Resolving Siemens 840D Alarm 810005: STEP 7 Diagnosis Guide

David Krause22 min read
Other TopicSiemensTroubleshooting
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Overview of Alarm 810005 on SINUMERIK 840D MMC100.2

Alarm 810005 "Operating states sequence event, error analysis via STEP 7 required" is a PLC-side general alarm raised by the SINUMERIK 840D system firmware when the integrated S7 PLC detects an illegal or unexpected transition in the operating-state sequence of the machine's safety/logic chain. The alarm is presented on the MMC100.2 HMI when the HMI polls the PLC and reads at least one of the eight user alarm bits (DB2.DBB0–DBB7 on the SINUMERIK 840D MMC100.2) set by the user program. Alarm 810005 does not carry a precise NCK fault address; it is a wrapper that points the operator directly at the PLC user program and forces a STEP 7 / SIMATIC S7 diagnostic session to read the S7-300 CPU diagnostic buffer.

The MMC100.2 generation is the predecessor of MMC103 and PCU50 hardware platforms and corresponds to a SINUMERIK 840D (Powerline) system with a SIMATIC S7-300 PLC sub-rack. The relevant Siemens documentation for this platform family is the SINUMERIK 840D sl/840Di sl/828D Operator Components Manual (08/2014 edition, 6FC5397-1CP40-3BA0) and the SINUMERIK 840D sl Diagnostics Manual (06/2019, 6FC5398-6AP40-3BA3). Although the cited manuals target 840D sl hardware, the alarm numbering, the PLC interface, and the diagnostic flow remain identical for the Powerline/MMC100.2 generation. The classic 840D/810D Commissioning Manual is the SINUMERIK 840D/810D Commissioning Manual (Edition 04.96, 6FC5297-1AD10-0AP0) and the SINUMERIK 840D sl/840Di sl/828D Diagnostics Manual (01/2018, 6FC5398-6AP40-3BA0).

On an MMC100.2 panel, alarm 810005 is displayed in the red alarm line on the bottom of the HMI; clearing the alarm by power-cycling the NCU only suppresses the display because the underlying PLC fault is latched in the S7 CPU's diagnostic buffer. The PLC bit that triggers 810005 is M0.0 on the SINUMERIK PLC interface (DB2.DBB0 bit 0) or one of the user-defined PLC alarms DB2.DBB0–DBB7 that the user program has assigned to the parts-catcher and spindle-lock sub-systems. The correct response is therefore not an NC reset but a structured PLC diagnosis with STEP 7.

Alarm 810005 Definition, Class, and Numbering Range

Siemens alarm numbering on the SINUMERIK 840D is partitioned into the ranges listed below. Alarm 810005 falls in the "PLC general alarms" range, which is reserved for user-program-generated messages routed through the PLC→HMI interface.

Alarm Range Source Clearing Method
000000‐000999 NCK operating system NC reset / power-on
001000–009999 NCK / drive (611D) alarms NC reset / power-on
400000–600000 PLC general alarms (HMI→PLC interface) PLC acknowledge / user logic
600000–600999 HMI alarms Power-on
700000–809999 PLC user alarms (FB/FC program) PLC acknowledge / user logic
810000–819999 PLC general OS / sequence alarms (this alarm) STEP 7 diagnostic buffer read required
820000–839999 PLC compile / download errors Re-compile / re-download
900000–900099 Safety Integrated (SPL) alarms F-acknowledge

Within the 810000 range, alarm 810005 is defined in the SINUMERIK Operate / MMC100.2 alarm text database as "Operating states sequence event, error analysis via STEP 7 required". The alarm is always associated with a fault in the PLC user program, not in the NCK. The PLC program has either:

  1. Detected an illegal sequence in the state machine (e.g., spindle-lock cylinder requested to engage before the previous disengage cycle completed).
  2. Latched a watchdog / OB121 / OB122 fault (programming or access error in a non-recoverable OB).
  3. Lost retentive data after a battery-backed SRAM drop on the S7-300 CPU (typical for MMC100.2 systems that have been in service 15+ years).
Alarm 810005 is essentially a "go look at STEP 7" pointer. The HMI cannot resolve it; only the S7 diagnostic buffer can pinpoint the faulting OB, FB, or DB.

Symptoms Reported on a Lathe with MMC100.2 V.1.01

The reported machine exhibits the following layered symptoms, all of which are downstream of the same root cause and should be treated as a single fault tree:

  1. Alarm 810005 appears at power-on while the machine is idle (not cutting). No NC motion was in progress when the alarm was raised.
  2. A power-cycle clears the HMI line momentarily, but secondary PLC alarms for the parts catcher and the spindle locking cylinder appear immediately after the PLC restart. These alarms are user-defined in DB2.DBB4 / DB2.DBB5 in the standard SINUMERIK 840D MMC PLC template (part of the SINUMERIK 840D/810D Commissioning Manual).
  3. Manual operation of the hydraulic/pneumatic valves by depressing the small red manual-override button on each valve still actuates the cylinder. This proves that 24 V DC, the proportional valve coil, the limit switches, and the I/O wiring are intact. The fault is upstream of the valve, in the PLC output path or in the PLC program logic that drives the output.
  4. The fuse on the customer-supplied picture is the standard MMC100.2 backplane / PLC-output group fuse, 5×20 mm glass, T 6.3 A / 250 V, supplied from the secondary of the 230 V / 24 V DC control transformer mounted inside the operator-panel cabinet.

The combination of "alarm 810005 + downstream PLC user alarms + blowing fuse" is the classic signature of a stuck output / shorted wiring fault combined with loss of PLC retentive data. The PLC user program can no longer drive the outputs correctly because the topology database (which valve is on which output byte) is corrupted, so the outputs default in a state that sinks excessive current through one branch of the valve manifold, blowing the fuse.

Root Cause Analysis Methodology

Begin the diagnosis in the order listed below. Each step is gated by an expected outcome; do not skip ahead.

Step 1 — Read the S7-300 CPU Diagnostic Buffer

The diagnostic buffer (Diagnosepuffer) is a 100-entry ring buffer in non-volatile memory of the S7-300 CPU. It is the single most important data source for 810005. It contains, in chronological order, every OB entry (OB1 cycle time exceptions, OB85, OB86, OB100, OB101, OB102, OB121, OB122), every STOP→RUN transition, every parameter assignment error, and every time-of-day stamp. Open it from STEP 7 via PLC → Diagnostic/Setting → Diagnostic Buffer or by right-clicking the CPU in the online view and selecting Module Information → Diagnostic Buffer.

For the 16-year-old MMC100.2 system described, the most common entries seen before 810005 are:

  • STOP because of OB not loaded — the S7-300 CPU was rebooted without the OB86 (rack failure) or OB122 (I/O access error) blocks loaded, causing the CPU to STOP and the NC to raise 810005.
  • Battery exhausted, CPU in STOP — the buffer-backed SRAM battery is dead. The S7-300 CPU cannot retain retentive M, T, C, and DB data through power-off. This is by far the most common cause on a 16-year-old 840D.
  • I/O access error (OB122) in FBxxx, DBxxx, Byte x, Bit x — the user program is reading or writing an I/O byte that no longer exists (a re-wired input or a removed terminal block).
  • Time-of-day interrupt OB10/OB11 lost — a side effect of the battery issue.

Step 2 — Identify Which PLC User Alarm Bits Are Set

In the SINUMERIK 840D MMC100.2 PLC interface, eight bytes of user alarms are exposed to the HMI. The default assignment is shown in the table below; the exact assignment for any given machine tool is defined in the manufacturer-specific PLC project. Read the live value with STEP 7's Monitor / Modify Variable function or with the HMI's PLC → Status menu.

Address Bit Default Assignment (Standard MMC100.2 Tooling PLC)
DB2.DBB0 Bit 0–7 Operating-state sequence alarms (810000–810079)
DB2.DBB1 Bit 0–7 Operating-state sequence alarms (810080–810159)
DB2.DBB2 Bit 0–7 User alarms 1–8 (701000–701079)
DB2.DBB3 Bit 0–7 User alarms 9–16 (701080–701159)
DB2.DBB4 Bit 0–7 User alarms 17–24 (701160–701239)
DB2.DBB5 Bit 0–7 User alarms 25–32 (701240–701319)
DB2.DBB6 Bit 0–7 User alarms 33–40 (701320–701399)
DB2.DBB7 Bit 0–7 User alarms 41–48 (701400–701479)

If, for example, the parts-catcher alarm appears as alarm 701600 on the HMI line, the offending bit is DB2.DBB6 bit 0. Write down every bit that is set; this is the error map of the machine.

Step 3 — Cross-Check the Spindle-Lock and Parts-Catcher I/O

Once the diagnostic buffer is read and the bits are mapped, walk the program from the alarm bit back to the output. For the parts catcher, the typical signal chain is:

  1. Input: I 0.x "Parts catcher extended" (proximity switch on the cylinder rod).
  2. Input: I 0.x "Parts catcher retracted" (proximity switch on the cylinder body).
  3. Logic: FC / FB "PartsCatcher" with two latching states (extended / retracted) and a watchdog timer that expects the cylinder to complete the move within 2–3 s.
  4. Output: Q 0.x "Parts catcher extend solenoid" — 24 V DC, 2.5 W.
  5. Output: Q 0.x "Parts catcher retract solenoid" — 24 V DC, 2.5 W.

If the output byte is stuck high on one channel because the program is latched in an illegal state, the corresponding solenoid is continuously energized. With a 24 V / 2.5 W coil at continuous duty, the coil will draw 104 mA. If the feedback proximity switch is shorted, the input current can rise to 200–300 mA on a single output group. Five valves in continuous duty on the same output byte draw 520 mA, which is within the 6.3 A fuse rating, but if the wiring is shorted to ground (e.g., a pinched cable on the parts-catcher carriage), the fuse blows within 100 ms.

Prerequisites: Hardware and Software Required for Diagnosis

To read the S7-300 diagnostic buffer on a 16-year-old SINUMERIK 840D with MMC100.2, the following are required. None of these is a free download; STEP 7 is licensed software, and Siemens discontinued the parallel-USB / parallel-MPI cable years ago.

Item Siemens Catalog / Article Notes
STEP 7 (SIMATIC Manager) V5.5 SP4 or V5.6 6ES7810-4CC10-0YA5 (V5.5 SP4) / 6ES7810-6CC03-0YE5 (V5.6) STEP 7 V5.6 runs on Windows 7/10 64-bit with the V14 license-key USB stick. Required for all S7-300 / S7-400 online functions. STEP 7 Lite is not supported on S7-300 and is not usable for this fault.
PC adapter USB → MPI/DP 6ES7972-0CB20-0XA0 (PC Adapter USB A2) USB-to-RS485 converter at 187.5 kbps. Replaces the legacy 6ES7972-0CA23-0XA0 parallel-port adapter. Pin assignment per S7-300 CPU 314 Manual (6ES7390-1AE80-0AA0).
MPI cable (alternative) 6ES7901-0BF00-0AA0 (5 m) Pre-fabricated PROFIBUS cable with two 6ES7972-0BA12-0XA0 connectors. Older systems used this directly.
S7-PCT (Port Configuration Tool) optional 6ES7658-3CX06-0YA5 For PROFINET configuration; not strictly required for MPI access.
PG field PG M3 / Field PG M4 6ES7710-0.... Pre-installed STEP 7 bundle; available for industrial service technicians.
STEP 7 Lite is not the same product as STEP 7 V5.x. STEP 7 Lite targets S7-200 / LOGO! and cannot establish a PROFIBUS-MPI link to an S7-300 CPU. The FAQ at the end of this article addresses this misconception in detail.

STEP 7 Online Connection Procedure (MPI/DP)

The standard procedure to bring STEP 7 online with the S7-300 inside the SINUMERIK 840D MMC100.2 NCU is as follows. The SINUMERIK MMC100.2 has two X122 / X132 PROFIBUS / MPI ports on the back; either can be used, but do not connect to the NCK's PROFIBUS-DP line (X122 on the 840D) because that line carries drives and may interfere with the S7-300's MPI traffic. The 840D's PLC side exposes its own MPI / PROFIBUS at X122 (lower) on the S7-300 CPU itself.

  1. Install STEP 7 V5.5 SP4 (or V5.6) on the service laptop. Restart, then accept the license-key prompt and insert the 6ES7810-... USB license stick.
  2. Open SIMATIC Manager and create a new project. Right-click the project icon, choose Insert New Object → SIMATIC 300 Station. The hardware is recognized later via PLC → Upload Station to PG.
  3. Set the PG/PC interface: Options → Set PG/PC Interface → PC Adapter (MPI) → Properties. Set the baud rate to 187.5 kbps (this is the only baud rate supported by an MMC100.2 system). Set the station address to 0. The S7-300 CPU default MPI address is 2; do not change it unless the system integrator changed it.
  4. Connect the PC Adapter USB A2 to the service laptop's USB port, then plug the 9-pin Sub-D connector of the adapter onto the MPI socket of the S7-300 CPU. Tighten the thumb screws.
  5. Power the NCU if it is not already powered. From SIMATIC Manager choose PLC → Display Accessible Nodes. The S7-300 CPU should appear with its MPI address (default 2, possibly 1, depending on configuration). If it does not appear, check the baud rate and the cable; if it still does not, see the troubleshooting matrix below.
  6. Once the CPU is visible, choose PLC → Upload Station to PG to copy the entire PLC project to the laptop. Save the upload as-is; do not recompile or modify anything at this point.
RS-232 serial online access via the COM port on the front of the MMC100.2 panel is for the HMI (MMC) and the NCK diagnostic monitor, not for the S7-300 PLC. The PLC requires MPI/DP. This is the reason that STEP 7 cannot "just connect via RS-232" — the COM port on the panel does not bridge to the PLC.

Reading and Interpreting the S7 Diagnostic Buffer

Open the diagnostic buffer at PLC → Diagnostic/Setting → Diagnostic Buffer (or Module Information → Diagnostic Buffer). The most recent events appear at the top. The format of each entry is:

DDD.HH:MM:SS.SSS Event Internal error | OB / FB / DB reference | Module address | Rack / slot

The following table maps the entries most likely to be seen on a 16-year-old MMC100.2 lathe when alarm 810005 is active:

Diagnostic Buffer Text (English / Deutsch) SF LED Recommended Action
Battery exhausted (Batterie leer) On Replace the lithium battery on the S7-300 CPU (order code 6ES7971-0BA00; one A 5×20 mm 3.6 V cell). After replacement, cold-restart the CPU with MRES. Expect retentive data loss; reload the NC PLC backup.
STOP because of OB not loaded (STOP wegen fehlendem OB) On Download all standard OBs (OB1, OB40, OB80, OB82, OB85, OB86, OB100, OB121, OB122) from the library. The 840D base PLC project requires at least OB1, OB40, OB100, OB121, OB122.
I/O access error (OB122) at FB/DB/Byte On Trace the address to the symbol list. The I/O is either removed, miswired, or duplicated. Re-wire to the correct terminal on the ET200M IM153 / SM321/SM322 modules.
Communication error to distributed I/O (OB86) On PROFIBUS-DP line to the ET200M is down. Check the 9-pin Sub-D, the terminating resistor (ON at the two end nodes, OFF in the middle), and the shield bonding.
Parameter assignment error (OB100 / OB101) On Hardware configuration mismatch. Re-run Hardware Configuration (HW Config) and compare against the physical module order. Look for an SM module set as "missing" in HW Config.
Checksum error in user program On The Flash card / MMC card in the CPU has corrupted. Reload the NC PLC backup from the original commissioning archive.

Save the entire diagnostic buffer to a .txt file (right-click the buffer → Save As) and attach it to your service ticket. The buffer is unambiguous evidence of root cause and protects the warranty conversation.

Fuse-Blowing: Secondary Symptom of a Short-Downstream Fault

The 5×20 mm glass fuse visible in the operator's picture is the standard 24 V DC output-group fuse on the SINUMERIK 840D MMC100.2. It is fed from the secondary of a 230 V AC → 24 V DC control transformer / regulated power supply (typically a Siemens 6EP1334-3BA00 Sitop modular 10 A power supply or its predecessor). The fuse protects the eight SM322 DO (digital-output) channels on the 24 V rail.

Three failure modes are common on a 16-year-old machine:

  1. Short to frame on the 24 V DC solenoid wiring: a pinched cable against the parts-catcher carriage chassis or a hydraulic-oil-soaked cable near the spindle-lock cylinder. Measure resistance from each solenoid terminal to chassis ground with the solenoid disconnected. A reading below 1 MΩ indicates insulation breakdown.
  2. Short between the 24 V DC output and the OV return on the SM322 module: the SM322 module itself has failed. This is rare but happens on MMC100.2 systems that have run hot for years. Replace the SM322 (typical order code 6ES7322-1BH01-0AA0 for 16 DO 24 V DC).
  3. Defective coil / diode in the valve solenoid: the solenoid has an internal short between coil windings, drawing 1–2 A at 24 V DC and blowing the fuse within 1–2 s of energization. Disconnect each solenoid in turn (a hydraulic technician can do this in 5 min) and re-energize the circuit to identify the offending coil.

Procedure to isolate the fault:

  1. Switch off the 24 V DC supply at the cabinet isolator (typically a Siemens 5SY2 / 5SP2 miniature circuit breaker / 3RV1 motor protector). Verify zero voltage with a Fluke 87V or equivalent on the load side.
  2. Pull all field wiring off the SM322 DO module that feeds the parts catcher and spindle lock. Label every conductor.
  3. Use a Megger MIT420 or a standard insulation tester to measure from each conductor to chassis ground. The reading should be ≥ 100 MΩ. Any reading below 1 MΩ is a short.
  4. Reconnect the conductors one at a time, powering the 24 V DC and observing the fuse and the PLC error bits. The fuse will blow when the shorted branch is reconnected.
  5. Once the shorted branch is found, repair the cable (heat-shrink, replace gland, route away from moving parts) and re-energize.

Re-loading the NC PLC Backup Data

If the diagnostic buffer shows a checksum error, lost retentive data, or a corrupt MMC card, the next step is to reload the NC PLC backup. Siemens strongly recommends doing this only with a known-good backup that matches the exact machine configuration.

  1. From the HMI: Start-up → Commissioning → NC/PLC → NC-PLC Data Transfer. The path is menu-driven and depends on the MMC version; on MMC100.2, the sub-tree is Start-up → NC/PLC → Commissioning.
  2. Locate the backup .arc file (Siemens archive format) on the CF card of the HMI (typical path: D:\DH\ARC or F:\CARD\DH\ARC.DIR\*). The customer should have at least one .arc file dated around the time of the original commissioning.
  3. Choose Read in and select the matching .arc file. The system will display a series of prompts for the password (default Siemens: SUNRISE on a fresh 840D Powerline, but the customer should know their own password).
  4. Once read in, the NCU will automatically perform a warm restart and reload the PLC into the S7-300. The 810005 alarm should clear if the reload was clean.
  5. Verify the alarm is gone: power-cycle the machine, leave it idle for 5 minutes, and confirm the HMI alarm line is empty.
Reloading a backup will reset all machine data: tool table, work offsets, R parameters, and the PLC machine-data table. Capture a fresh backup of the current (corrupt) data first, and capture all user data (GUD, settable zero offsets) before reloading. Failing to do so will turn an 810005 fault into a full machine-recommissioning job.

Verification and Commissioning Checks

After the PLC backup is reloaded, run the following checks before returning the machine to production. Each row is a single-pass / fail test; record the result for the service ticket.

Test Pass Criterion Action on Fail
Power on with no alarms Alarm line is empty for 5 min idle Re-read diagnostic buffer; do not return to service.
Spindle lock engages on M10 Hydraulic pressure ≥ 50 bar, locking pin extended, feedback prox switch on within 1.5 s Check the output byte and the FC; suspect a corrupt FB.
Spindle lock disengages on M11 Pin retracted within 1.5 s, M11 completion reported Check the retract solenoid and the prox switch.
Parts catcher extends on M36 Carriage moves out, extended prox within 1.5 s, no fuse blow Check the cable; suspect a pinched wire.
Parts catcher retracts on M37 Carriage moves in, retracted prox within 1.5 s Check the retract solenoid and the cable.
Emergency stop All drives stop within 250 ms, E-stop relay drops out, all valves de-energize Check the safety chain (SPL); suspect Safety Integrated wiring.
Battery voltage at S7-300 CPU ≥ 3.0 V at the lithium cell (3.6 V nominal) Replace the battery; cold-restart the CPU.
Backup of current PLC project Successful .arc export to CF card, MD5 of the file noted Investigate the CF card reader.

Troubleshooting Matrix for 810005 + Blowing Fuse

The combined symptom of "alarm 810005 + PLC user alarms + blowing fuse" has a small set of possible root causes. The matrix below is the field-proven decision tree.

Observed Likely Root Cause Confirm By Fix
Diagnostic buffer: "Battery exhausted" Dead lithium battery on S7-300 CPU; lost retentive data Measure 3.6 V cell voltage with multimeter Replace 6ES7971-0BA00 cell; reload PLC backup; cold-restart
Diagnostic buffer: "STOP because of OB not loaded" OB121 / OB122 / OB86 / OB100 missing after a bad download Open Blocks folder in the online view; list OBs Re-add OBs from the Standard Library and reload
Diagnostic buffer: "I/O access error OB122" User program reads an I/O byte that does not exist Open the FB/FC called out in the buffer; read the byte access Re-wire to the correct ET200M terminal; or update the symbol list
Fuse blows only when the spindle-lock output is on Short in the spindle-lock solenoid wiring Insulation-test the conductor end-to-end Replace the cable; check the cable carrier for pinch points
Fuse blows at every power-on even with all outputs forced off SM322 module internal short Disconnect the field wiring; measure resistance on the SM322 terminals Replace the SM322 (6ES7322-1BH01-0AA0); rewire
All OK in STEP 7, but alarm 810005 still present at HMI HMI/PLC interface (DB2 / FC2) corrupted Compare the FC2 and DB2 against the original commissioning archive Reload the NC PLC backup archive; re-cross-check
All OK in STEP 7, alarm 810005 still present, no other symptoms NCK PROFIBUS line to the drives / NCU is bouncing Check X122 PROFIBUS connector, terminating resistor, shield bonding Re-terminate the bus; replace the connector

Spindle-Lock and Parts-Catcher Signal Chains (Reference)

The two sub-systems that raised the user alarms are the most safety-relevant auxiliary systems on a CNC lathe. The table below shows the typical I/O and timing for each.

Sub-system Inputs Outputs Typical Cycle Time Watchdog M-Code
Spindle lock (C-axis clamping) Lock engaged prox, lock released prox, hydraulic pressure switch Lock solenoid 24 V, release solenoid 24 V 1.0–1.5 s 2.0 s FC1 / FC2 timer M10 / M11
Parts catcher Extended prox, retracted prox, chuck-closed interlock Extend solenoid 24 V, retract solenoid 24 V 1.0–2.0 s 2.5 s FC1 timer M36 / M37
Chuck (aux) Chuck-closed prox, chuck-open prox, foot-switch Open solenoid 24 V, close solenoid 24 V 1.5–2.5 s 3.0 s FC1 timer M12 / M13

All four sub-systems share the same 24 V DC output group and the same 6.3 A fuse. A single short in any of them can blow the fuse and prevent all four from operating. The cross-checking procedure in Fuse-Blowing: Secondary Symptom of a Short-Downstream Fault above isolates which sub-system is shorted.

Spare Parts Recommendation for a 16-Year-Old MMC100.2

For a machine in service for 16+ years, the following spares are strongly recommended and should be on the shelf before the next failure:

Spare Part Siemens Order Code Quantity
S7-300 CPU 314 (or 315-2 DP) 6ES7314-1AE13-0AB0 / 6ES7315-2AH14-0AB0 1
S7-300 lithium battery 6ES7971-0BA00 2
SM322 DO 16×24 V DC 6ES7322-1BH01-0AA0 1
SM321 DI 16×24 V DC 6ES7321-1BH02-0AA0 1
PC Adapter USB A2 (MPI/DP) 6ES7972-0CB20-0XA0 1 (loan pool if not owned)
5×20 mm T 6.3 A / 250 V glass fuse Non-Siemens (Wickmann 196 series or equivalent) 10
CF card for MMC100.2 backup 6FC5247-0AA00-0AA0 (CF 2 GB) or compatible 1

Reference Documentation

Refer to the following official Siemens documents while performing this diagnosis. The URLs below are the official Siemens Industry Online Support entries and should be opened with a registered Siemens MySupport account for full PDF access.

What does Siemens 840D alarm 810005 actually mean?

Alarm 810005 is a PLC-side general alarm in the 810000–819999 range, defined as "Operating states sequence event, error analysis via STEP 7 required." It tells the operator that the S7-300 PLC has detected an illegal transition or programming error and that the S7 diagnostic buffer must be read with STEP 7 to identify the faulting OB, FB, or DB.

Can I clear alarm 810005 by simply turning the machine off and on?

No. Power-cycling the NCU may suppress the HMI display temporarily, but the underlying PLC fault is latched in the S7-300 CPU's diagnostic buffer. If the cause is a lost OB, dead battery, or corrupt user program, the alarm (and any user-defined downstream PLC alarms such as the parts-catcher / spindle-lock alarms on DB2.DBB0–DBB7) will return on the next restart. A STEP 7 diagnosis is mandatory.

Is STEP 7 Lite good enough to diagnose this fault on a 16-year-old 840D?

No. STEP 7 Lite is for S7-200 / LOGO! and does not support PROFIBUS-MPI online access to an S7-300 CPU. Use STEP 7 V5.5 SP4 (6ES7810-4CC10-0YA5) or V5.6 (6ES7810-6CC03-0YE5) together with a PC Adapter USB A2 (6ES7972-0CB20-0XA0) at 187.5 kbps. The default MPI address of the S7-300 in an MMC100.2 system is 2.

Can I go online with the S7-300 via the RS-232 port on the front of the MMC100.2 panel?

No. The RS-232 (COM) port on the front of the MMC100.2 is for the HMI's own serial service interface; it does not bridge to the S7-300 PLC. Online access to the S7-300 requires an MPI/DP connection at 187.5 kbps via the PC Adapter USB A2 or an equivalent MPI cable on the CPU's MPI socket. The PROFIBUS port at X122 on the NCU is for NCK ↔ drive communication, not for PLC online access.

Why does the fuse blow only when I run a parts-catcher M-code and not at idle?

The fuse is on the 24 V DC output group that powers the parts-catcher and spindle-lock solenoids. At idle, those outputs are OFF and no current flows. When the M-code turns one of the outputs ON, a short-circuit in the field wiring (pinched cable, oil-soaked insulation) or a shorted solenoid coil sinks the full short-circuit current — typically tens of amps for tens of milliseconds, more than the 6.3 A slow-blow fuse can sustain, so the fuse opens. Insulate-test the wiring and the coil; replace the SM322 module if the wiring is clean.

Is it safe to reload the NC PLC backup data while the customer is mid-job?

No. Reloading the NC PLC backup archive will reset the tool table, all work offsets, all R parameters, all GUD (global user data), and the PLC machine-data table. Always capture a fresh backup of the current (even if corrupt) state first, export all user data, and inform the customer that a full recommissioning of the machine's working data is required. The PLC program itself can be reloaded; the user's working data cannot be recovered from the original backup.

Back to blog