1. Problem Description
When the central processing unit of a SIMATIC S7-400 station is exchanged in STEP 7 V5.x HW Config and the resulting configuration is recompiled in NetPro, the following PROFIBUS validation error can appear even though the bus cabling, connectors, terminators, and slave addresses are correct:
The parameter Tslot on the PROFIBUS subnet 'PROFIBUS(<line_name>)' outside of STEP7 is set to a value that is too low. The following applies: Tslot >= Tid2 + 15
The error indicates a violation of the PROFIBUS bus timing rule (TSL ≥ TID2 + 15 Tbit) that the STEP 7 compiler enforces before the bus parameters are downloaded to the DP master. The message is independent of the physical wiring; it is a purely logical/parameter error in the offline project and will block a successful NetPro compile and a subsequent download of the PROFIBUS configuration.
Typical environments in which this symptom appears are mixed S7-400 cells with multiple masters, distributed I/O on ET 200M / ET 200S, SEW-Eurodrive MOVIMOT / MOVIDRIVE drives on PROFIBUS-DP, and operator panels (OP/TP/MP) on the same segment, exactly the topology described in the originating case (4 PLCs, 4 OPs, several SEW drives, all sharing one DP backbone).
2. Affected Hardware and Firmware
The symptom is observed when an S7-400 CPU is replaced by a different variant in the same S7-400 family. The two part numbers appearing in this specific case are:
| MLFB (Order Number) | Model | Interfaces | Firmware | Role |
|---|---|---|---|---|
| 6ES7 414-2XG03-0AB0 | CPU 414-2 DP | 1× MPI/DP, 1× DP master/slave | V4.0 / V4.1 typical | Original |
| 6ES7 414-2XK05-0AB0 | CPU 414-3 PN/DP | 1× MPI/DP, 1× DP master/slave, 1× PROFINET (2-port switch) | V5.x typical | Replacement |
The replacement is non-trivial: the 2XG03 part is a pure DP device, while the 2XK05 is a PN/DP device. STEP 7 stores the bus timing defaults per CPU MLFB and per firmware version, so the timing table the compiler sees after the replacement can be inconsistent with the values that were authored by hand in the original project.
Refer to the official product manuals for the electrical, mechanical and functional limits of each CPU:
- SIMATIC S7-400 CPU 414-2 DP (6ES7 414-2XG03-0AB0) Manual
- SIMATIC S7-400 CPU 414-3 PN/DP (6ES7 414-2XK05-0AB0) Manual
- STEP 7 V5.5 - Programming and Operating Manual
3. Root Cause Analysis
The validation rule that fires in NetPro is derived from IEC 61158 / IEC 61784 (PROFIBUS DP). It is the same constraint the bus itself enforces at runtime; STEP 7 just exposes it as a compile-time check.
The mathematical rule being violated is:
Tslot [Tbit] >= Tid2 [Tbit] + 15 [Tbit]
with all quantities expressed in bit times (Tbit = 1 / baud rate). The reason this rule exists is that the DP master has to allow enough "slot" time between sending a request to a slave and receiving the matching response to absorb the worst-case station delay (TSM) of every repeater, the propagation through the cable, the quiet time (TQUI), the slave's processing, the reply transmission, and the idle time (TID2) the bus enforces before the next access is permitted.
When a CPU is replaced, the bus profile assigned in the project is left as it was on the previous CPU. If the previous engineer selected User-defined bus profile and entered the timing values manually, the new CPU's firmware revision can carry slightly different defaults in its GSD-derived profile, and the compiler will detect the inconsistency. Conversely, if the project was set to DP or Standard profile, the compiler should be able to recompute a consistent set, but in some combinations of firmware revision and project XML structure the auto-recalculation also fails to converge and the error persists.
Three common paths lead to the error in practice:
- Hand-edited values in a previous project — the original integrator set the bus profile to User-defined and entered values that were valid for the old CPU's DP ASIC characteristics. The new CPU has a marginally different default TID2, so the inequality TSL ≥ TID2 + 15 no longer holds with the same TSL.
- Mixed DP-V0 and DP-V1 slaves on the same segment — DP-V1 slaves require longer monitoring and parameterization windows; the compiler can occasionally under-size TID2 for the worst-case slave if the auto-profiler does not see the DP-V1 capabilities in the imported GSD.
- Bus profile set to DP but baud rate set so high that Tbit is too small — for a 12 Mbit/s segment Tbit = 83.3 ns; 15 Tbit = 1.25 µs, which is already below the quiet time of many repeaters. If TSL was authored for 1.5 Mbit/s and then the baud rate is raised, the inequality fails.
4. PROFIBUS Bus Timing Parameters Reference
The following table summarizes the parameters that govern a PROFIBUS DP segment, the units used by STEP 7 (Tbit), and the role of each parameter. The values listed are representative — actual values must be derived from the GSD files and the bus profile selected.
| Parameter | Symbol | Typical role | Typical range @ 1.5 Mbit/s | Typical range @ 12 Mbit/s |
|---|---|---|---|---|
| Bit time | Tbit | 1 / baud rate | 666.7 ns | 83.3 ns |
| Slot time | TSL = Tslot | Wait window for a slave response after a master request | 200 – 1023 Tbit | 200 – 1023 Tbit |
| Idle time 1 | TID1 | Minimum delay after a reply before a new request | 3 – 255 Tbit | 3 – 255 Tbit |
| Idle time 2 | TID2 = Tid2 | Minimum delay between two bus accesses | 10 – 255 Tbit | 10 – 255 Tbit |
| Station delay max | TSM | Worst-case repeater/slave delay | 1 – 1000 Tbit | 1 – 1000 Tbit |
| Setup time | TSET | Time to set up a new master | 1 – 255 Tbit | 1 – 255 Tbit |
| Quiescent time | TQUI | Quiet time on the bus before a new transmission | 0 – 255 Tbit | 0 – 255 Tbit |
| Target rotation time | TTR | Worst-case token rotation | 256 – 16 777 215 Tbit | 256 – 16 777 215 Tbit |
STEP 7 exposes these values under PROFIBUS Properties → Bus Parameters and shows them in Tbit, with a Tbit time computed from the selected baud rate. The rule the compiler checks is:
Tslot >= Tid2 + 15 (1)
with a strong recommendation from Siemens and IEC 61158 that TSL should also satisfy TSL > TSM_max + TQUI + 2·TID1 for the worst-case repeater topology. Equation (1) is the hard constraint; equation (2) is the practical one that keeps the bus from stalling.
Tslot > Tsm_max + Tqui + 2 * Tid1 (2)
5. Quick Diagnostic Procedure
Run the steps below in order; the first one that resolves the issue is the canonical fix.
- Recompile HW Config from the master station. Open the S7-400 master, double-click the DP interface line, switch to the Bus Parameters tab, and read the values of Tslot and Tid2. The error message itself prints the violating pair — write them down.
- Check the bus profile on the Network Settings tab. The drop-down lists DP, Standard, and User-defined. If it is on DP or Standard, click Recalculate and accept the new values, then save the project. Recompile NetPro. If the error is gone, the timing was simply stale.
- If the profile is User-defined, switch the profile back to DP and click Recalculate. STEP 7 will overwrite the manual values with valid ones for the current CPU and baud rate. Save, recompile NetPro. If the error is gone, the manual values were the problem; note them in the project documentation for future reference.
- If neither recompilation path clears the error, the project XML is in a corrupt state. Build a fresh S7 project, re-import the hardware from the most recent backup, re-create the DP slaves, then copy the symbol table and the program blocks from the old project. This is the most reliable escape hatch and is the procedure recommended by Siemens support for any timing-validation error that survives a clean recompile.
6. Canonical Solution A — Use the Re-calculate Function
This is the preferred approach for any profile other than User-defined, and for most cases where the project has been authored in User-defined as well. STEP 7 uses the GSD files of the slaves, the selected baud rate, and the repeater topology to derive a valid timing set.
- Open the S7 project in SIMATIC Manager.
- Double-click Hardware on the master station that owns the offending DP segment.
- In HW Config, click the DP interface row of the CPU, then right-click and choose Properties → PROFIBUS interface DP master → Properties.
- On the Bus Parameters tab, confirm the baud rate (e.g., 1.5 Mbit/s) and read the Profile drop-down.
- If the Profile is DP or Standard, click Recalculate. STEP 7 will write new TSL and TID2 values directly into the table.
- Click OK to confirm. STEP 7 will warn you that the values are about to be overwritten — confirm.
- Click Station → Save and Compile.
- Open NetPro, right-click the subnet and choose Compile and Check All. The error must no longer appear.
- Download the HW Config to the master CPU.
7. Canonical Solution B — Switch to a User-defined Profile and Author Valid Values
Use this path when the network contains a repeater topology or non-default cabling that the standard profiler cannot model, or when the project must run on a fixed set of values that the field team has previously qualified. The procedure below derives values that satisfy equation (1) and equation (2).
- In the same Bus Parameters tab, set the Profile drop-down to User-defined.
- Set the baud rate to the desired value (e.g., 1.5 Mbit/s, Tbit = 666.7 ns).
- For each slave, the GSD reports a max Tsdr (station delay) value. Identify the largest max Tsdr across the segment and add it to TQUI + 2·TID1 + 1 Tbit. That sum is the lower bound for TSL per equation (2).
- Set TID2 to the GSD-reported min Tsdr of the slowest slave, plus 1 Tbit safety margin.
- Verify equation (1): TSL >= TID2 + 15. If not, raise TSL by the deficit.
- Click OK and recompile.
Worked example for a 1.5 Mbit/s segment with three repeaters in series, two DP-V1 slaves (largest max Tsdr = 175 Tbit), TQUI = 0, TID1 = 10 Tbit:
Tbit = 666.7 ns
Tqui = 0 Tbit
Tid1 = 10 Tbit
max_Tsdr = 175 Tbit (worst slave)
Tslot_min = max_Tsdr + Tqui + 2 * Tid1 + 1
= 175 + 0 + 20 + 1
= 196 Tbit (lower bound from eq. 2)
Tid2 = max(min_Tsdr_slowest_slave) + 1
= 11 + 1
= 12 Tbit
Tslot_check (eq. 1): 196 >= 12 + 15 = 27 OK
A safe value is Tslot = 300 Tbit, Tid2 = 12 Tbit at 1.5 Mbit/s. At 12 Mbit/s, Tslot is in the same Tbit range, but the actual time on the wire is 12 times shorter, so the bus is far more sensitive to TSM for the repeaters — in practice, no more than 3 repeaters in series at 12 Mbit/s.
8. NetPro Recompile and Download
After the timing values are correct in HW Config, NetPro must be re-validated to propagate the values to all masters on the subnet. The procedure is:
- Open NetPro. Right-click the offending subnet and choose Compile and Check All (or use Network → Compile and Check All).
- Read the lower status bar — if no validation errors are listed, the build is clean.
- From HW Config on each affected master, click PLC → Download to Target System and select Download to Target System → Entire Station so that the DP interface parameters are pushed together with the slave parameterization.
- On the target CPU, switch to STOP for the duration of the download if the bus is going to a different topology, then back to RUN. Watch the diagnostic buffer of the CPU for SF / BF (bus fault) entries.
If the error reappears on a different subnet after a CPU swap, the same procedure applies to that subnet's master, with the appropriate baud rate and topology for that segment.
9. CPU Variant Comparison and Migration Caveats
| Property | 6ES7 414-2XG03-0AB0 | 6ES7 414-2XK05-0AB0 | Migration impact |
|---|---|---|---|
| DP interface count | 1 (master/slave) | 1 (master/slave) | No port change |
| PROFINET interface | None | 2-port switch | New subnet may be visible in NetPro |
| Work memory | 0.7 MB code / 0.7 MB data (typical) | 2 MB code / 4 MB data (typical) | Existing program will load; some SFCs are upgraded |
| DP-V2 features (clock sync, etc.) | Limited (firmware dependent) | Full (firmware dependent) | Auto-profile for Tslot can be re-derived |
| STEP 7 version required | STEP 7 V5.4 SP5 or later | STEP 7 V5.5 SP4 / SP5 with HSP | Older STEP 7 will not list the new MLFB |
The migration is not just a CPU swap; the project must be updated with the proper Hardware Support Package (HSP) so that the new MLFB resolves to the right firmware-derived bus timing defaults. Refer to the SIMATIC S7-400 S7-400H Fault-tolerant Systems Installation List for the exact firmware / STEP 7 compatibility matrix and to the HSP (Hardware Support Package) installation manual for the install path.
10. Verification Checklist
After applying Solution A or B and before placing the segment back into production, walk through this list:
- [ ] HW Config compiles without warnings on the master station.
- [ ] NetPro Compile and Check All reports zero errors and zero warnings.
- [ ] The diagnostic buffer of the master CPU is empty of SF (system fault) and BF (bus fault) entries after a power cycle.
- [ ] Every DP slave is in the Exchange state in the DP Slave Diagnostics view of HW Config.
- [ ] All SEW-Eurodrive MOVIDRIVE / MOVIMOT nodes report Bus OK on their parameter units (parameter P080 / P083 depending on the unit type).
- [ ] All operator panels respond to tag polling within the configured acquisition cycle.
- [ ] A 10-minute continuous run on the master with no timeout on the bus is logged.
11. Preventive Measures and Field Notes
- Always back up the project (including the GSDs installed at the time) before any CPU swap. The offline archive created with File → Archive contains the GSDs and is the only reliable way to roll back.
- When authoring timing values manually, capture the baud rate, the largest max Tsdr across the slaves, the number of repeaters, and the value of TQUI as a comment in the project. This is invaluable when the next CPU swap happens five years later.
- Avoid setting the bus profile to User-defined unless the topology is non-standard (more than two repeaters, mixed DP-V0/DP-V1/DP-V2, or very long segments). For standard segments, DP profile + Recalculate is the most robust choice.
- After any CPU firmware upgrade, recalculate the bus parameters even if the project compiles cleanly. The DP master ASIC timing parameters can change between firmware versions.
- Always install the latest GSD for every DP slave in the segment, and never mix GSD revisions across slaves of the same part number. The PROFIBUS configuration tool derives TID2 from the slowest slave's min Tsdr; a stale GSD can mis-state this value.
12. Frequently Asked Questions
What does the error "Tslot >= Tid2 + 15" mean in STEP 7?
It means the offline PROFIBUS bus parameters in your STEP 7 project violate equation (1) of the PROFIBUS timing rules: the slot time (Tslot) is smaller than the idle time (Tid2) plus 15 bit times. STEP 7 blocks the NetPro compile to prevent an inconsistent configuration from being downloaded to the DP master, since at runtime the master would either time out waiting for slave responses or stutter on the bus.
Can I just raise Tslot to silence the error?
Yes, raising Tslot to a value that satisfies Tslot >= Tid2 + 15 will silence the validation. However, raising Tslot too high degrades the bus throughput because the master waits longer for every reply; the lower bound from equation (2) — Tslot > Tsm_max + Tqui + 2*Tid1 — is the practical minimum. Click Recalculate in the Bus Parameters tab to let STEP 7 derive a value that balances both rules.
Why does the error appear only after a CPU swap and not before?
The bus profile timing defaults in STEP 7 are CPU-specific and firmware-specific. A change of CPU (for example from 6ES7 414-2XG03-0AB0 to 6ES7 414-2XK05-0AB0) brings different default values for Tid2 and Tslot, so a project that was valid for the old CPU can become invalid for the new one. Re-running Recalculate on the new CPU's bus profile aligns the values to the new defaults.
Is the error related to bad cabling or shielding?
No. The Tslot >= Tid2 + 15 check is purely an offline validation of the project parameters; it is independent of the physical cable length, shielding, baud rate, or connector quality. Cable-related faults typically show up as a BF (bus fault) LED on the master and a "Slave failure" or "Station failure" entry in the diagnostic buffer, not as a NetPro compile error.
Do I need to use User-defined profile to fix the issue?
Not usually. The standard recommendation is to keep the profile as DP and click Recalculate on the Bus Parameters tab; this gives STEP 7 the chance to derive consistent timing from the GSDs. Switch to User-defined only when the topology is non-standard (extra repeaters, mixed DP-V0/DP-V1, very long cable) and the auto-profiler is unable to find a valid set.
Will the fix work the same way on a S7-400H fault-tolerant CPU pair?
The PROFIBUS timing rules are identical. On a S7-400H pair, the same Bus Parameters tab is exposed on both H-CPUs; after recalculation, download to both H-CPUs to keep their parameters synchronized. Refer to the S7-400H installation list for the H-specific bus profile notes.