Resolving PROFIdrive SubIndex Error on Siemens G120 CU240E-2

David Krause14 min read
SiemensTroubleshootingVFD / Drives
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Problem Overview

SINAMICS G120 drives equipped with a CU240E-2 PN Control Unit occasionally reject parameter downloads executed by StartDrive V16 Update 3 with a PROFIdrive error whose text reads "SubIndex invalid". The first failure usually names a BICO list parameter, most commonly p9462[22] ("List of the parameters for BICO signal source"). After a Control Unit reset, the same alarm reappears but points at a different sub-index on subsequent attempts, producing an apparently random pattern of failed parameters on each new download. The alarm persists even though the same values were previously accepted by the drive. The root cause is almost never a defect on the indexed parameter itself - it is a sequencing conflict between the StartDrive download state machine and the SINAMICS operating state.

This technical reference walks through the diagnostic logic, the affected firmware versions, the meaning of p9462, the role of the drive operating state, and a deterministic procedure to clear the alarm and complete the download.

Prerequisite read: the commissioning engineer must have rights to connect to the G120 in StartDrive V16 Update 3, must know the active drive firmware version (here V4.7.13 in the offline project vs. V4.7 SP13 SP2 on the physical device), and must keep the PROFINET topology online throughout the download.

Affected Hardware and Software

Component Version observed Notes
Power Module PM240-2 or compatible Power section firmware loaded with the Control Unit
Control Unit CU240E-2 PN (no Safety Integrated) PROFINET variant, 6SL3244-0BB13-1FA0 / -2FA0 family
Drive firmware (physical) V4.7 SP13 SP2 (V4.7.13) Read via r0964[4..7]
Drive firmware (StartDrive offline) V4.7.13 Selected in the device configuration in TIA Portal
Commissioning tool StartDrive V16 Update 3 (TIA Portal V16 Update 3) Starter is not used for CU240E-2 PN in V16
Telegram type Free PROFINET telegram, configurable PZD count Word widths chosen by system integrator
Application class Encoderless speed control for fan Application class 4 (Standard Drive Control)

The combination of a free telegram with a BICO-heavy commissioning dataset - where p9462[] is rebuilt during the write - tends to expose the SubIndex error. Drive firmware V4.7 SP13 SP2 and the matching Support Package contain the changes that tightened the sub-index handshake. Older HSP releases and HSP-less TIA Portal configurations are more vulnerable to the symptom.

Root Cause Analysis

Every PROFIdrive parameter has the structure (ParameterNumber, SubIndex). The SINAMICS drive exposes multi-element arrays (for example p9462[0..30]) by mapping each element to a unique sub-index of the same parameter number. When the StartDrive download service opens a parameter request it sends the parameter handle first, then opens each sub-index in turn. Three distinct mechanisms trigger a "SubIndex invalid" reply:

  1. Drive not in parameter-write state. The SINAMICS state machine distinguishes Commissioning, Ready, Run, Identification, Fault, and Identification. Indexed writes triggered while the drive is in the Commissioning state (the orange "Quick commissioning" prompt) are rejected for any parameter whose sub-index has not yet been built in the firmware. The reply is the generic SUBINDEX_NOT_SUPPORTED alarm.
  2. Length mismatch between StartDrive index view and drive index view. When the offline project uses V4.7.13 with a different BICO list count than the connected drive (for example V4.7 SP13 SP2 with extra BICO interconnect objects), the request asks for sub-indices the device has not yet allocated. Each request triggers the same generic reply - which is why the parameter number appears to "move" between attempts.
  3. BICO interconnections re-built during download. p9462[] ("List of the parameters for BICO signal source") is rebuilt the moment a BICO source/target pair is committed to the drive. If the StartDrive sequencer commits BICO sources before the sub-index table is refreshed, the freshly added index returns SUBINDEX_INVALID until the next download cycle restarts.

The field insight is that the rotating parameter number is misleading: the underlying fault is the drive state at the moment of the write, not the parameter itself. Once the drive has transitioned to Ready (ZSW1 bit 0 = 1, no bits in the "Commissioning" group), the same parameter set downloads cleanly on the next pass.

Diagnostic rule of thumb: if p9462, p9481, p9500, p9610, or any Safety parameter rotates as the failed index, first suspect the operating state. If the same parameter/index always fails across multiple resets, suspect data corruption in the parameter set and read it back with "Upload to PG" in StartDrive.

What p9462 Means in the SINAMICS BICO Model

Parameter p9462 is the BICO signal source list - the registry of all source-side parameters currently bound to a sink parameter via a BICO interconnection. Each element of p9462[] stores the parameter number, the sub-index and the bit number of one source. Typical contents on a fan application include:

Index Typical source object Typical use
[0] OFF1 / OFF2 / OFF3 Stops
[1..5] Control word bit selectors STW1 routing
[6..10] Setpoint sources (r0020, r0021, r0063) Speed setpoint chain
[11..15] Ramp-function generator RFG output monitoring
[16..20] V/f or vector controller outputs Closed-loop transitions
[21..29] Free BICO and technology extensions Application-specific wiring

During a full download StartDrive rewrites the entire BICO source list. Each write opens a new sub-index and asks the firmware for the current value of p9462[n] before sending the new entry. The handshake fails when the firmware temporarily cannot answer because the table is mid-rebuild, which then surfaces as SUBINDEX_INVALID.

Do not delete or "blank" p9462 from the project to bypass the alarm. The list is regenerated automatically by the firmware. The right place to manipulate BICO sources is through p9491 (BICO source object), p9492 (BICO source signal), and p9493 (BICO source bit) - or in StartDrive via the BICO editor (right-click → Disconnect all).

Drive Operating States Relevant to the Error

The SINAMICS G120 state machine is published in the SINAMICS G120 Parameter Manual and the SINAMICS G120 Operating Instructions. The transitions relevant to this fault are:

State (display) ZSW1 bit pattern Parameter writes allowed Typical user action
Commissioning (yellow text) Bit 0 = 0, bit 6 = 1 Partial - commissioning parameter set only Drive just powered up, or p0009 ≠ 0
Ready (green "Ready to run") Bit 0 = 1 All non-safety parameters Quick commissioning completed, no ON command yet
Run Bit 0 = 1, bit 2 = 1 Read-only Drive is modulating
Identification Bit 1 = 1 (Identification active) Blocked until finished p1910 = 1 in progress
Fault / Safe Stop Bit 3 = 0, bit 6 = 0 Resets only Check r0947 / r2124

The reported symptom - the user cannot leave the commissioning state because the drive automatically reverts on each download attempt - is the firmware's safety behavior. When StartDrive injects parameters that the state machine cannot validate while commissioning is active (specifically the BICO source list and the free-telegram layout), it rolls back to p0009 = 1 (Quick commissioning).

A separate but related state to watch is p0010 (commissioning parameter filter). While p0010 ≠ 0 the firmware blocks writes to a subset of parameters including the entire BICO list - exactly the parameters reported in the user's fault rotation.

Always confirm p0010 = 0 and p0009 = 0 before starting a download in StartDrive. The display "Quick commissioning" or the menu bar in StartDrive showing "Drive in commissioning" indicates that this assumption is violated. Both parameters are visible in the StartDrive parameter table under "Drive - all parameters".

Free Telegram versus Standard Telegram

The user is using a free PROFINET telegram (that is, Siemens telegram type "free PZD-12/12" or similar). Free telegrams are configured via:

  • p0922 = 999 (free telegram selection)
  • p2079 (PROFIdrive PZD telegram extended setpoint/strobe bit)
  • p2051[0..n] - list of PZD sent to the controller (drive inputs)
  • p2061[0..n] - list of PZD received from the controller (drive setpoints)

The length of these lists must agree with the StartDrive project and with the device configuration in HWCN (TIA Portal → Devices & Networks → PROFINET interface → Telegram configuration). A mismatch of even one PZD causes the firmware to reject the next sub-index write because the slot has not yet been allocated.

For an encoderless fan application the conventional telegram mapping is:

Slot Drive word Direction Signal Source/sink
PZD1 STW1 / ZSW1 bi-directional Control / status word 1 r2089[0] / p2050[0]
PZD2 NSOLL / NIST bi-directional Speed setpoint / actual r0063 / p1155
PZD3..n Optional bi-directional Current, torque, fault codes r0027, r0031, r0035

The user opted out of this with a custom telegram. As long as the count n in p2051/p2061 matches StartDrive's offline list and the BICO source list p9462 is properly populated before the telegram is initialised, the download succeeds. Reordering the BICO list after the free telegram is commissioned is what triggers the rotating SubIndex error.

Step-by-Step Resolution Procedure

  1. Save the project. TIA Portal → Project → Save As, including the StartDrive plug-in data. Keep a backup of the offline parameter set (.par) by exporting the online drive via StartDrive "Upload to PG".
  2. Read the current drive firmware. Connect online, navigate to Configuration → Commissioning → Overview and note the firmware string under "Drive firmware version". Compare to the offline project (V4.7.13). If they differ at SP level (V4.7 SP13 SP1 vs SP2), install the matching Support Package in TIA Portal.
  3. Force the drive to Ready. Open Configuration → Commissioning → Overview in StartDrive. The status panel must show Ready (green LED, ZSW1 bit 0 = 1). If the drive is in Quick commissioning, complete the wizard. If the wizard closes itself - the symptom reported by the user - clear p0009 and p0010 manually to 0 in the parameter table.
  4. Temporarily switch to standard telegram 1. Set p0922 = 1 (standard telegram 1, two PZD), save the parameters to the drive EEPROM (p0971 = 1), and acknowledge with the "Copy RAM to ROM" button in StartDrive. This resets the BICO list length to a known good state before the free telegram is re-installed.
  5. Re-import the project BICO data. Reconnect StartDrive, open the BICO editor, right-click → Disconnect all. Reconnect the application's BICO sources one by one in the order: control word, status word, setpoint chain, ramp-function generator, then outputs. Commit with "Download to device (RAM)" only - not "Download to ROM".
  6. Restore the free telegram. Set p0922 = 999, re-populate p2051[0..n] and p2061[0..n]. Click the StartDrive "Reload telegram" button and verify the new telegram appears in the device view.
  7. Save permanently. In StartDrive, choose Drive → Save data to memory card (ROM). Confirm with the parameter p0971 = 1 in the parameter table; the drive acknowledges with F-A0187 "Save All Parameter to ROM" for approximately 3 seconds.
  8. Power-cycle the Control Unit. Pull the 24 V supply for at least 30 s, then re-energise. After power-up the LED must show Ready, not Commissioning.
  9. Download again. Run StartDrive "Download to device" once more. The SubIndex alarm must not reappear.

Alternative Recovery: Manual Parameter Reset

If the drive refuses to leave the commissioning state because the BICO list is permanently corrupted in RAM, perform a factory reset of the application class and re-bring the drive up cleanly:

  1. Set p0009 = 30 (factory reset - commissioning parameter filter).
  2. Set p0976 = 1 (start the factory reset of all parameters).
  3. Wait for the drive to show F-A0186 ("Reset of all parameters to factory setting") with state = DONE (LED flashes).
  4. Once the drive returns to "Ready", re-launch StartDrive's quick commissioning, choose the same motor and application class (Encoderless speed control, fan), and enter the data from the original project.
  5. Before reopening the free telegram, copy RAM to ROM (p0971 = 1) and then download the project in two passes (BICO first, free telegram second).
A factory reset wipes all parameter changes including the access level (p0006), any safety parameters and the free-telegram layout. Capture these via "Upload to PG" before resetting. Re-apply Safety Integrated parameters through the Safety Acceptance Test, which is mandatory after a parameter reset. The official procedure is documented in the SINAMICS G120 Safety Integrated Function Manual.

Verification

After completing the resolution procedure, confirm the following on the running system:

Check Where to read Expected value
No SubIndex alarm StartDrive alarm window Empty / "All OK"
BICO source list rebuilt p9462[0..30] All non-zero entries match the StartDrive offline view
Free telegram active r0922 and PROFINET device diagnostics 999
Process data updated Trace with Telegram / PZD trace in StartDrive STW1 toggles, NIST reflects the setpoint
Drive state r0002 4 ("Ready")
Parameter filter p0009, p0010 0 each
Parameter save p0971 last executed value Logged with timestamp in r31211
Firmware versions r0964[4..7] CU firmware matches the StartDrive offline project

The trace facility is the most useful verification tool: open StartDrive → Trace and add p9462[0], p9462[22], p0010, p0922 and r0002. Capture a 30-second window. If p0010 momentarily returns to a non-zero value during the download, the SubIndex error will repeat.

Firmware Compatibility Notes

The mismatch between StartDrive showing V4.7.13 and the physical drive showing V4.7 SP13 SP2 is one of the most common reasons for a rotating SubIndex error on a CU240E-2 PN. Use the following matrix to choose the right StartDrive version:

Drive firmware Required TIA Portal + StartDrive version HSP file
V4.7 SP13 (base) TIA Portal V16 Update 3 + StartDrive V16 Update 3 HSP0311 (G120 V4.7 SP13)
V4.7 SP13 SP1 TIA Portal V16 Update 4 + StartDrive V16 Update 4 HSP0311 SP1
V4.7 SP13 SP2 TIA Portal V16 Update 5 or V17 + StartDrive matching HSP0311 SP2
V4.7 SP14+ TIA Portal V17 Update 4 or newer HSP0313 / HSP0314

Loading HSP0311 SP2 into TIA Portal V16 Update 5 brings the project in sync with the drive. The Support Package is also available on the Siemens Industry Online Support portal. For long-term stability, upgrade the Control Unit firmware with the official SINAMICS firmware package via the Web server or the StartDrive "Update firmware" wizard. Do not downgrade a CU240E-2 PN from V4.7 SP13 SP2 to V4.7 base - the Safety kernel and the BICO sub-index tables are not backward-compatible.

Common Edge Cases

Edge case 1 - drive with Safety Integrated telegram

If the CU240E-2 PN is commissioned with PROFIsafe, an additional BICO layer is activated (p9500, p9610, p9620) and p9462[] is expanded. After a Safety acceptance test the drive must be re-initialised with p9761 → 0 and the parameters committed with the Safety password (p9762).

Edge case 2 - second Control Unit from a different project

If the CU was formerly used in a different machine, the StartDrive data stored in non-volatile memory still holds the previous BICO layout. Clear the project with "Reset drive to factory settings" before commissioning.

Edge case 3 - encoderless fan load with pump curve

Pump and fan applications (G120 "P" application class) add p1220, p1221 and p1226 to the BICO chain. They share indices with the regular ramp-function generator. After the first download, confirm p9462[22] shows the expected control-word bit (typically bit 0 of STW1).

Edge case 4 - StartDrive multi-user / TIA-multi-user project

In multi-user TIA Portal projects the StartDrive data may be stale relative to the local edit. Right-click the drive in the project tree → "Reload from project" before the download; otherwise the download sends an empty BICO list and the firmware creates empty sub-indices that fail validation on the next pass.

Related Fault Codes and Alarm Codes

Alarm code Text in drive display Meaning in this context
F-A0187 Save all parameters to ROM Normal - copy RAM to ROM completed
F-A0186 Reset of all parameters to factory setting Factory reset completed
F-A0185 Reset of parameters to factory setting on CU Reset requested - watch for the state transition
A01841 PROFIdrive: parameter not supported SubIndex invalid (generic PROFIdrive reply)
F08501 PN: cyclic connection loss Download interrupted - retry
A08502 PN: sign-of-life counter fault Watchdog, no impact on SubIndex
F08505 PN: parameter error in telegram Free telegram mismatch (refer to p0922)
F30001 Power unit overcurrent Wait until the power unit has cooled, then retry download

Codes A01841 and F08505 are the two most useful early indicators - they appear immediately before the rotating SubIndex errors described in this article. If they are missing in the alarm history but the SubIndex error persists, suspect a corrupted parameter file on the offline project rather than the drive.

FAQ

Why does the failed parameter number keep changing between downloads?

The StartDrive download engine walks the indexed parameters one element at a time. After every Control Unit reset the firmware rebuilds the internal sub-index tables, so the next download starts from the first index it cannot validate, which may differ from the previous attempt. The underlying cause - usually the operating state - is the same on each attempt.

Can I simply increase p9462 length and force the download to succeed?

No. p9462 is regenerated automatically by the firmware based on the current BICO wiring. Manipulating its length only hides the symptom while keeping the drive in a fault-prone commissioning state. Fix the state and the warning disappears permanently.

Is a free telegram required for an encoderless fan application?

No. Standard telegram 1 (NSOLL / NIST) plus the ramp-function generator trace is sufficient for encoderless speed control of a fan. Free telegrams are needed only when additional process data is required, such as load current, torque, or a digital I/O mirror.

What StartDrive version pairs with V4.7 SP13 SP2?

TIA Portal V16 Update 5 (or later) with StartDrive V16 Update 5 (or later) and HSP0311 SP2 installed. Newer versions of TIA Portal (V17, V18) also ship the matching Support Package but require a project upgrade.

Does the rotating SubIndex fault endanger the motor or the drive?

No. The drive rejects the parameter write while in commissioning, so the motor never receives an invalid setpoint. The drive returns to the previous state because the write is discarded. To stay on the safe side, however, never disable the on-site run command during a StartDrive download.