Resolving Siemens MasterDrive VC Fault F002: DC Link Diagnosis

David Krause12 min read
SiemensTroubleshootingVFD / Drives
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

1. Problem Statement: Intermittent F002 on a MasterDrive VC

The Siemens SIMOVERT MASTERDRIVES Vector Control (VC) drive, catalog number 6SE7016-1EA61-Z with option Z=G91, has been reported to trip on fault F002 intermittently within the first 20 operating hours. The fault is non-deterministic: the drive will refuse to start on several attempts, then begin operating normally, only to repeat the trip hours or days later. A replacement unit shipped under warranty subsequently triggered a Safe Off alarm that the option code should not have permitted, prompting a second warranty swap and a factory field engineer visit. This article isolates the F002 root cause, ties it to the DC link measurement path, and walks through the diagnostic and verification sequence used to clear the fault in production.

Field note: F002 on a MasterDrive VC is a measurement-class fault, not a power-class trip. It does not automatically imply a destroyed IGBT module. Treat the drive as repairable until the measurement chain is proven defective.

2. F002 Fault Definition

On the 6SE70 platform, F002 = DC link voltage measurement error. The control board (CUVC) samples the DC bus through an isolated voltage divider on the inverter power stage, digitises the result, and compares it against the firmware model. When the sampled value disagrees with the model by more than a fixed tolerance for a defined time window, the drive declares F002 and inhibits pulse enable.

Attribute Value
Fault number F002
Fault class Measurement / supervision
Default drive response Pulse inhibit, coast to stop, OFF2
Acknowledgement Power-cycle or fault reset per P840
Parameter affected r006 (DC link voltage actual), r047 (fault memory)
Cross-references F001 (DC link overvoltage), F004 (DC link undervoltage), F006 (line phase failure)

The fault should not be confused with F001 (DC link overvoltage) or F004 (DC link undervoltage), which are threshold trips on a known-good measurement. F002 means the measurement itself is untrustworthy, so the drive refuses to enable rather than risk operating from a corrupt bus value.

3. Affected Drive: 6SE7016-1EA61-Z, Z=G91

The 6SE70 catalog is decoded as follows for the unit in question:

  • 6SE7016 – Compact PLUS frame size, 400 V class, approximate 5.5–7.5 kW continuous output.
  • 1EA61 – Vector Control (VC) firmware, CUVC control board, standard IGBT inverter.
  • Z=G91 – Customer-specific option, typically a special firmware variant, connector pin-out, or label set. Confirm the option sheet shipped with the drive before assuming standard parameter defaults.

Reference the official SIMOVERT MASTERDRIVES Compendium (6SE70) and the 6SE70 Operating Instructions on Siemens Industry Online Support to confirm the exact frame size, rated current, and option interpretation. The ratings sticker on the drive (typically on the side of the heatsink) is the authoritative source for kW, A, and input voltage range.

4. Root Cause Analysis: The DC Link Measurement Chain

The DC link voltage is measured through the following chain, and a defect at any stage can produce F002:

  1. DC bus capacitor bank – supplies the actual voltage to be measured.
  2. Precharge / soft-charge circuit – limits inrush at line connect; if it is open, the bus may not reach the model-predicted value during the precharge window.
  3. Isolated voltage divider on the IVI (Inverter) board – scales the bus to a level the CUVC ADC can read.
  4. Optocoupler / isolation barrier – provides the galvanic isolation between power stage and control.
  5. CUVC control board ADC channel – digitises the scaled value.
  6. Firmware model and tolerance check – r006 is the final read-back; if the firmware self-check on this read-back fails, F002 is raised.

Reported root causes for F002, in order of frequency in the field:

Rank Root cause Diagnostic clue
1 Intermittent solder joint / cold joint on IVI voltage divider Fault clears after thermal cycling; r006 stable when warm
2 Failing optocoupler on the isolation barrier r006 reads correctly at no-load, errors under load
3 DC link capacitor ESR increase (early-life defect) Excessive bus ripple, F002 more likely under high load
4 Precharge contactor / resistor failure Bus does not reach nominal within precharge time
5 CUVC ADC channel drift r006 is offset by a fixed amount across the operating range
6 Wiring / motor insulation breakdown creating reflected transients on the bus Fault correlates with motor switching events
7 EMI / grounding issue on the control wiring harness Fault correlates with adjacent VFD switching or welding

5. The Safe Off (SSTO) Complication

The replacement drive in the source incident raised a Safe Off alarm, which on the 6SE70 family is implemented as the Safe Standstill (SSTO) safety function. SSTO requires the safety option hardware to be present – typically order codes K80 or similar – and gates the IGBT gate-drive signals through a redundant hardware path so that the motor cannot develop torque.

Important: If the option code sheet (the Z= suffix) does not include a safety option such as K80, L20, or a G91-specific safety sub-option, the drive should not be able to enter the Safe Off state. A Safe Off alarm on a non-SSTO drive is one of two things: (1) a firmware build mismatch on the CUVC that includes SSTO logic even when the option hardware is absent, or (2) the option sheet has been misread and the safety option is actually present. Always verify against the factory Z-Option Sheet shipped with the unit, not the commercial catalog description.

Safe Off typically ties to parameter r049 / P980 and the safety SS1 / STO timing parameters. On a non-safety drive that raises Safe Off, reflash or replace the CUVC firmware to the build matched to the option code. Confirm the firmware build with the MASTERDRIVES Compendium firmware matrix.

6. Pre-Diagnostic Safety Checks

Before opening the drive, complete these safety steps without exception. The 6SE70 DC bus retains lethal voltage for the discharge time printed on the front cover (typically 5 minutes after line removal for this frame size).

  1. Lock out and tag out the upstream disconnect.
  2. Wait the full discharge interval posted on the drive.
  3. Measure the DC bus at the test points (TB1 on most 6SE70 Compact PLUS units) with a properly rated meter. Confirm < 5 VDC before contact.
  4. Verify the motor is mechanically free to rotate or is decoupled.
  5. Document r006, r008, r047, r049, P515, P516, P518 from the keypad before powering down. Use DriveMonitor or the OP1S operator panel.

7. Step-by-Step Diagnostic Procedure

Follow this sequence to isolate the F002 cause with a minimum of board swaps.

Step 1 – Capture the fault buffer

On the OP1S panel: navigate to Menu > Parameters > r047 and record the last eight faults with their time stamps. F002 appearing repeatedly without F001/F004 (overvoltage/undervoltage) confirms a measurement rather than a threshold event.

Step 2 – Monitor r006 live

With the drive enabled and unloaded, observe r006 (DC link voltage actual). For a 400 V class drive the expected value is approximately 540 VDC at no load with a 400 VAC three-phase supply. A reading that:

  • Reads zero – open in the voltage divider, broken sense wire, or IVI board defect.
  • Reads a constant offset – ADC calibration drift on the CUVC.
  • Fluctuates wildly – intermittent solder joint, failing optocoupler, or noisy grounding.
  • Is correct at no-load, errors at load – optocoupler linearity failure or motor-side transient injection.

Step 3 – Verify the model value

Compare r006 to the model value computed by the firmware. The drive predicts the expected DC link from the rectified line voltage (P017 / r017). If the predicted and measured values diverge, the measurement hardware is suspect, not the firmware model.

Step 4 – Measure the bus directly

With the drive de-energised and discharged, measure the resistance from each DC bus test point to the corresponding ADC input on the CUVC edge connector. Compare to the schematic in the operating instructions. An open reading identifies a broken trace or cold joint.

Step 5 – Inspect the IVI (Inverter) board

Remove the IVI board and visually inspect under magnification. Reflow any suspect solder joints, particularly the voltage divider and optocoupler pins. Reinstall and re-test. This step alone resolves a majority of intermittent F002 faults on drives with low operating hours.

Step 6 – Test the motor cable and insulation

Megger the motor windings and the cable to ground. A winding with degraded insulation can inject common-mode transients that the CUVC interprets as a measurement error. Disconnect the motor leads at the drive terminals and re-test; if F002 disappears, the issue is downstream.

Step 7 – Evaluate capacitor health

Measure DC link ripple with an isolated scope probe on the bus test points. A healthy 400 V class bus shows < 5 % peak-to-peak ripple at full load. Excessive ripple combined with F002 indicates capacitor ESR increase and warrants an IVI / capacitor bank replacement.

8. Parameter Reference

The following MasterDrive VC parameters are central to F002 diagnosis. Always confirm against the parameter list shipped with your firmware build; numbers below are representative for the standard CUVC firmware family.

Parameter Function Use for F002
r006 DC link voltage actual (V) Live read-back to confirm measurement
r008 Status word Identify the bit set at trip (bit 3 = DC link fault)
r017 Modulation depth / line voltage derived Compare to r006
r047 Fault buffer (8 deep) Read full fault history
r049 Operating hours, fault counter Confirm 20-hour operating profile from source case
P515 DC link undervoltage threshold Confirm not mis-tuned
P516 DC link overvoltage threshold Confirm not mis-tuned
P518 DC link monitoring enable / time Tune window if borderline hardware
P536 DC link voltage setpoint source For V/Hz and vector profiles
P840 Fault acknowledgement source Set to local for bench test
P980 Safety / SSTO configuration Investigate Safe Off on non-safety drive

9. Repair vs. Replacement Decision

With only 20 hours on the clock, the unit is well inside the infant-mortality window. The decision tree:

  • Repair on-site – reflow IVI solder joints, replace optocoupler, replace capacitor bank. Cost-effective if the IVI is accessible and the shop is equipped for through-hole / SMD rework.
  • Warranty swap – justified in the source case, but verify the replacement carries the same firmware build and option code. A swap that changes the CUVC firmware can introduce the Safe Off issue seen in the source thread.
  • Factory refurbishment – preferred when the drive carries a safety option, when the fault is intermittent (suggesting intermittent component failure), or when a Siemens field engineer is already on site.

When requesting a warranty replacement, supply Siemens with the r047 fault buffer, the operating-hours counter (r049), and the Z-option sheet. This package allows the repair depot to correlate the failure with any known batch issue and to ship a replacement with a verified firmware build.

10. Verification & Commissioning

After the repair or replacement, complete this verification sequence before releasing the drive to production.

  1. Power the drive with the motor disconnected. Run a no-load test of at least 30 minutes, monitoring r006 for stability.
  2. Apply load in 25 % steps up to 100 % rated current. Hold each step for 10 minutes and log r006, r008, the heatsink temperature, and the fault buffer.
  3. Cycle the drive on and off ten times, with a 2-minute run and 1-minute stop, to exercise the precharge circuit. No F002 should occur.
  4. Confirm all three input line phases are present and within tolerance; loss of a phase can produce F002 on some firmware builds.
  5. Verify the Safe Off / SSTO behaviour matches the option code. On a non-safety drive, the Safe Off bit must remain low at all times.
  6. Capture the final commissioning parameter dump (DriveMonitor trace or OP1S upload) and file it with the drive's serial number.

11. Troubleshooting Matrix

Symptom Most likely cause First action
F002 only on cold start Capacitor ESR / precharge contactor Check precharge, measure bus at power-up
F002 only when warm Solder joint / optocoupler drift Reflow IVI, replace optocoupler
F002 only under load Optocoupler linearity / motor insulation Megger motor, scope bus ripple
r006 reads 0 V Open in voltage divider Resistance check from bus to CUVC input
r006 offset by fixed value CUVC ADC calibration Replace or recalibrate CUVC
Safe Off on a non-safety drive Firmware / option mismatch Verify option sheet, reflash CUVC to matched build
F002 recurs within hours of repair Second-stage component failure Full bench test with logged r006 over 8 h
F002 with F006 simultaneously Lost line phase Check input fuses, contactor, line quality

12. Documentation & Escalation Path

If the F002 recurs after a warranty replacement, escalate through the following channels with the listed evidence:

  1. Open a Siemens Industry Online Support ticket (SIOS) referencing the drive serial number and the previous RMA.
  2. Attach the r047 fault buffer, the r006 log, and the option sheet.
  3. Request a Siemens field engineer visit, citing intermittent measurement-class fault with infant-mortality operating profile.
  4. If the engineer visit confirms a batch issue, request a coordinated firmware audit of all 6SE7016-1EA61-Z, Z=G91 units on site.

For the latest MASTERDRIVES documentation, firmware listings, and safety advisories, consult the SIMOVERT MASTERDRIVES Compendium and the 6SE70 Operating Instructions on Siemens Industry Online Support.

What does fault F002 mean on a Siemens MasterDrive VC?

F002 is a DC link voltage measurement error on the 6SE70 platform. The drive's control board cannot trust its own bus voltage read-back, so it inhibits pulses. It is distinct from F001 (overvoltage) and F004 (undervoltage), which are threshold trips on a known-good measurement.

Is F002 always a hardware failure?

No. F002 can be triggered by a failing optocoupler, a cold solder joint on the IVI board, capacitor ESR increase, a precharge circuit defect, motor insulation breakdown, or CUVC ADC drift. Software or parameter causes are possible but rare; always rule out the measurement chain first.

Why did the replacement MasterDrive show a Safe Off alarm when the option code should not include it?

The replacement CUVC was likely flashed with a firmware build that includes SSTO logic even though the option hardware is absent, or the option sheet was misread and a safety option is actually present. Compare the CUVC firmware version against the Z-option sheet and reflash to the build that matches the order code.

What is the first parameter to monitor when chasing F002?

Monitor r006 (DC link voltage actual) live on the OP1S panel. For a 400 V class drive, expect approximately 540 VDC at no load. A reading of zero, an offset, or wild fluctuation identifies which stage of the measurement chain is failing.

Can the F002 drive be repaired on site, or does it need a warranty swap?

If the operating hours are low (the source case was 20 hours, well inside the infant-mortality window), on-site repair of the IVI board (reflow, optocoupler replacement, capacitor bank replacement) is often faster than a warranty swap. Reserve the warranty route for confirmed board-level failures or when a Siemens field engineer is already engaged.

Back to blog