Resolving S_RCV Error 1E0E 1E10 on ET200S 1SI RS232 with S7-1500

David Krause13 min read
Serial CommunicationSiemensTroubleshooting
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Resolving S_RCV Error 1E0E and 1E10 on ET200S 1SI RS232 with S7-1500

When commissioning an ET 200S distributed I/O station with the 1SI serial interface module (6ES7 138-4DF01-0AB0) on a SIMATIC S7-1500 controller, engineers frequently encounter persistent STATUS outputs of 16#1E0E and 16#1E10 on the legacy S_RCV instruction. These status words indicate that the receive block cannot bind to the serial port. The root cause is almost always a misconfigured LADDR input—the parameter is being wired with the module's I/O start address instead of the Hardware Identifier (HWID) that TIA Portal assigns to the slot. This article walks through the diagnosis, the correct configuration, the supporting RS232 interface specifications, and the verification procedure required to bring the link up.

Field-proven caveat: The same hardware works under STEP 7 V5.x for S7-300/400 with the start address in LADDR. The S7-1500 instruction set, including the long-form S_RCV / S_SEND FBs, expects a symbolic or numeric Hardware Identifier. Mixing the two address spaces is the most common reason the 1SI module is "configured, online, and still faulted."

1. Problem Description

The reported fault occurs in the following hardware topology:

  • Controller: SIMATIC S7-1511-1 PN (6ES7 511-1BK02-0AB0 or later firmware release) on PROFINET.
  • Head-end: IM 151-3 PN (6ES7 151-3AA23-0AB0) terminating the ET 200S rack on PROFINET.
  • Serial module: 1SI 6ES7 138-4DF01-0AB0 inserted in the ET 200S backplane, configured for RS232 transmission (not RS422/485).
  • End device: A measurement gauge exposing an ASCII/RS232 port.
  • Programming environment: STEP 7 Professional V14 (or higher) in TIA Portal.

The S_RCV instruction is called cyclically in OB1. The output STATUS returns hexadecimal 16#1E0E on every call, alternating with 16#1E10 depending on the runtime state. The ERROR and DONE bits never transition to TRUE, so no data is delivered to the receive DB. The module itself is reachable in the device view, is reporting no diagnostics in the IM 151-3 PN diagnostic buffer, and the physical LEDs on the 1SI module indicate normal operation (no SF/BF LED lit).

2. Error Code Reference

Both error codes are produced by the legacy point-to-point instruction set when the runtime cannot bind the call to a valid point-to-point port.

STATUS (hex) STATUS (dec) Typical Meaning Common Triggers
16#1E0E 7694 Internal binding error — the LADDR input does not resolve to a known point-to-point port on the configured module. LADDR contains the diagnostic address, the I/Q start address, or an HWID from a different slot.
16#1E10 7696 Port resource not available — the binding to the CP/CM/1SI exists but the port is locked, busy, or not yet initialized. Port is assigned to a different FB instance, the module is in a different PROFINET slot than the configuration shows, or the configuration is being downloaded while the call is active.

Both codes point to the same physical layer of the problem: the LADDR input is not pointing at the Hardware Identifier of the 1SI's serial interface. Once the correct identifier is wired into the block, both status codes clear and the receive buffer starts populating.

3. Root Cause — LADDR Mismatch

The S_SEND and S_RCV instructions predate the S7-1500. They were originally written for S7-300 CP 340/341 and S7-400 CP 440/441 point-to-point modules, and were carried forward as long-form FBs in the S7-1500 for migration scenarios. In the original S7-300/400 environment the LADDR input was filled with the logical base address of the CP — the same address that appeared in the hardware catalog under "I/O addresses."

On the S7-1500 platform the same FBs were generalized to support not only the new CM PtP modules (such as CM PtP RS232 BA (6ES7540-1AD01-0AA0) and CM PtP RS232 HF (6ES7541-1AD01-0AB0)) but also distributed point-to-point modules such as the ET 200S 1SI and the ET 200SP CM PtP. To unify the address model, the LADDR input on the S7-1500 was redefined to accept the Hardware Identifier — a 16-bit (or 32-bit on newer FBs) symbolic handle assigned by TIA Portal to each submodule during device configuration.

Engineers migrating S7-300 code or copying logic from a sample project frequently retain the I/Q start address at the LADDR pin. The block then performs an internal lookup that fails, returning 16#1E0E. The 16#1E10 returns occur on subsequent cycles because the runtime has now created a partial binding object that conflicts with itself.

4. Locating the Hardware Identifier in TIA Portal

There are three reliable methods to retrieve the Hardware Identifier for the 1SI module's serial interface.

4.1 Method A — Module Properties Dialog

  1. Open the ET 200S station in the Device view of TIA Portal.
  2. Click the 1SI module (6ES7 138-4DF01-0AB0) in the rack.
  3. Open the Properties inspector (lower pane, "General" tab).
  4. Navigate to System constants or to Hardware identifier.
  5. Note the numeric value shown (for example 266). The same value is also published as a constant under the default name ~1SI_Slot1_Interface in the PLC tag table.

4.2 Method B — Default Tag Table

  1. Expand PLC_1 > PLC tags > Default tag table.
  2. Switch the view filter to Show all tags or filter on the constant prefix ~.
  3. Locate the constant whose name references the 1SI module (e.g. ~1SI_1, ~1SI_1_Interface_1, or the renamed HWID_1SI).
  4. The data type is HW_IO or HW_INTERFACE; the value is the numeric HWID.

4.3 Method C — System Constants View

  1. From the project tree, right-click the S7-1500 CPU and select Information > System constants.
  2. Filter the list by the 1SI module's name or by interface type Point-to-Point.
  3. Copy the value directly into the LADDR input of the S_RCV / S_SEND call.
On a multi-slot ET 200S station, the Hardware Identifier for the 1SI is unique to the slot, not to the station. Do not copy HWIDs across slot positions or between projects without verifying the slot number in the device view.

5. Step-by-Step Resolution Procedure

Prerequisites

  • TIA Portal V14 or higher installed.
  • The S7-1500 program containing the 1SI module and the S_RCV / S_SEND FBs.
  • Online connection to the CPU (PROFINET or PROFIBUS).
  • Read/write access to the project.

Procedure

  1. Compile the project before going online. This populates the system constants and forces TIA Portal to assign a stable Hardware Identifier to every slot in the ET 200S station.
  2. Open the FB / OB containing the S_RCV call. Double-click the LADDR input of the block. The I/O field shows whether the parameter is a constant, a tag, or unconnected.
  3. Replace the start address with the Hardware Identifier discovered in Section 4. Use a symbolic reference (e.g. "1SI_Slot1_Interface") whenever possible so that the address follows the slot if you reorder the rack later.
  4. Save and download the hardware configuration and the program block to the CPU. Use "Download to device > Hardware and software" so the new system constants are pushed to the PLC.
  5. Reset the CPU (cold restart) to clear any partial binding objects from the previous configuration. The reset is necessary because the runtime keeps the old LADDR binding in its session state until a restart.
  6. Monitor the call online. The STATUS output should now return 16#0000 (or the documented "no data yet" code) and NDR should pulse TRUE each time the 1SI module receives a complete frame.

6. Verification Procedure

After the LADDR correction has been downloaded, validate the link end-to-end with the following checks.

6.1 Online STATUS Inspection

  1. Open the OB1 watch table with the S_RCV instance open.
  2. Confirm STATUS = 16#0000 when no data is in flight.
  3. Trigger a transmission from the gauge and confirm NDR pulses for one cycle, with the receive DB populated and a non-zero LEN output.

6.2 Module Diagnostic Buffer

  1. In the project tree, right-click the IM 151-3 PN and select Online & diagnostics > Diagnostic buffer.
  2. Look for "Port initialized" or "Protocol ASCII active" events. Any entry referencing "Port not configured" or "binding error" means the runtime is still resolving to a stale identifier.

6.3 LED Pattern

LED Color State Interpretation
SF (group) Red Off Module diagnostic clear.
BF (bus) Red Off PROFINET link to IM is healthy.
TX / RX Green Flicker on send/receive Port is operational.

6.4 Loopback Test

  1. Disconnect the gauge and insert a loopback plug (TX ↔ RX) on the 1SI port.
  2. Send a known ASCII string via S_SEND and read it back with S_RCV.
  3. If the loopback works but the gauge does not, the binding is correct and the residual problem is in the physical layer (cable, shielding, gauge-side protocol).

7. RS232 Interface Electrical Specifications

The 1SI 6ES7 138-4DF01-0AB0 implements a voltage-mode RS232 interface. The same electrical model applies to the modern S7-1500 CM PtP RS232 BA and HF modules (6ES7540-1AD01-0AA0 / 6ES7541-1AD01-0AB0) and to the ET 200SP CM PtP, so the same precautions apply across the platform.

Parameter Value Notes
Standard EIA-RS232C / V.24 / V.28 Two-line voltage interface.
Logic level (mark / space) −3 V to −15 V / +3 V to +15 V Between data lines and signal ground.
Maximum cable length 15 m (typical), 30 m with low-capacitance cable RS232 is not designed for long runs.
Galvanic isolation Inputs and outputs are not isolated from each other Reference Siemens TIA Portal documentation on the RS232 interface of the communications module.
Lines used in RS232 mode TXD, RXD, RTS, CTS, DSR, DCD, DTR, RI (subset depends on protocol) Data on two lines; handshakes optional.
Supported baud rates (1SI) 300, 600, 1200, 2400, 4800, 9600, 19200, 38400 bit/s (firmware-dependent) Set in the device configuration under "Protocol > Serial interface parameters."
Isolation caveat: Because the RS232 inputs and outputs share a common reference, the connected gauge must also reference the same ground potential. If the gauge is floating or powered from a different ground, fit an isolated RS232 repeater or switch to RS422/485 with galvanic isolation (the 1SI supports both via firmware setting; the CM PtP HF also supports RS422/485).

8. Hardware Configuration in TIA Portal

Open the device view of the ET 200S station and click the 1SI module. The configuration tabs that matter for the RS232 link are listed below.

Tab Parameter Typical Setting Effect on Application
Port configuration Interface type RS232 Selects the physical driver.
Port configuration Baud rate 9600 / 19200 Must match the gauge.
Port configuration Parity None / Even / Odd Match the gauge. ASCII gauges commonly use "None."
Port configuration Data bits / Stop bits 8 / 1 Match the gauge.
Protocol Frame end detection On receive line idle, fixed length, or end-of-text character (e.g. CR/LF) Defines when the 1SI closes a frame and pulses NDR.
Protocol XON/XOFF Off unless the gauge uses it Software flow control.
Protocol RTS/CTS On if hardware handshaking is required Hardware flow control.
Diagnostics Diagnostic interrupt Enabled Recommended. Routes status to OB82.

Save the configuration and download it. The Hardware Identifier is finalized at this point and is stable across compiles unless the slot order changes.

9. S_RCV / S_SEND Call Pattern in SCL or LAD

The 1SI module is driven by the long-form point-to-point FBs. The following SCL snippet shows the recommended call pattern.


// S_RCV — receive data from the gauge
"S_RCV_DB"(REQ   := bTrigger,
           CONT  := TRUE,
           LADDR := "1SI_Slot1_Interface",  // Hardware Identifier, NOT start address
           BUF   := P#DB_Rx.DBX0.0 BYTES 200);

if "S_RCV_DB".NDR then
    iRxLen := "S_RCV_DB".LEN;
    bNewFrame := TRUE;
end_if;

if "S_RCV_DB".ERROR then
    wStatus := "S_RCV_DB".STATUS;   // 16#1E0E / 16#1E10 on misconfiguration
end_if;

// S_SEND — transmit command to the gauge
"S_SEND_DB"(REQ   := bSend,
            CONT  := TRUE,
            LADDR := "1SI_Slot1_Interface",
            BUF   := P#DB_Tx.DBX0.0 BYTES 50,
            LEN   := iTxLen);

Notice the symbolic reference at LADDR. This binds the call to whatever Hardware Identifier TIA Portal assigned to the 1SI module, and it survives recompiles and slot reorders.

10. Alternative — Send_P2P / Receive_P2P for S7-1500

For new programs, Siemens recommends the native Send_P2P / Receive_P2P / Receive_Reset_P2P instructions, which are part of the SIMATIC S7-1500 base library. These instructions use the same Hardware Identifier model and expose richer diagnostics, including per-port error codes, buffer overrun counters, and parity-error statistics. The legacy S_SEND / S_RCV remain in the catalog specifically to support the 1SI migration scenario described in this article.

The Siemens TIA Portal help "RS232 mode (S7-1500)" lists the modules that participate in the new instruction model:

  • CM PtP RS232 BA — 6ES7540-1AD01-0AA0
  • CM PtP RS232 HF — 6ES7541-1AD01-0AB0
  • CM PtP (ET 200SP) — 6ES7137-6AA00-0BA0 family

Migration to the ET 200SP platform is recommended where the application is being modernized; the 1SI itself remains in production for installed base support but is no longer the recommended choice for new S7-1500 installations.

11. Troubleshooting Matrix

Symptom Most Likely Cause Action
STATUS = 16#1E0E on every S_RCV call LADDR contains a start address, not a Hardware Identifier Replace LADDR with the symbolic HWID from system constants
STATUS = 16#1E10 after correcting LADDR Stale binding from a previous compile Cold restart the CPU; re-download the configuration
STATUS = 16#1E0E and project will not compile LADDR is a non-existent constant name Recompile project to regenerate system constants, then re-link
STATUS = 16#0000 but no data arrives Frame end detection is wrong (gauge does not send CR/LF) Set "end of frame on character" or "fixed length" in protocol tab
Intermittent garbled data Baud / parity mismatch between gauge and 1SI Loopback test, then re-verify gauge settings
SF LED lit, diagnostic buffer: "Port not configured" Module configuration was downloaded without a project compile Compile project, then "Download to device > Hardware and software"
Data received but with extra bytes at start of buffer Gauge emits a preamble not configured as part of the frame end detection Use frame end on a specific delimiter (e.g. LF) and trim the buffer in user code
Receive DB extends beyond DB boundary DB is too small for the configured buffer Increase the DB size or shrink the buffer reference in S_RCV

12. Sample Program Reference

Siemens publishes a sample program for the 1SI ASCII protocol on the ET 200S — file zXX21_10_1SI_ASCII.zip for STEP 7 (TIA Portal). The archive contains:

  • A reference project for STEP 7 V13 (and an updated build for V14 SP1).
  • Pre-wired S_SEND / S_RCV calls with the LADDR set to the symbolic Hardware Identifier.
  • An ASCII test pattern generator and a watch table for verification.

If the project must be opened on a different TIA Portal version than the one used to create it, use File > Open > Migrate project rather than re-saving. The migration path preserves the binding between the symbolic constant and the HWID.

13. Frequently Asked Questions

Why does my S_RCV keep returning 16#1E0E on the S7-1500 even though the 1SI module is online?

The LADDR input expects the Hardware Identifier, not the I/Q start address. Open the device view, click the 1SI module, copy the symbolic constant (for example ~1SI_Slot1_Interface) into LADDR, recompile, and download. STATUS should clear to 16#0000 after a CPU cold restart.

Is the 1SI 6ES7 138-4DF01-0AB0 still supported on S7-1500 with TIA Portal V17 and V18?

Yes — the 1SI module is in the TIA Portal hardware catalog through V20 and is supported on the S7-1500 via PROFINET on the IM 151-3 PN head-end (6ES7 151-3AA23-0AB0 or later). For new installations, Siemens recommends the ET 200SP CM PtP (6ES7137-6AA00-0BA0) or the S7-1500 CM PtP RS232 HF (6ES7541-1AD01-0AB0).

Can I use Send_P2P / Receive_P2P with the ET 200S 1SI module?

Send_P2P and Receive_P2P are designed for the S7-1500 CM PtP modules and the ET 200SP CM PtP. The ET 200S 1SI is supported through the legacy S_SEND / S_RCV FBs. Use the modern instruction set only when migrating to a CM PtP module.

What is the maximum RS232 cable length for the 1SI?

EIA-RS232C specifies a maximum of approximately 15 m at 19.2 kbit/s. With low-capacitance shielded cable the practical limit extends to about 30 m, but for any run longer than 10 m in a noisy industrial cabinet, an isolated RS232 repeater or a switch to RS422/485 is recommended.

How do I know the gauge and the 1SI are using the same ground reference?

The RS232 interface on Siemens point-to-point modules is not isolated between the data lines and the backplane. Measure the voltage between the shield ground of the gauge cable and the PE terminal of the IM 151-3 PN. A potential difference above ~1 V indicates that the gauge is on a different ground reference and you must install an isolated repeater to avoid damage.

Back to blog