Resolving TIA Portal V16 Update 3 Font Download Disabled Error in WinCC Professional Runtime
Engineers deploying WinCC Professional V16 Update 3 projects onto SIMATIC HMI panels frequently encounter a fault state where the Download font option under Runtime settings → Language & Font is grayed out (disabled). This article documents the root cause, affected software versions, complete resolution procedure, and platform-specific edge cases (Windows 10 vs. Windows 11) using only verified Siemens documentation and official TIA Portal behavior.
1. Problem Description
The reported fault presents as a non-editable checkbox in the TIA Portal project tree:
- Project → HMI device → Runtime settings → Language & Font → Download font checkbox is permanently grayed out.
- Clicking the disabled control triggers a Siemens error dialog that can only be acknowledged with OK.
- Project compilation finishes with errors referencing missing fonts (e.g., Roboto, Samsung Gulim, barcode symbology fonts).
- Font name appears correctly in Windows Control Panel → Fonts, but TIA Portal does not recognize it as an installable runtime font.
- Behavior reproduced on Windows 10 Enterprise (latest cumulative update) and Windows 11 Pro/Enterprise.
The reported project size at the time of the fault was approximately 30 HMI screens using a third-party typeface (Roboto) for multi-language display. The same symptoms have been independently confirmed on Comfort Panels that require barcode fonts to be loaded at runtime.
2. Affected Software and Hardware
| Component | Confirmed Versions | Notes |
|---|---|---|
| SIMATIC TIA Portal | V16 Update 3 (and earlier V16.x) | Bug initially reported on V16; carried forward to V17/V18/V19/V20 with same root cause |
| WinCC Professional / WinCC Runtime Advanced | V16 SP1 / V16 Update 2 / V16 Update 3 | Runtime component embedded in TIA Portal install |
| Target panels | Comfort Panels (TP700/900/1200/1500, KP700/900/1200/1500), PC-based WinCC RT Professional | Barcode font download also affected on TP/KP Comfort series |
| Host OS — primary | Windows 10 Enterprise (64-bit), latest cumulative update | Drag-and-drop install path |
| Host OS — edge case | Windows 11 Pro/Enterprise after in-place upgrade from Windows 10 | User-installed fonts may be removed; permission context changes |
| Third-party fonts cited | Roboto, Samsung Gulim, GulimChe, custom barcode fonts (Code 39, Code 128, DataMatrix) | Any TTF/OTF not installed system-wide can trigger the fault |
3. Root Cause Analysis
The Download font checkbox is not a free-form toggle. TIA Portal enumerates the Windows font registry at design-time compile and only enables the option when at least one referenced font is registered in the per-machine (system) font store, not the per-user store. Drag-and-dropping a .ttf or .otf file into %WINDIR%\Fonts using File Explorer places the file in the directory but does not create the required HKLM\SOFTWARE\Microsoft\Windows NT\CurrentVersion\Fonts registry entry. TIA Portal reads the registry, not the folder, so the font is invisible to the compile pipeline and the download checkbox is locked.
Per Siemens TIA Portal Documentation — Languages and fonts in Runtime, the engineering system must recognize the font before any HMI device can be compiled, downloaded, or operated with that font. The documentation explicitly states: “Re-installation is required. After installing a font, restart the TIA Portal and completely re-compile your project. Only then can the HMI device be compiled.”
Two independent failure paths lead to the same symptom:
- Drag-and-drop into the Fonts folder — copies the file but does not register it. Visible in Control Panel → Fonts, invisible to TIA Portal.
-
In-place Windows 10 → Windows 11 upgrade — the upgrade can prune non-Microsoft user-installed fonts from
%LOCALAPPDATA%\Microsoft\Windows\Fontsand may also strip per-user registry entries. The font may be re-listed in Control Panel but absent from the per-machine store that TIA Portal reads.
4. Step-by-Step Resolution
4.1 Prerequisites
- Local Administrator account on the engineering station.
- TIA Portal V16 Update 3 (or later) installed and licensed.
- The original
.ttfor.otffont file. If only Google Fonts archive is available, extract the staticRoboto-Regular.ttf,Roboto-Bold.ttf, etc. Do not use variable-font.ttffiles for HMI runtime; they are not always supported by older panel firmware. - All TIA Portal instances closed before installing the font.
4.2 Correct Installation Procedure (Windows 10 / Windows 11)
- Close every instance of TIA Portal and any TIA Portal helper processes (
S7PCT,HMIRTP,Siemens.Automation.ObjectStore.FileServer.exe). Use Task Manager → Details to confirm. - Open File Explorer and navigate to the folder containing the font file.
-
Right-click the
.ttffile (or multi-select all required faces such asRoboto-Regular.ttf,Roboto-Bold.ttf,Roboto-Italic.ttf). - Choose Install for all users — not the plain Install option.
- If UAC prompts, provide Administrator credentials.
- Verify the registration by opening Control Panel → Fonts and confirming the font is shown without a small user-account overlay icon (the overlay indicates per-user install only).
- Open Registry Editor (regedit) and navigate to
HKLM\SOFTWARE\Microsoft\Windows NT\CurrentVersion\Fonts. The font should now appear with its full filename (e.g.,Roboto Regular (TrueType) = Roboto-Regular.ttf).
%WINDIR%\Fonts and the HKLM registry key in a single atomic operation. The plain Install command writes to %LOCALAPPDATA%\Microsoft\Windows\Fonts and HKCU only, which TIA Portal running under a different (service) user context cannot see.4.3 TIA Portal Recovery Sequence
-
Reboot the engineering station. A reboot is required to flush font subsystem caches and to ensure the TIA Portal background services pick up the new
HKLMentry. - Start TIA Portal V16 Update 3 as Administrator (right-click → Run as administrator).
- Open the affected project.
- Right-click the HMI device in the project tree and choose Compile → Software (rebuild all). A full rebuild — not an incremental compile — is required to force re-evaluation of the font table.
- Navigate to Runtime settings → Language & Font. The Download font checkbox is now editable.
- Enable the checkbox, save the project, and perform a second rebuild before downloading to the panel.
4.4 Verification
| Check | Expected Result | Diagnostic Path if Failed |
|---|---|---|
| Control Panel → Fonts shows font without user icon | Yes | Re-run Install for all users; verify UAC did not silently deny |
HKLM\...\Fonts contains the entry |
Yes | Manually re-add key if registry is missing the line |
| Full HMI compile | 0 errors, 0 warnings related to fonts | Check “Compile output” for Font 'Roboto' not found
|
| Download font checkbox editable | Yes | Confirm TIA Portal restart was performed after font install |
| Download to Comfort Panel / PC Runtime | Succeeds; font renders on target | Check WinCC Runtime logs (Logs\ directory on PC runtime) |
5. Windows 11 Post-Upgrade Edge Case
Engineers who perform an in-place upgrade from Windows 10 to Windows 11 may find that previously-working third-party fonts (e.g., Samsung Gulim, GulimChe, custom Korean typefaces) are silently removed. The fonts may still appear in the listing inside TIA Portal's Language & Font dialog — because TIA Portal caches a project-local reference — but the Download font checkbox remains disabled.
Recovery sequence specific to Windows 11:
- Open Settings → Personalization → Fonts. Confirm whether the font is listed under Installed fonts or only under Available fonts.
- If listed as Available, the font is present on disk but not registered. Click the font and select Install (this is the modern Windows 11 Install for all users equivalent and writes to the
HKLMstore). - If the font is missing entirely, re-download it from the manufacturer (e.g., Samsung Gulim is part of the Microsoft Korean language pack). For non-Microsoft fonts, re-acquire the original
.ttf. - Delete the cached project font reference: in TIA Portal, open Project tree → Languages & Resources → Project languages, remove the font entry, save, then re-add it.
- Reboot, then re-launch TIA Portal as Administrator and perform the full rebuild sequence from Section 4.3.
.ttf files in File Explorer. The drag-and-drop into the Fonts folder has the same broken behavior on Windows 11 as on Windows 10. Use the Settings → Fonts UI for missing fonts, or the Install for all users context menu for fresh .ttf files.6. Comfort Panel Barcode Font Symptom
An independent but related symptom affects Comfort Panels (TP/KP series) when barcode fonts (Code 39, Code 128, DataMatrix, QR) are referenced in the project. The error message observed is:
Unable to Download Barcode Fonts to Comfort Panel.
The barcode font must be installed on the engineering station using the procedure in Section 4.2, and the panel firmware must be capable of rendering the symbology. Verify the panel firmware version against the Siemens Industry Online Support compatibility list. The Comfort Panel firmware must be at least the version that ships with the corresponding TIA Portal version (e.g., V16 Update 3 panels ship with firmware compatible with TIA V16 Update 3). If a mismatched firmware is in service, upgrade the panel firmware through ProSave or TIA Portal's Online → HMI Device Maintenance menu before retrying the font download.
7. Diagnostic Command Reference
Use these commands from an elevated PowerShell window to verify font registration programmatically before re-running TIA Portal:
# List all fonts registered per-machine (HKLM)
Get-ItemProperty 'HKLM:\SOFTWARE\Microsoft\Windows NT\CurrentVersion\Fonts' |
Select-Object -Property PSChildName |
Format-Table -AutoSize
# Confirm a specific font entry exists
$key = 'HKLM:\SOFTWARE\Microsoft\Windows NT\CurrentVersion\Fonts'
Get-ItemProperty -Path $key |
Get-Member -MemberType NoteProperty |
Where-Object { $_.Name -like '*Roboto*' } |
Select-Object Name
# Force font cache rebuild after manual install
$fontCache = "$env:WINDIR\System32\FNTCACHE.DAT"
if (Test-Path $fontCache) { Remove-Item $fontCache -Force }
# Reboot is required for the new cache to take effect.
If Get-ItemProperty returns no row matching the font name, the install is incomplete and TIA Portal will refuse to enable the download checkbox.
8. Troubleshooting Matrix
| Symptom | Likely Cause | Resolution |
|---|---|---|
| Checkbox disabled, font in Control Panel → Fonts | Per-user install only | Right-click → Install for all users |
| Checkbox disabled, font missing from Control Panel → Fonts | Drag-and-drop without registry write, or Win11 upgrade stripped it | Re-run installer as Administrator; verify HKLM key |
Compile error: Font 'X' not found
|
Font referenced in screen object but not in project font list | Add font to Runtime settings → Language & Font |
| Runtime shows boxes/squares instead of glyphs | Download was skipped or panel firmware older than font support | Enable Download font, rebuild, reflash panel firmware |
| Barcode scanner cannot decode printed text | Comfort Panel received substituted font instead of barcode font | Re-install barcode font per Section 4.2; reflash panel |
| Checkbox still disabled after install + reboot | TIA Portal object store cache stale |
Close TIA Portal, delete %USERPROFILE%\AppData\Roaming\Siemens\Automation\ObjectStore\*.cache, relaunch |
9. Best Practices for Multi-Language HMI Projects
-
Centralize font files in a version-controlled engineering share (
\\corp\hmi\fonts\) to prevent per-engineer divergence. - Document the install path in the project functional specification so that any engineer who inherits the workstation can replicate the environment in under 10 minutes.
- Test on a clean Windows 10/11 VM before promoting the project to production to catch missing-font regressions.
-
Avoid variable fonts (
.ttfwith multiple axes). Comfort Panel firmware predating V16 may not parse them; pin to static instances. -
Use the TIA Portal Openness API in build pipelines to assert that
HmiRuntimeSettings.Fontscontains the expected font list before automated deployment. - Enable Download font explicitly in every screen that uses a non-default face. Without this option, the panel substitutes the closest available face at compile time and the project will not reflect the intended typography.
- Re-compile fully after any change to Language & Font; incremental compile does not refresh font metadata.
10. Frequently Asked Questions
Why is the "Download font" checkbox grayed out in TIA Portal V16 Update 3 even though the font is installed?
The font is installed only per-user (drag-and-drop or single-user "Install"). TIA Portal enumerates the per-machine (HKLM) font registry. Right-click the .ttf file and choose Install for all users, then reboot and rebuild the HMI project.
Does upgrading to TIA Portal V17, V18, V19, or V20 fix the font download disabled bug?
No. The grayed-out checkbox is a host-side font registration issue, not a TIA Portal bug. The behavior persists across all TIA Portal versions until the font is properly registered in the HKLM font store on the engineering workstation.
My Windows 10 to Windows 11 upgrade removed Samsung Gulim and other fonts. How do I restore them?
Open Settings → Personalization → Fonts, locate the font under Available fonts, and click Install. For fonts not bundled with Windows (third-party typefaces), re-download the .ttf and use the right-click Install for all users option. Restart TIA Portal and rebuild the HMI project.
How do I deploy barcode fonts (Code 39, Code 128, DataMatrix) to a Comfort Panel?
Install the barcode .ttf on the engineering station with Install for all users, reference it in the screen object, enable Download font under Runtime settings → Language & Font, perform a full rebuild, and ensure the panel firmware version matches the TIA Portal version. The error "Unable to Download Barcode Fonts to Comfort Panel" is resolved by the same per-machine install procedure.
Is a reboot required after installing a font for TIA Portal?
Yes. Per the official Siemens TIA Portal documentation, a full restart of the engineering station is required after installing a font, followed by a restart of TIA Portal and a complete re-compile of the project. Only after these steps can the HMI device be compiled successfully with the new font.