Engineer field reference for supervising Siemens Comfort Panel alarm classes and triggering dedicated PLC bits when unacknowledged alarms exist. Covers TIA Portal V20 ProDiag integration, VBScript polling workarounds, and PLC-side aggregation when the WinCC Professional Runtime alarm object is not available on the HMI.
Overview
WinCC Professional Runtime exposes a complete alarm object model that lets scripts query class-level state directly ("any unacknowledged alarm in class X"). Comfort Panels run WinCC Comfort or WinCC Advanced Runtime, which implements a deliberately smaller scripting surface. The sample project described in the Siemens Support post 135130 for WinCC Professional V13 SP1 drives a horn and warning lamp by evaluating alarm-class state inside a VBScript that calls the full alarm object. That script depends on alarm object methods not present in Comfort Panel Runtime and cannot be ported verbatim.
This reference documents three engineering approaches that do work on a Comfort Panel, ordered by reliability and license cost:
- Tag-based acknowledgment state per alarm, aggregated in the PLC by class. Works on every Comfort Panel firmware from V11 onward and on every WinCC Comfort/Advanced license.
- ProDiag-based visualization with TIA Portal V20, which adds code-level monitoring alarms and class-filtered alarm views on Panels, Comfort Panels, and RT Advanced/Professional.
- Scheduled VBScript polling of the HMI alarm buffer where the Comfort Panel Runtime license permits script execution against the alarm subsystem.
All three produce a single boolean tag per alarm class on the PLC side. The PLC uses that boolean to drive a horn, a beacon, an SMS sender, or an alarm forwarding function block.
Prerequisites
| Component | Requirement | Notes |
|---|---|---|
| Engineering software | TIA Portal V20 (or V18/V19 with corresponding HSP) | ProDiag HMI capability requires V20 features per the TIA Portal V20 ProDiag alarm view documentation |
| Comfort Panel firmware | ≥ V17.0 for full ProDiag HMI support | Older panels run tag-based Method 1 without changes |
| PLC | S7-1500, S7-1200, S7-300, or S7-400 | ProDiag monitoring is fully supported on S7-1500; S7-1200 supports a subset |
| ProDiag license | Required on the PLC for ProDiag alarms | Method 2 only |
| WinCC Comfort/Advanced license | Required for engineering the HMI project | Method 1 works on every Comfort license |
| User rights for VBScript | "Scripts" must be enabled in HMI Runtime security settings | Method 3 only |
| Number of alarm classes | Up to 16 in WinCC Comfort; up to 32 in WinCC Advanced | Most projects use 3 (Critical, Warning, Info) |
| Number of alarms per class | Up to 32 in one HMI word; 16 recommended for clarity | Split across multiple HMI tags for larger classes |
| PROFINET or MPI connection | Required between PLC and panel for tag updates | Update time typically 100 ms |
The Comfort Panel Runtime Limitation
WinCC Professional Runtime and WinCC Comfort Runtime share the alarm configuration screens in TIA Portal but expose different runtime APIs. The differences that matter for this problem are:
- Alarm object scripting surface: The full alarm object model with class-state queries, event-driven scripts, and centralized buffer access is fully available on PC Runtime. Comfort Panels allow VBScript but the function set against the alarm subsystem is restricted; calling unsupported methods on the alarm object returns a Runtime error rather than a defined value. The Comfort Panel script environment does not expose a method that returns "any unacknowledged alarm in class X" as a single call.
- HMI-side aggregation: A Comfort Panel cannot natively publish a per-class boolean to the PLC. The acknowledgment state of each individual alarm is a per-alarm Runtime value, not an aggregate. Any class-level boolean has to be derived either on the PLC side (by feeding it per-alarm state) or on the HMI side via a scheduled script that emulates the missing query.
- Event-driven alarm scripts: The WinCC Professional sample referenced above uses an event-driven alarm script that fires on state change. Comfort Panels support scheduled scripts but the event-driven alarm hookup is more limited; in practice, polling is the only reliable path on a Comfort Panel.
- Alarm buffer size: the default Comfort Panel alarm buffer is typically 512 entries. A project with thousands of alarms must size the buffer explicitly under Runtime Settings > Alarms.
The Siemens support thread post 132006 covers alarm class configuration and confirms that the API-level class-state query is not exposed on Comfort Panels.
Result: a Comfort Panel cannot give you a one-shot answer to "any unacknowledged in class X". The aggregate has to be computed either on the PLC side (by feeding it per-alarm state) or on the HMI side via a workaround script.
Method Comparison
| Method | PLC Required | License Cost | Engineering Effort | Latency | Best For |
|---|---|---|---|---|---|
| 1 - Tag-based aggregation | Any S7 | None (uses base alarm licensing) | Low to medium (one HMI tag per alarm) | 1 PLC cycle + HMI update | All projects; baseline approach |
| 2 - ProDiag visualization | S7-1500 recommended | ProDiag PLC license + V20 panel firmware | Medium (block supervision setup) | 1 PLC cycle | Code-level supervision (motion, sequence) |
| 3 - VBScript polling | Any S7 | Scripts option on panel | High (script maintenance) | Scheduler period (250-1000 ms) | HMI-side-only aggregation (rare) |
Engineers should default to Method 1. Methods 2 and 3 are supplements, not replacements. ProDiag in particular is a code-monitoring framework, not a class-aggregation tool; it does not answer "any unacknowledged in class X" for the project's existing discrete/analog alarms.
Method 1: Tag-Based Acknowledgment State
The most reliable approach. Each alarm is configured to write its acknowledgment state to a dedicated bit in an HMI tag. The PLC OR-aggregates those bits per alarm class and exposes a single boolean per class to the rest of the program.
HMI Alarm Configuration
- In the TIA Portal project tree, open HMI alarms > Discrete alarms (or analog alarms, depending on the application).
- Select the first alarm, open Properties > Settings, and assign an acknowledgment tag in the trigger section. WinCC Comfort supports a 1-bit acknowledgment tag per alarm.
- Set the tag's update mode to "On change" so the PLC sees both the rising edge (alarm raised, not yet acknowledged) and the falling edge (alarm acknowledged or cleared).
- Assign each alarm to one of the three alarm classes you created earlier.
- Repeat for every alarm in the project, allocating a unique bit offset in a structured HMI tag (a
WordorDWordmapped to a PLC data block). - Compile and download the HMI project. The HMI now writes the acknowledgment state of every alarm to its assigned bit.
Bit Layout Convention
Use a single HMI tag of type Word or DWord per alarm class so the PLC can OR the whole word in a single instruction. The example below assumes 16 alarms per class maximum; for up to 32 alarms use a DWord.
| Class | HMI Tag | PLC DB Address | Aggregation Tag |
|---|---|---|---|
| Class_1 (Critical) |
HMI_Alarms_Class1 (Word) |
%DB20.DBW0 | PLC_Class1_Unack |
| Class_2 (Warning) |
HMI_Alarms_Class2 (Word) |
%DB20.DBW2 | PLC_Class2_Unack |
| Class_3 (Info) |
HMI_Alarms_Class3 (Word) |
%DB20.DBW4 | PLC_Class3_Unack |
Within each word, allocate bit 0 to alarm 1, bit 1 to alarm 2, and so on. Document the mapping in a project spreadsheet so future alarm additions do not collide. Reserve bit 15 of each word for a "synthetic" alarm raised from the PLC side (e.g. a heart-beat that always forces the aggregate up while the PLC is running, used for diagnostics).
Why This Works
WinCC Comfort writes the acknowledgment tag exactly when the alarm state transitions. If the bit is set in the alarm word, it indicates "raised and not yet acknowledged". The PLC OR-aggregates the word and produces a single class has unacknowledged boolean. The acknowledgment tag in WinCC Comfort follows the convention: 1 = unacknowledged active, 0 = acknowledged or inactive. Verify this against your project's alarm settings; the convention matches the standard WinCC behavior used in the WinCC Professional V13 SP1 reference sample.
Method 2: ProDiag-Based Visualization (TIA Portal V20)
ProDiag is a TIA Portal capability that provides detailed monitoring of PLC program execution. It is licensed on the PLC side and visualized on the HMI. With TIA Portal V20, ProDiag alarms are displayable on Panels, Comfort Panels, and RT Advanced/Professional, as documented in the ProDiag alarm view configuration guide.
Enabling ProDiag
- In the PLC device configuration, open Properties > Runtime > ProDiag and enable the ProDiag functions for the CPU.
- Ensure the panel firmware supports the ProDiag HMI runtime extension. TIA Portal V20 documentation explicitly lists Comfort Panels as supported targets.
- Place ProDiag-typed blocks in the PLC program (typically a GRAPH sequencer or HLFB block). The PLC automatically generates ProDiag alarms when block conditions are violated.
- Assign each ProDiag alarm to one of the three alarm classes created in the HMI project.
Filtering the HMI Alarm View by Class
- Open the screen that contains the alarm view, select the view, and switch to Properties > General.
- In the filter section, select the alarm classes that the view should display. The configuration step is shown in the TIA Portal V20 ProDiag alarm view documentation.
- Configure a separate alarm view per class if the operator needs to see them in isolation (typical for a dedicated "Critical Alarms" tab).
- Use the Properties > Layout dialog to give each class view a distinct background color so operators can identify the class at a glance.
Trade-offs
ProDiag requires an S7-1500 (or limited S7-1200) CPU with a ProDiag license, plus a Comfort Panel that supports the V20 ProDiag HMI extension. On older panels or older TIA Portal versions, the ProDiag HMI integration is not available and Method 1 must be used for the entire project. For mixed fleets (some panels V20, some older), accept that ProDiag alarms will only display on the newer panels and let Method 1 drive the PLC.
Method 3: Scheduled VBScript Polling
If the project does not have a PLC powerful enough to OR dozens of bits per cycle, or if the engineer wants a single HMI-side computed tag, use a scheduled VBScript to evaluate the alarm buffer and write a class-level tag.
Script Skeleton (Conceptual)
The exact VBScript API for filtering alarms by class on a Comfort Panel is not exhaustively documented in the public Siemens function manual; the engineer should test the call on the target panel firmware. A representative polling skeleton is shown below; treat the buffer-iteration primitives as a starting point and verify against the panel's Runtime help.
Sub PollAlarmClasses()
Dim i, sClass
' Reset aggregates
SmartTags("PLC_Class1_Unack") = False
SmartTags("PLC_Class2_Unack") = False
SmartTags("PLC_Class3_Unack") = False
' Iterate visible alarm entries
For i = 0 To AlarmBuffer.Count - 1
sClass = AlarmBuffer.Item(i).Class
If AlarmBuffer.Item(i).State = hmiAlarmStateUnacknowledged Then
Select Case sClass
Case "Class_1": SmartTags("PLC_Class1_Unack") = True
Case "Class_2": SmartTags("PLC_Class2_Unack") = True
Case "Class_3": SmartTags("PLC_Class3_Unack") = True
End Select
End If
Next
End Sub
Scheduling the Script
Configure a Scheduler > Trigger task in the HMI project that runs the script every 500 ms to 1000 ms. The HMI tag PLC_ClassX_Unack is a normal HMI tag connected to a PLC tag, so any change is pushed to the PLC over the fieldbus on the next acquisition cycle. Avoid periods below 250 ms; the Comfort Panel's script scheduler can saturate and starve other HMI tasks.
Edge Cases and Caveats
- Comfort Panel reboot: the script stops running until the panel completes startup. Method 1 has the same limitation but the PLC tags retain their last value.
- Alarm buffer overflow: if more than the buffer capacity of unacknowledged alarms exist, the script may miss older entries. Configure the alarm buffer size in the HMI Runtime settings to match the worst-case alarm count.
- Class identifier vs display name: WinCC Comfort uses internal class identifiers, not the human-readable name. The "Class_1" string above is illustrative; check the project's alarm class identifier to determine the exact value to compare against.
- Script Runtime error: if the panel's Runtime does not expose the alarm buffer API, the script raises a Runtime error visible in the HMI diagnostic viewer. In that case, fall back to Method 1; tag-based aggregation does not use the alarm scripting object.
-
Concurrent alarms in the same class: a single pass through the alarm buffer correctly identifies the class-aggregate because the script sets the output tag to
Trueif any unacknowledged alarm of that class exists. The reset at the start of each pass prevents the output from being sticky across cycles.
PLC Program Sample (S7-1500 / S7-1200)
The PLC side is identical for all three methods. The aggregated class-level booleans are written by the HMI; the PLC publishes them and adds the standard handling (edge detection, latching, masking by operator enable).
Data Block Layout (SCL)
DATA_BLOCK "DB_AlarmClass"
{ S7_Optimized_Access := 'TRUE' }
VERSION : 0.1
NON_RETAIN
STRUCT
Class1_Unack : Bool; // Any unacknowledged alarm in class 1
Class2_Unack : Bool;
Class3_Unack : Bool;
Class1_Latch : Bool; // Latched until operator reset
Class2_Latch : Bool;
Class3_Latch : Bool;
Class1_Edge_Memory : Bool; // Edge detection helper
Class2_Edge_Memory : Bool;
Class3_Edge_Memory : Bool;
Horn_Out : Bool; // Combined horn trigger
END_STRUCT;
END_DATA_BLOCK
Aggregation and Latching Logic (SCL)
// Method 1: PLC-side OR aggregation of acknowledgment tag words.
// "HMI_Alarms_ClassX" is a Word HMI tag; bit n = alarm n of class X.
"DB_AlarmClass".Class1_Unack := "HMI_Alarms_Class1" <> 16#0000;
"DB_AlarmClass".Class2_Unack := "HMI_Alarms_Class2" <> 16#0000;
"DB_AlarmClass".Class3_Unack := "HMI_Alarms_Class3" <> 16#0000;
// Latch the unacknowledged state so a momentary flicker does not
// release a beacon. Latch resets when the operator acknowledges
// ALL alarms of that class (i.e. the aggregate returns to FALSE).
IF "DB_AlarmClass".Class1_Unack THEN
"DB_AlarmClass".Class1_Latch := TRUE;
END_IF;
IF NOT "DB_AlarmClass".Class1_Unack AND "HMI_Ack_Class1" THEN
"DB_AlarmClass".Class1_Latch := FALSE;
END_IF;
// Repeat the block for Class2 and Class3.
// Horn trigger: rising edge of any class latch.
"DB_AlarmClass".Horn_Out := "DB_AlarmClass".Class1_Latch
OR "DB_AlarmClass".Class2_Latch
OR "DB_AlarmClass".Class3_Latch;
For S7-300/400 use STL or LAD with the equivalent OW and <>0 instructions. The HMI word is moved into a temporary, OR-aggregated with the running total, and compared to zero. The latch logic uses standard set/reset coil pairs in LAD.
Alarm Class Color Configuration
Operators differentiate alarm classes at a glance. Configure the class colors in the HMI project so the unacknowledged state is visually distinct. Per Siemens Support forum post 1270551, WinCC Comfort exposes the alarm class colors under HMI alarms > Alarm classes. The recommended color convention is:
| Class | Background (incoming) | Background (acknowledged) | Typical use |
|---|---|---|---|
| Class_1 (Critical) | Red (RGB 255,0,0) | Dark red (RGB 128,0,0) | E-stop, safety, drive fault |
| Class_2 (Warning) | Yellow (RGB 255,255,0) | Olive (RGB 128,128,0) | Process limit, sensor fail |
| Class_3 (Info) | Blue (RGB 0,176,240) | Gray (RGB 128,128,128) | Operator message, status |
Verification and Commissioning
- Compile and download the HMI project to the Comfort Panel and the PLC project to the CPU.
-
Trigger a test alarm in class 1 (force the trigger tag in the PLC). Verify the
HMI_Alarms_Class1word shows the corresponding bit as1in the HMI tag table (online > monitor). -
Verify the aggregate: the
Class1_Unackboolean in the PLC should switch toTRUEwithin one cycle of the bit being set. -
Acknowledge the alarm on the HMI. The bit must fall to
0and the aggregate must fall toFALSEwithin one cycle. - Repeat for all three classes. Stress-test with simultaneous alarms in multiple classes to ensure the OR aggregation is correct.
- Test the latch: clear a momentary alarm and confirm the latch holds until the operator acknowledges (or until the configured latch reset condition).
- If using Method 3: temporarily reduce the scheduler period to 100 ms and confirm the script executes without Runtime errors in the HMI diagnostic viewer.
- Operator acceptance: have the operator confirm the alarm colors meet the site's standards before sign-off.
-
Power-cycle test: power down the Comfort Panel, bring it back up, and confirm the aggregates return to
FALSEwithin one acquisition cycle. Stale state from a previous session is a common cause of phantom horn triggers. - Network-load test: with the PLC running at peak cycle load, verify the HMI tag update does not stall. Add a diagnostic tag that counts tag updates per second and alarm if it drops below 5 Hz.
Troubleshooting Matrix
| Symptom | Likely Cause | Diagnostic Step | Fix |
|---|---|---|---|
Class aggregate never goes TRUE
|
Alarm acknowledgment tag is not assigned | Check the alarm's Settings > Acknowledgment tag in the HMI project | Assign an acknowledgment tag of type Bool; recompile and download |
Aggregate stays TRUE after acknowledge |
Tag update mode is "On change" but the PLC reads at a slower cycle than the HMI pushes | Monitor the HMI tag online and the PLC tag simultaneously | Switch the PLC to event-driven evaluation or set the HMI tag to continuous update |
| Class aggregate toggles randomly | Multiple alarms share the same bit in the HMI word | Print the alarm-tag mapping in the HMI project | Reassign each alarm a unique bit offset |
| VBScript runtime error "Object not supported" | Comfort Panel Runtime does not expose the alarm buffer API used | Open Help > Runtime help on the panel and search the function name | Fall back to Method 1; tag-based aggregation does not use the alarm scripting object |
| ProDiag alarms not visible on the panel | Panel firmware below the ProDiag HMI support level | Check Panel > Properties > Firmware version | Upgrade the panel firmware to a V20-compatible version or use Method 1 |
| ProDiag class filter shows empty alarm view | Wrong class selected in the view filter | Open the view's Properties > General and check the class filter | Re-select the target alarm class per the TIA Portal V20 ProDiag alarm view configuration |
| PLC aggregation slow (> 1 s) | PLC cycle time too long for the project | Check the PLC's online cycle time diagnostics | Use the latch output (one-shot pulse) for horn triggers; do not rely on the aggregate staying TRUE
|
| Phantom horn after power cycle | HMI tag retains its last value from previous session | Inspect the HMI tag's startup value | Set the HMI tag's startup value to 0 in the tag properties |
| Wrong class bit gets set | Alarm class assignment is misconfigured | Open the alarm's Properties > Settings and check the class dropdown | Reassign to the correct class and re-download the HMI project |
| Aggregate briefly true on every project download | HMI pushes initial tag values to PLC after download | Watch the HMI tag table during the first 5 seconds after download | Add a 1-second startup delay before the PLC evaluates the aggregate, or initialize the HMI tag to 0 on startup |
| Aggregate stuck on one class, others silent | HMI tag area pointer collision with another HMI tag | Open the HMI tag table and verify address ranges do not overlap | Move the conflicting tag to a free DBW range and recompile |
Field-proven caveats to keep in mind: the Comfort Panel loses Runtime state on power cycle, so the PLC must rely on the HMI reinitializing the acknowledgment tags to 0 at startup. If the project allows the operator to mute a single alarm without acknowledging, the acknowledgment tag may transition differently from the visible state; cross-check the alarm configuration's Acknowledgment setting ("On acknowledgment" vs "On reset"). For distributed I/O on PROFINET with sub-millisecond cycle, the HMI tag update can lag by several PLC cycles; the aggregation still works but the operator may see a one-cycle delay. If more than one Comfort Panel writes to the same acknowledgment tag (primary and mirror panel), designate a single owning panel or OR the values from both panels on the PLC side.
FAQ
Why does the WinCC Professional V13 SP1 sample not work on a Comfort Panel?
The sample uses the full WinCC Professional alarm object model, including methods that query class-level state. WinCC Comfort on a Comfort Panel implements a smaller API; the class-state query is not exposed. Use Method 1 (tag-based aggregation) for portable results across all Comfort Panels.
Can a single Comfort Panel trigger different PLC bits for different alarm classes?
Yes. Assign a unique acknowledgment tag per alarm, group the bits by class into separate HMI words, and let the PLC OR-aggregate each word into a dedicated class boolean. The recommended layout uses one HMI tag of type Word per class, mapped to a PLC data block word.
Does ProDiag replace the manual tag-based approach for alarm class aggregation?
No. ProDiag provides per-instance monitoring of PLC program execution and an HMI alarm view filtered by class, but the class-aggregate boolean is still derived from per-alarm state. ProDiag is best used alongside Method 1 for code-level monitoring (GRAPH sequence errors, HLFB interlocks), not as a replacement for the discrete/analog alarm aggregation.
How fast does the PLC see a new unacknowledged alarm on a Comfort Panel?
Typical latency is one PLC cycle plus one HMI tag-update cycle. For an S7-1500 with a 1 ms cycle and a 100 ms HMI update, expect 100 to 200 ms end-to-end. Use the latch output for horn and beacon applications where a 100 ms response is acceptable. Sub-100 ms response requires the PLC to generate the alarm itself and bypass the HMI.
What happens if the HMI tag word overflows with more than 32 alarms in one class?
Split the class across two or more HMI tags of type Word. In the PLC, OR all words for that class into a single boolean. The class-aggregate bit stays correct as long as every alarm has a unique bit position and the PLC-side OR is updated each cycle.