL | Rising-edge job trigger. Must only be set when the previous job is finished (BUSY = FALSE). |
| IN | DATA_TYPE | BYTE / INT | Modbus function-code selector. See Section 2.2. |
| IN | START_ADDRESS | WORD / DINT | Modbus 0-based or 1-based register/coil start address as required by the server. |
| IN | LENGTH | WORD / INT | Number of elements. Unit depends on DATA_TYPE: words for register types, bits for coil/input types. |
| IN | WRITE_READ | BOOL | FALSE = Read request; TRUE = Write request. |
| IN | UNIT | BYTE / INT | Connection path selector. Typically 1 = path A, 2 = path B. |
| IN | MONITOR | BOOL | TRUE = monitor mode (only evaluates connection health, no real Modbus transaction). |
| IN | REG_KEY | STRING | License key string for the Modbus/TCP CP Red library. |
| IN | id_0_a, id_1_a | WORD | Connection IDs of the path-A TCP connections for CPU 0 and CPU 1 (from NetPro). |
| IN | id_0_b, id_1_b | WORD | Connection IDs of the path-B TCP connections for CPU 0 and CPU 1 (from NetPro). |
| IN | laddr_cp0, laddr_cp1 | WORD | Logical base addresses of CP 443-1 in slot 0 / slot 1 of the H-station (from HW Config). |
| IN | check_conn_cycle | TIME | Optional automatic re-check interval of the configured connections. |
| IN | use_all_conn | BOOL | If TRUE, MB_REDCL can use both path A and path B for redundancy switching. |
| IN | single_write | BOOL | TRUE = force Modbus function code 5/6 (write single) instead of 15/16 (write multiple) for write jobs. |
| IN | data_type_1..4, db_1..4, start_1..4 | misc. | Persistent job parameters for a second, third, and fourth queued job on the same path. |
| OUT | BUSY | BOOL | TRUE while a job is in progress. ENQ may not be re-asserted while BUSY = TRUE. |
| OUT | DONE | BOOL | TRUE for one OB35 cycle after a successful job. Reset by the next rising edge at ENQ. |
| OUT | ERROR | BOOL | TRUE for one OB35 cycle if the job finished with an error. The corresponding STATUS_* word then contains the error code. |
| OUT | STATUS_0A, STATUS_1A | WORD | Error / status word for the path-A connection on CPU 0 / CPU 1. |
| OUT | STATUS_0B, STATUS_1B | WORD | Error / status word for the path-B connection on CPU 0 / CPU 1. |
| OUT | IDENT_CODE | WORD | Internal identification code; used for diagnostics only. |
| OUT | LICENSED | BOOL | TRUE when the library license has been validated against REG_KEY. |
| IN_OUT | DB_1 .. DB_4 (data area references) | ANY | Data areas for the Modbus payload. |
2.2 DATA_TYPE values and corresponding Modbus function codes
| DATA_TYPE | Modbus function code (read) | Modbus function code (write) | Object | LENGTH unit |
|---|---|---|---|---|
| 1 | FC 02 (Read Discrete Inputs) | FC 05 / FC 15 | Coil / discrete input (1 bit) | Bits |
| 2 | FC 04 (Read Input Registers) | n/a | Input register (16 bit) | Words |
| 3 | FC 03 (Read Holding Registers) | FC 06 / FC 16 | Holding register (16 bit) | Words |
| 4 | FC 04 (Read Input Registers) | n/a | Input register (alias) (16 bit) | Words |
LENGTH always expresses the number of Modbus objects, not bytes. For register access (DATA_TYPE = 2, 3, 4), LENGTH = 5 means 5 words = 10 bytes of payload. For coil/input access (DATA_TYPE = 1), LENGTH = 5 means 5 bits. Mismatching this is one of the most common reasons MB_REDCL reports W#16#A042 / W#16#A043.
3. Root Cause Analysis
Every reproducible W#8304 / W#A083 case in the source material maps to one of the following five causes. They are listed in order of frequency.
3.1 Status W#16#8304 – "No connection to the communication partner"
W#16#8304 is the SIMATIC standard error code meaning "the configured connection is not established at the moment the job is sent". The Modbus request could not be transmitted because the TCP connection was down, not yet opened, or had been aborted. Common underlying reasons include:
- The TCP connection in NetPro is configured as a passive (server) connection – i.e., "Accept incoming connection" – on the S7-400H side, but the third-party device (here, the Ventyx / eDNA "VMS") does not dial in.
- Both connections in the redundant pair are passive and the partner never dials in.
- The partner IP address, partner port, or own port (default 502 for Modbus/TCP) is wrong in the connection properties.
- The CP 443-1 firmware does not support Modbus/TCP keep-alive on the configured port (verify firmware version, see Section 8).
- Connection ID (
id_0_a/id_1_a) handed to MB_REDCL does not match the ID assigned in NetPro.
3.2 Status W#16#A083 – "TCP error during send/receive"
W#16#A083 indicates that the TCP send or receive call inside the Modbus/TCP stack returned a non-success error. The most frequent triggers in the field are:
-
ENQis set on every OB35 cycle while a previous job is still pending. The block therefore re-issues a request on top of an in-flight job, which the underlying CP rejects. - The application uses a fresh ENQ rising edge but the OB35 cycle is shorter than the time the Modbus server needs to answer (typical eDNA or third-party server round-trip is 50–200 ms, while OB35 may be 20–50 ms). The block enters its error state at the next cycle.
- Firewall / router silently drops Modbus/TCP frames; the CP eventually reports a TCP-level reset.
3.3 WRITE_READ polarity
The example code in the original post sets WRITE_READ = TRUE while the user comment states "I want to read from the server". With WRITE_READ = TRUE, MB_REDCL builds a Modbus write request, but the application does not provide a source DB of the requested length. The block therefore either ignores the request (no DONE) or surfaces W#16#A083 because the stack cannot build a valid FC 06/16 PDU. For pure read polling, WRITE_READ must be FALSE.
3.4 LENGTH unit confusion
The user's code writes L 5 / T "CONTROL_DAT".LENGTH with DATA_TYPE = 3 (holding register). For DATA_TYPE = 3, LENGTH is in registers (words), not bytes. With LENGTH = 5, MB_REDCL will read 5 holding registers from address 834. This happens to be the correct interpretation here, but the user must be aware that for FC 01/02 (coils/inputs) the same constant would mean 5 bits. When in doubt, always cross-check with the server's Modbus map and the function code in the wire capture.
3.5 ENQ trigger logic in OB35
MB_REDCL must be called cyclically – the block is stateful and uses the cyclic call to advance its internal handshake with the CP. The rising edge at ENQ, however, must only be applied once per finished job. The original code resets ENQ in the same cycle that ENQ was set:
A "CONTROL_DAT".ENQ
R "CONTROL_DAT".ENQ // reset in the SAME cycle
This is technically a one-cycle pulse and is acceptable, provided that the next rising edge is only generated when the previous job has finished (BUSY = FALSE). The original code, however, triggers ENQ every OB35 cycle without checking BUSY. Combined with a down TCP connection, this floods the CP with retries and produces the continuous W#8304 / W#A083 pattern observed.
4. Hardware Configuration Constraints
MB_REDCL is a redundant Modbus/TCP client block and requires a redundancy-capable topology. The supported hardware combinations are documented in the library manual and are strict:
| Configuration | Supported? | Notes |
|---|---|---|
| S7-400H CPU pair (e.g., two CPU 412-3H / 414-3H / 416-3H / 417-4H) with 2 × CP 443-1 | Yes | Native use case. Each CPU owns one CP; MB_REDCL runs on both via the S7-400H software redundancy. |
| 1 × S7-400 single CPU (e.g., CPU 414-3) with 2 × CP 443-1 | Yes | Both CPs connected to a single CPU; MB_REDCL provides CP-level redundancy without H-CPU. |
| 1 × S7-300 single CPU (e.g., CPU 315-2 DP / 317-2) with 2 × CP 343-1 | Yes | Library variant for S7-300 is the regular MB_CLIENT or the Modbus/TCP CP Red package with 2 CPs. |
| 2 × S7-300 CPUs each with one CP 343-1 | No | The S7-300 does not provide software redundancy for CPs. Each CPU can only establish connections that were configured for its own CP. |
| S7-1200 / S7-1500 with 2 × CP 1543-1 | No | Use MB_RED_CLIENT in TIA Portal V17+ instead. See MB_RED_CLIENT in TIA Portal for the S7-1200/1500 equivalent. |
5. Step-by-Step Solution
Apply the steps below in order. Each step is followed by a verification check.
Step 1 – Confirm the CP 443-1 firmware supports the Modbus/TCP CP Red library
Verify the firmware version on both CP 443-1 modules. The minimum required firmware for the Modbus/TCP CP Red library is documented in the library manual "SIMATIC Modbus/TCP - Redundant Communication via CP 443-1 in H-Systems" (Siemens entry ID 109754927). A CP 443-1 with firmware < V3.2 typically does not support the redundancy functions. If the firmware is older, update it with the SIMATIC Manager's "PLC → Update Firmware" function.
Verification: In HW Config, right-click the CP 443-1 → Object Properties → Diagnostics tab. The firmware version must match or exceed the version listed in the library manual.
Step 2 – Create the TCP connections in NetPro with active connection establishment
- Open the S7 project in SIMATIC Manager.
- Open NetPro (Options → NetPro).
- Insert a new TCP connection for each CP. In the H-station, this means one connection from CPU 0 / CP 443-1 (rack 0) and one from CPU 1 / CP 443-1 (rack 1) to the VMS partner.
- Open the connection properties → General tab. Confirm the connection direction is set to "Establish an active connection". If it reads "Accept incoming connection", the S7 is acting as the TCP server and will not dial out – this is the single most common cause of W#8304.
- Set the partner IP address (the VMS server), the partner port (default 502), and the local port (any free port, or leave blank to let the OS assign).
- Save and compile NetPro, then download the connection configuration to both CPUs.
Verification: In NetPro → Connections, the icon for the connection should be a solid arrow from the S7-400H to the partner, and the status byte in the connection diagnostics (online → connection status) should read 01 (connection established) after a few seconds.
Step 3 – Capture the connection IDs and CP logical base addresses
For each connection created in Step 2, note:
-
Connection ID (a number assigned by NetPro – usually 1, 2, 3, …). Hand it to MB_REDCL at
id_0_a(for the connection that is active on CPU 0) orid_1_a(for the connection that is active on CPU 1). The same for path B atid_0_b/id_1_b. -
CP logical base address from HW Config (for example,
256for CP in slot 4). Hand it to MB_REDCL atladdr_cp0(CPU 0) orladdr_cp1(CPU 1).
Verification: Cross-check that each ID used in the program exists in the NetPro download. An ID that exists in the program but not in NetPro is the most common silent cause of W#8304 on cold start, because the connection table in the CPU has no entry for that ID.
Step 4 – Wire the library block to the right FB instance DB
Each call of MB_REDCL must use a dedicated instance DB (multi-instance is allowed). Renaming or rewiring the FB to a DB of the wrong type is the most common reason the outputs of the block show undefined or static values, and the DONE / ERROR / STATUS words never update. Make sure the call is:
CALL "MB_REDCL" , "IDB_Modbus_Client"
where IDB_Modbus_Client is an instance DB generated by STEP 7 when the FB is inserted into the S7 program. Do not hand the call a shared DB of the wrong type.
Step 5 – Set WRITE_READ, DATA_TYPE, START_ADDRESS, and LENGTH for read polling
For "read 5 holding registers starting at address 834 once per second":
| Parameter | Value | Meaning |
|---|---|---|
| DATA_TYPE | 3 | Holding register (FC 03 read / FC 06/16 write) |
| START_ADDRESS | 834 | Modbus start address (0-based or 1-based per server convention) |
| LENGTH | 5 | 5 words (10 bytes) of holding register payload |
| WRITE_READ | FALSE | Read request – the application reads from the server, not writes to it |
| UNIT | 1 | Path A (set to 2 to use path B) |
START_ADDRESS = 833 for a 0-based stack, or 834 if the block already adds the +1 offset. Verify against a wire capture (Wireshark with the modbus dissector) during commissioning.
Step 6 – Correct the ENQ trigger logic
Re-arm the trigger only when the previous job has finished (BUSY = FALSE) and the cycle timer (1 s for the user's requirement) has elapsed:
// 1-second cyclic trigger
A "TICK_1S".Q // 1 Hz clock from OB35 (every 20th call at 50 ms)
AN "IDB_Modbus_Client".BUSY
S "CONTROL_DAT".ENQ // rising-edge request
// Reset ENQ in the same cycle (single-cycle pulse)
A "CONTROL_DAT".ENQ
R "CONTROL_DAT".ENQ
Do not re-assert ENQ while BUSY is TRUE. The original code did not check BUSY, which is the second half of the W#A083 problem.
Step 7 – Apply the correct license key
MB_REDCL requires a valid license key at the REG_KEY input. The key is shipped with the library and is typically a 24-character string. With an invalid or missing key, the LICENSED output stays FALSE and the block reports W#16#A005 / W#16#A007. For the Modbus/TCP CP Red library, the key is bound to the CP serial number. If the CP is replaced, the license must be re-applied.
6. Corrected STL Code for OB35
Below is a production-ready call pattern for MB_REDCL running in OB35, polling once per second with a 50 ms OB35 base cycle. The pattern is derived from the original post but applies the corrections documented above.
// === OB35, 50 ms base cycle, 1 s poll period ===
// Trigger every 20th OB35 call (= 1.0 s)
A "TICK_1S".Q // clock generator
AN "IDB_Modbus_Client".BUSY // only when no job is pending
S "CONTROL_DAT".ENQ
A "CONTROL_DAT".ENQ
R "CONTROL_DAT".ENQ // 1-cycle pulse
// Job parameters (read holding register 834, 5 words, path A)
L 3
T "CONTROL_DAT".DATA_TYPE // holding register
L 834
T "CONTROL_DAT".START_ADDRESS // Modbus start address
L 5
T "CONTROL_DAT".LENGTH // 5 words
CLR
= "CONTROL_DAT".WRITE_READ // FALSE = read
L 1
T "CONTROL_DAT".UNIT // path A
CALL "MB_REDCL" , "IDB_Modbus_Client"
ENQ := "CONTROL_DAT".ENQ
DATA_TYPE := "CONTROL_DAT".DATA_TYPE
START_ADDRESS := "CONTROL_DAT".START_ADDRESS
LENGTH := "CONTROL_DAT".LENGTH
WRITE_READ := "CONTROL_DAT".WRITE_READ
UNIT := "CONTROL_DAT".UNIT
MONITOR := FALSE
REG_KEY := "LICENSE_DB".REG_KEY
id_0_a := W#16#0001 // path A, CPU 0 - from NetPro
id_1_a := W#16#0002 // path A, CPU 1 - from NetPro
id_0_b := W#16#0003 // path B, CPU 0 - from NetPro
id_1_b := W#16#0004 // path B, CPU 1 - from NetPro
laddr_cp0 := W#16#0100 // CP 443-1 base address, CPU 0 - from HW Config
laddr_cp1 := W#16#0200 // CP 443-1 base address, CPU 1 - from HW Config
check_conn_cycle:= T#5s
use_all_conn := TRUE
single_write := FALSE
BUSY := "CONTROL_DAT".BUSY
DONE := "CONTROL_DAT".DONE
ERROR := "CONTROL_DAT".ERROR
STATUS_0A := "CONTROL_DAT".STATUS_0A
STATUS_1A := "CONTROL_DAT".STATUS_1A
STATUS_0B := "CONTROL_DAT".STATUS_0B
STATUS_1B := "CONTROL_DAT".STATUS_1B
IDENT_CODE := "CONTROL_DAT".IDENT_CODE
LICENSED := "CONTROL_DAT".LICENSED
7. Verification and Diagnostics
After the fix is applied, run the verification matrix below.
| Check | Expected result | How to read |
|---|---|---|
LICENSED output |
TRUE | Library license is valid. If FALSE, the key in REG_KEY is wrong or unbound. |
STATUS_0A / STATUS_1A
|
W#16#0000 between jobs; A090 transiently during a job | W#16#A090 is an informational code ("AG_CNTRL") and is normal during a job. W#16#8304 / W#16#A083 indicate a connection problem. |
BUSY |
TRUE while a job is in progress, FALSE otherwise | Use BUSY as the gating condition for the next ENQ pulse. |
DONE counter |
Increments once per 1 s poll | If the Done counter stays at 0 and the Error counter increments, the connection is still down. |
ERROR counter |
0 in steady state, may briefly count during failover | Persistent increment points to W#8304, W#A083, or license problem. |
| NetPro online connection status | 01 (= established) on both path A and path B | Online → right-click connection → Connection status. A status of 02 or 04 means "not established / aborting". |
| Wireshark on CP 443-1 port | Modbus/TCP polls (function code 03) every 1 s, response with function code 03 and 10 bytes of payload | Set up a SPAN port on the managed switch that the S7-400H rack is connected to, filter on port 502. |
| CP 443-1 diagnostic buffer | No "connection aborted" entries | HW Config → CP 443-1 → Module Information → Diagnostic Buffer. |
8. Common Status Codes Reference
| Code | Meaning | Severity | Remediation |
|---|---|---|---|
| W#16#0000 | No error | OK | - |
| W#16#8304 | Connection to partner not established | Error | Set connection to active in NetPro; verify IP, port, route, firewall |
| W#16#A083 | TCP send/receive error | Error | Re-trigger ENQ only when BUSY = FALSE; check ENQ rate vs. server response time |
| W#16#A090 | Job running on connection (informational) | OK | Suppress in application logic – not an error |
| W#16#A005 | License key invalid | Error | Re-enter REG_KEY; rebind to CP serial number |
| W#16#A007 | License not found in CPU | Error | Re-install license in the CPU's license database |
| W#16#A042 | DATA_TYPE invalid | Error | Use 1, 2, 3, or 4 only |
| W#16#A043 | LENGTH = 0 or > max for DATA_TYPE | Error | Coil/input: 1–2000 bits; register: 1–125 words |
| W#16#A044 | START_ADDRESS out of range | Error | Check server Modbus map; address ≤ 65535 |
| W#16#A091 | Connection being torn down | Warning | Transient during redundancy switch; do not evaluate |
9. Field-Commissioning Checklist
- Confirm CP 443-1 firmware ≥ minimum version specified in the Modbus/TCP CP Red manual.
- Open HW Config and confirm both CP 443-1 modules are in the correct slots of the H-rack (UR2-H).
- Open NetPro and confirm two TCP connections exist, both with active establishment.
- Compile NetPro, download to both H-CPUs, and verify online connection status = 01.
- Open the program in STEP 7 and confirm each MB_REDCL call has a dedicated instance DB.
- Confirm
WRITE_READmatches the intended direction (FALSE for read, TRUE for write). - Confirm
LENGTHis in registers (words) for DATA_TYPE 2/3/4, and in bits for DATA_TYPE 1. - Confirm
id_0_a,id_1_a,id_0_b,id_1_bmatch the IDs assigned in NetPro. - Confirm
laddr_cp0/laddr_cp1match the CP base addresses in HW Config. - Confirm
REG_KEYcontains a valid license key for the serial number of the active CP. - Implement BUSY-gated ENQ logic; do not retrigger on every OB35 cycle.
- Run a 60-second observation. The Done counter should increment at the configured poll rate, the Error counter should stay at 0.
- Capture traffic with Wireshark on port 502 to confirm FC 03 polls are leaving the S7 and valid responses are returning.
- For a redundant site, pull the network cable from the primary CP and confirm the secondary CP takes over (STATUS_0A / STATUS_0B transition, but communication continues).
- Document the ID → CP mapping in the project notes for future maintenance.
10. Edge Cases and Alternate Platforms
10.1 Migrating to S7-1200/1500 with MB_RED_CLIENT
Newer S7-1200 (FW 4.4+) and S7-1500 stations use the TIA Portal instruction MB_RED_CLIENT in place of MB_REDCL. The interface is similar but parameter names differ: REQ replaces ENQ, DONE / BUSY / ERROR are identical, and the connection IDs are replaced by the symbolic Connection reference. The redundancy topology is still 1 × S7-1500 CPU with 2 × CP 1543-1. See the official TIA Portal manual at MB_RED_CLIENT – Redundant communication over PROFINET as a Modbus/TCP client for the exact parameter mapping.
10.2 Single-CPU S7-300 with 2 × CP 343-1
If the user has an S7-300 station and wants the same redundant Modbus/TCP behavior, the same library works with the S7-300 variant. The two CP 343-1 modules are wired to the same CPU. The two H-specific parameters (id_0_a / id_1_a) collapse to a single connection ID per CP. laddr_cp0 is set to the base address of the first CP, laddr_cp1 to the second. The license key is bound to the CPU serial number rather than the CP.
10.3 Polling rate vs. OB35 cycle
For a 1 s poll rate, use an OB35 cycle of 50 ms and a counter that fires every 20th call. For a sub-100 ms poll rate, drop the cycle to 10 ms (OB35 supports 1 ms minimum) and confirm the Modbus server can keep up. If the server's response time is greater than the cycle, the BUSY gate will throttle the next ENQ automatically – no extra logic required.
10.4 S7-300 software redundancy: not supported
Modbus/TCP is not part of the S7-300 software-redundancy model. Two S7-300 stations linked via PN redundancy cannot share a single MB_REDCL block. Each station can only run its own MB_CLIENT with its own CP, and a takeover will not transfer the active Modbus connection. Plan for an S7-400H or a single-CPU S7-300 with two CPs if redundancy is required.
10.5 Status word polling
When integrating MB_REDCL into a higher-level diagnostics display (WinCC, PCS 7, or a custom HMI), the recommended approach is to expose only the steady-state DONE counter, the ERROR counter, and the latched Save_STATUS_0A / Save_STATUS_1A words (capture the status on the rising edge of ERROR, exactly as in the original post). Do not display transient W#16#A090 as an alarm – it will cause alarm floods at every poll.
FAQ
What does status W#16#8304 from MB_REDCL mean?
W#16#8304 means the Modbus/TCP request could not be sent because the TCP connection is not established. In 90% of cases the connection in NetPro is configured as passive ("Accept incoming connection") instead of active. Change the connection direction to "Establish an active connection" in NetPro, recompile, and download.
Why does MB_REDCL keep returning W#16#A083 even though the connection is up?
W#16#A083 is a TCP send/receive error. It usually means the application is re-asserting ENQ while a previous job is still in progress. Gate ENQ with AN "IDB".BUSY so a new request is only fired when BUSY is FALSE.
What is the unit of the LENGTH parameter for MB_REDCL?
LENGTH is in Modbus objects, not bytes. For DATA_TYPE = 2, 3, or 4 (registers), LENGTH is in words (1 word = 2 bytes). For DATA_TYPE = 1 (coils/inputs), LENGTH is in bits. LENGTH = 5 with DATA_TYPE = 3 means 5 holding registers = 10 bytes of payload.
Can MB_REDCL run on two separate S7-300 CPUs in a software-redundancy configuration?
No. Modbus/TCP is not part of S7-300 software redundancy. Each S7-300 CPU can only establish connections that are configured for its own CP. For a redundant Modbus/TCP client, use an S7-400H station, a single S7-400 CPU with two CP 443-1, or a single S7-300 CPU with two CP 343-1.
Do I need a license key for MB_REDCL, and where do I get one?
Yes. MB_REDCL ships with the optional library "SIMATIC Modbus/TCP - CP Red". A license key bound to the CP serial number (for CP 443-1) or the CPU serial number (for S7-300) must be loaded and passed to the block via the REG_KEY input. If the license is missing, the LICENSED output is FALSE and the block reports W#16#A005 / W#16#A007.
Should WRITE_READ be TRUE or FALSE for reading from a Modbus/TCP server?
FALSE. WRITE_READ = TRUE triggers a Modbus write function code (FC 05/06/15/16) and requires a source data block of the requested length. For pure read polling, always set WRITE_READ = FALSE so MB_REDCL issues FC 03 (holding register) or FC 04 (input register) requests.