Resolving S7-1200 SM 1222 6ES7 222-1HH32-0XB0 No Output Voltage

David Krause16 min read
S7-1200SiemensTroubleshooting
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Problem Statement

After installing two Siemens SM 1222 digital output modules (order code 6ES7 222-1HH32-0XB0) and one SM 1223 digital input/output module (6ES7 223-1PL32-0XB0) on an S7-1214C CPU, the engineer observed that the output LEDs on the SM modules illuminated when the corresponding bits were set in the process image, yet measuring the output terminals against M produced 0 V. The CPU's own onboard outputs operated normally, and the SM 1223 inputs registered field signals correctly. Forcing a bit to DQb.0 in TIA Portal produced the same symptom: LED on, no voltage at the terminal. The fault appeared on both SM 1222 modules. After routing the 24 VDC rail of the cabinet to the module's L+ and M terminals, all 16 outputs per module switched correctly.

This article documents the diagnostic path, the underlying root cause, and the corrected wiring for the affected hardware. It also captures the current-loading rules, group structure, and common S7-1200 signal-module pitfalls that should be checked whenever a "LED on but no output" symptom is reported.

Symptom signature. Output status LED illuminates, but the output terminal remains at 0 V (transistor SM) or remains open (relay SM). The CPU is in RUN, no diagnostic interrupt is raised, and forcing a single output from TIA Portal produces the same fault. This pattern is the classic "module supply missing" failure on S7-1200 SM modules.

Affected Hardware

Slot MLFB Description Function
CPU 6ES7 214-1xxxx-0XB0 S7-1214C, DC supply variant Logic, sensor power, onboard I/O
SM 1 6ES7 222-1HH32-0XB0 SM 1222, 16 DO relay, 2 A 16 isolated relay outputs, 4 groups of 4
SM 2 6ES7 222-1HH32-0XB0 SM 1222, 16 DO relay, 2 A 16 isolated relay outputs, 4 groups of 4
SM 3 6ES7 223-1PL32-0XB0 SM 1223, 16 DI 24 V / 16 DO relay 16 × 24 V inputs + 16 × relay outputs

The MLFB suffix "32" identifies the V3 generation of the S7-1200 SM, supported on CPU firmware V3.0 and later. The CPU in the reported case was manufactured in Germany; the SM modules were manufactured in China. Manufacturing origin is irrelevant to the failure mode — the root cause is wiring, not hardware provenance. Genuine Siemens modules from either production site are tested to the same acceptance criteria at the factory.

Root Cause: Module Electronics Supply (L+/M) Not Energised

The S7-1200 signal module requires two distinct 24 VDC rails to switch an output:

  1. Module electronics supply on terminals L+ and M. This rail powers the backplane transceiver, the relay coils (or the output-driver transistors), and the status LEDs. It is sometimes called the "logic supply" or "module supply". Operating range is 20.4 V to 28.8 V DC.
  2. Load supply on terminals 1L, 2L, 3L, 4L (relay SM) or 1L / 2L (transistor SM). This is the rail that the relay contact — or the source-driver high-side FET — actually switches to the field device. It is galvanically isolated from the module electronics supply and may be any voltage the contact is rated for (for HH32 relay contacts, that is 5 V to 30 V DC or 5 V to 250 V AC).

With the module supply unpowered, the following chain of events occurs on the affected SM 1222 / SM 1223:

  1. The CPU can still write the process image and the SM's I/O ASIC latches the requested state — so the on-board LED logic may still appear to track the commanded value (the status LEDs are typically driven from the logic side, not the contact side).
  2. The relay coils have no energy and the contacts stay open. With a transistor SM the high-side drivers are biased off, so the output terminal sits at 0 V regardless of the commanded state.
  3. Forcing a bit in TIA Portal → Online & diagnostics → Force table succeeds at the data-link level (the LED toggles, the watchdog does not trip), but the physical output does not change because the driver stage is unpowered.
  4. No SF (system fault) LED is raised and no diagnostic interrupt is queued — the CPU has no way to know the module is unpowered, because the backplane is still functional.

The original wiring in the reported case connected 230 VAC to the 3L terminal of the SM 1222 in the mistaken belief that this would switch the relay output. The 24 VDC electronics supply on L+ / M was never wired. The fix was to route a clean 24 VDC source to the module's L+ and M terminals; the load-supply terminals were then wired with the actual field voltage, and all 16 outputs of each SM 1222 began to switch.

Why no fault is reported. The S7-1200 SM does not monitor the presence of the 24 VDC on L+/M. The SF LED stays off, the diagnostics buffer remains clean, and the CPU's web server / HMI shows no error. This is by design — a separately powered I/O island can be intentionally de-energised while the controller keeps running. It is also why the failure mode can fool even experienced technicians: a healthy "green RUN" and a healthy communication handshake are not the same as a healthy output.

S7-1200 Signal Module Power Architecture

The S7-1200 separates power domains deliberately. The diagram below shows the corrected wiring for an SM 1222 6ES7 222-1HH32-0XB0, which is the same architecture used by the SM 1223 6ES7 223-1PL32-0XB0 relay outputs.

SM 1222 (6ES7222-1HH32-0XB0) — Correct Power Wiring 24 VDC Power Supply L+ / M (cabinet rail) CPU 1214C (DC/DC/RLY) L+ (24 V in) M (0 V in) Sensor Pwr L+ (out) Sensor Pwr M (out) DQ a.0 .. a.7 DQ b.0 .. b.7 (onboard relay contacts) Sensor Pwr limit: typ. 400 mA total SM 1222 (16 DO Relay) 6ES7222-1HH32-0XB0 L+ (24 V module) M (0 V module) Output groups (relay contacts) 1L 2L 3L 4L DQ a.0..a.3 DQ a.4..a.7 DQ b.0..b.3 DQ b.4..b.7 Field Load (e.g. contactor coil) +24 VDC (L+) 0 V (M) Load (group L → DQ) ⚠ Module supply (L+/M) and load supply (1L..4L) are SEPARATE — both must be wired

Key observations from the diagram:

  • The cabinet 24 VDC rail feeds the CPU's L+/M power input.
  • The CPU's sensor power output (or a separate 24 V rail, recommended) feeds the SM's L+ and M. This is the rail that was missing in the original wiring.
  • The four load-supply terminals 1L..4L on the SM 1222 each connect to the source that the corresponding group of four relay contacts switches. Each group is electrically isolated; the rail voltage on each nL can be different (24 VDC, 120 VAC, 230 VAC, etc., within the contact rating).

Diagnostic Methodology

Use this sequence whenever a S7-1200 SM output "does nothing" while the LED appears correct.

  1. Confirm the CPU is in RUN and the slot is mapped. In TIA Portal, open Online & diagnostics → Diagnostics status for the affected SM. The status should read OK with no pending diagnostic interrupts. If the slot shows Fault or Not accessible, the wiring is a secondary issue — resolve the backplane problem first.
  2. Measure the SM supply terminals. Place a DMM between L+ and M on the SM itself (not the upstream rail). The expected reading is 20.4 V to 28.8 V DC. A reading of 0 V is the failure mode that caused the original incident.
  3. Measure the load-supply terminals. With the load supply rail de-energised for safety, place a DMM between each nL terminal and the corresponding DQ terminal with the output commanded ON. The expected reading is closed contact (typically < 1 Ω). If the reading is open (> 1 MΩ) while the LED is on, the relay coil is not energising — go back to step 2.
  4. Force the output. In TIA Portal, use Online & diagnostics → Force table to force a single output. Watch the SM LED. If the LED tracks the force but the contact does not close, the module's internal driver or coil is unpowered or damaged. If the LED does not track the force, the slot mapping or firmware is wrong.
  5. Test other outputs in the same group. Force a different DQ in the same group. If the other outputs work, you have an over-current or short on the failing channel that may be dragging the group rail down. If all outputs in the group fail, the group supply (nL) is missing or the module is defective.
  6. Test outputs in a different group. Force an output in 2L's group. If that group works, the problem is isolated to the 1L/2L/3L/4L rail and its wiring — not the module supply.
  7. Inspect for DOA hardware. If steps 1–6 all point to a healthy module supply and healthy load supply, but a specific DQ still does not switch, the module is defective. Tag it for RMA. Do not chase a wiring fault that does not exist.
Force vs. Modify. Use Force (F) to override the program output; use Modify (M) for a one-shot write. Forcing a value that the program then overwrites is a normal, not an error condition. Forcing is a diagnostic action — remove the force after the test or the output will stay latched.

Step-by-Step Wiring Procedure

The procedure below restores the missing 24 VDC module supply to the SM 1222 / SM 1223 and verifies correct operation. Power down the cabinet before touching terminals.

  1. Lock out and tag out (LOTO) the cabinet. Open the main breaker and verify zero energy with a known-good DMM at the field bus terminals.
  2. Identify the SM terminals. On the SM 1222 HH32, the module supply terminals are L+ and M on the upper connector. The load-supply terminals 1L..4L are below them. The 16 output terminals DQ a.0..b.7 are on the right-hand connector.
  3. Route a 24 VDC source to L+ and M. Use a dedicated 24 V PSU sized for the sum of all SM electronics (≈ 200 mA per SM 1222 HH32, ≈ 180 mA per SM 1223 PL32 at 24 V). Run the L+ and M conductors as a twisted pair back to the PSU to minimise noise pickup on the backplane.
  4. Wire the load-supply terminals 1L..4L. Connect each nL to the source that the corresponding group of four contacts switches. For DC loads, observe polarity only if the load is polarity-sensitive (most relay contacts are not). For AC loads, no polarity.
  5. Wire the field loads to the DQ terminals. Run the load conductor from DQ a.x / DQ b.x through the field device back to the appropriate supply return. For DC sourcing transistor outputs, this is the equivalent of a low-side switch — the load is between DQ and the positive rail, and M returns to the rail negative.
  6. Tighten terminals to the specified torque (typically 0.6 N·m for the S7-1200 spring terminals, 0.5 N·m for screw terminals — verify against the S7-1200 system manual).
  7. Restore cabinet power. Watch the SM LEDs at power-up. The PWR LED on the SM should illuminate within < 1 s. A SF LED or a flashing PWR LED indicates a hardware fault or under-voltage — re-check the supply rail at the SM terminals.
  8. Run a force-table test. Force each output ON for 2 s, then OFF. Verify the LED tracks the command and the contact closes. Cycle through all 16 outputs of each SM.
  9. Run a real-load test. Replace the force with a controlled program (e.g. a 5 s toggle in OB1 or a watch table) and verify the field device energises and de-energises cleanly.

Output Current Limits and Group Loading

Relays and transistors fail differently. The relay output modules (HH32, PL32) are limited by contact rating; the transistor modules (BH32, BL32) by on-resistance and thermal limits. The table below summarises the electrical limits you must respect; for the binding values, always consult the S7-1200 Programmable Controller system manual for your specific MLFB.

Parameter SM 1222 HH32 (16 DO relay) SM 1223 PL32 (16 DI / 16 DO relay)
Outputs per module 16 16
Output groups 4 isolated groups of 4 4 isolated groups of 4
Load-supply terminal per group 1L, 2L, 3L, 4L 1L, 2L, 3L, 4L
Continuous current per output 2 A (resistive) 2 A (resistive)
Continuous current per group (4 outputs) 8 A 8 A
Inrush (lamp load) 30 W DC / 200 W AC @ 230 V 30 W DC / 200 W AC @ 230 V
Mechanical life (cycles) 10 M (no load) 10 M (no load)
Electrical life (cycles, rated load) 100 k 100 k
Module supply L+/M current ~ 200 mA @ 24 V (all coils energised) ~ 180 mA @ 24 V (all coils energised)
Contact voltage range 5 V..30 V DC or 5 V..250 V AC 5 V..30 V DC or 5 V..250 V AC
Group limits are not optional. Four outputs in a group of four, each at the 2 A continuous rating, total 8 A — exactly the per-group limit. Any attempt to push the contact current above 2 A per point or 8 A per group will accelerate contact wear and may weld the contacts. If the load exceeds 2 A, use an interposing relay sized for the load.

Verification

After the wiring repair, run a structured verification cycle before releasing the panel:

  1. Voltage check at the SM terminals. With the cabinet powered, measure L+ to M at the SM itself. Expect 20.4 V to 28.8 V DC. Repeat for each load-supply terminal nL to its return. Record all readings.
  2. Force-table walk-through. Force each of the 16 outputs ON for 2 s in turn. Confirm the corresponding LED and the field device respond. Capture the readings with a screen recorder for the commissioning report.
  3. Group-load check. If the application drives all four outputs of a group simultaneously, measure the group current with a clamp meter. Confirm the steady-state current is ≤ 8 A and the inrush is within the lamp-load rating.
  4. Module electronics temperature. After 30 min of operation with the expected load profile, measure the front face of the SM with an IR thermometer. A reading above 60 °C is a sign of over-loaded or improperly tightened terminals.
  5. Diagnostic buffer sanity check. In TIA Portal, open the CPU's diagnostic buffer and confirm no entries for the SM slots. Any Wire break, Short circuit, or Load voltage missing entry (where supported by your firmware) needs to be investigated before sign-off.

Defective-on-Arrival (DOA) and Warranty Handling

Hardware can be DOA. The diagnostic path above should rule out wiring, supply, and configuration issues first; if a module still fails to switch a single output after the L+/M rail and the group load rail are confirmed healthy, the module is defective. Field-engineer practice:

  • Document the failure with the diagnostic buffer export, a wiring photo, and the DMM readings at L+/M and at the failing DQ terminal.
  • Open a warranty case with the Siemens regional representative. The MLFB and serial number are on the front of the module and in the device master in TIA Portal.
  • Do not attempt to repair the module. The relay contacts and the output-driver PCB are not field-serviceable; opening the housing voids the warranty.
  • While waiting for the replacement, run the application on a reduced I/O count if the program allows. Forcing outputs is a diagnostic action, not a workaround for production.

Common Wiring Pitfalls on S7-1200 Signal Modules

Pitfall Symptom Fix
L+ / M not connected to 24 VDC Output LED tracks the command but contact stays open (relay) or terminal stays at 0 V (transistor). No SF LED. Route a 24 VDC source to the module supply terminals.
230 VAC applied to L+ or nL of a DC-only module Immediate damage to the module's input protection; potential fire hazard. Power down, de-energise, replace the module, rewire with 24 VDC.
Mixing 1L..4L rails across different voltages without isolation check Short circuit at the first output; the entire group may be lost. Confirm each group's load supply is appropriate for the contact rating; keep groups galvanically separate if mixing AC and DC.
CPU sensor power overloaded (CPU 1214C sensor Pwr limited to ~400 mA) SM electronics intermittently resets, PWR LED flickers, outputs chatter. Use a separate 24 V PSU sized for the SM electronics + sensor loads.
Force table left populated after commissioning Outputs ignore the program. The HMI shows the right value but the field is stuck. Stop the CPU → Force table → Remove all → Restart.
Slot address offset miscalculated in TIA Portal Forcing DQb.0 toggles a different module's LED. Open Device configuration and verify the slot order. S7-1200 SM addresses are contiguous in the process image starting at the configured slot.
CPU firmware too old for V3 SM (suffix 32) Module does not come online, SF LED steady on. Update the CPU firmware to V3.0 or later (V4.0+ recommended for current support).
Mixed AC/DC groups. On the SM 1222 HH32, the four groups are isolated, so it is legitimate to run 24 VDC on 1L and 230 VAC on 3L at the same time. The relay contacts of one group cannot be back-fed into the load supply of another group as long as the supplies themselves are independent. If you mix AC and DC, label the wiring clearly and apply the right cable colour code to each group.

Quick Reference: MLFBs Mentioned

FAQ

Why does the SM 1222 output LED illuminate but the relay contact does not close?

The status LED is driven from the module's internal logic, which is powered by the 24 VDC on the module's L+/M terminals. The relay coil is also powered by that same rail. If L+/M is missing, the coil cannot energise, the contact stays open, and the LED can still appear to track the command. Measure 20.4–28.8 VDC between L+ and M at the SM itself to confirm the supply is present.

Do I need a separate 24 V supply for each SM 1222?

No. A single 24 VDC rail sized for the sum of all SM electronics can feed multiple modules in parallel. The SM 1222 HH32 draws approximately 200 mA at 24 V with all 16 relays energised. For a cabinet with several SMs, an external 24 V PSU in the 3–5 A range is usually the right choice. Avoid pulling the SM supply from the CPU's sensor power output, which is typically limited to ~400 mA and is reserved for CPU inputs and external sensors.

Can I power the SM's L+/M from the CPU sensor power output?

Technically yes, but only if the total sensor power budget (CPU inputs + SM electronics + external sensors) stays below the sensor power rating of the specific CPU. For a CPU 1214C the sensor power output is rated at approximately 400 mA. Forcing the SM 1222 plus a few 24 V sensors off that rail can trip the sensor power foldback. An external 24 V PSU is the safer choice for a populated cabinet.

Is the SM 1222 defective if forcing the output in TIA Portal does not switch the contact?

Not necessarily. Confirm first that L+/M reads 20.4–28.8 VDC at the SM, and that the load supply is present on the relevant nL terminal for the group containing the output. If both supplies are healthy, the output's DQ terminal still reads open against nL when forced, and the LED does not track the force, the SM is likely defective and should be returned under warranty.

What is the difference between L+, M and 1L, 2L, 3L, 4L on the SM 1222 HH32?

L+ and M are the 24 VDC module electronics supply; they power the backplane, the relay coils, and the status LEDs. 1L through 4L are the load-supply terminals for the four isolated groups of four relay outputs each. 1L feeds the contacts of DQ a.0..a.3, 2L feeds DQ a.4..a.7, 3L feeds DQ b.0..b.3, and 4L feeds DQ b.4..b.7. Each nL can be at a different voltage (5–30 VDC or 5–250 VAC) within the contact rating.

Back to blog