Resolving WinCC RC PO Error Caused by Archive Variable Limit

David Krause11 min read
SiemensTroubleshootingWinCC
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Resolving WinCC RC PO Error Caused by Archive Variable License Exceeded

When a Siemens PCS 7 OS station starts WinCC Runtime, the Data Manager loading phase can abort with a WinCC RC PO Error stating the system detected more tags than the licensed Power Tag count allows. A common misdiagnosis is to assume the Power Tag license is short. In many field cases, the real constraint is the separate archive variable license dimension, which is licensed and counted independently from Power Tags. This article explains the error, the licensing architecture behind it, and the two resolution paths supported by Siemens licensing rules.

1. Problem Description

Environment: PCS 7 V7.0 SP1 with one Engineering Station / OS (ES+OS) and a redundant OS server pair. After adding new I/O, editing CFC charts, and re-compiling the OS project, WinCC Runtime fails to start. The Data Manager reports:

WinCC RC PO Error
Detected tags: 412
Licensed limit: 2000

The operator cannot acknowledge the message, and the message reappears on every Runtime start. The system appears unaffected on the configuration side because the project compiles cleanly. The OS server runs for a few seconds, then the WinCC Explorer closes the Runtime.

1.1 Symptoms Checklist

  • Data Manager stalls during initial load and reports a tag-count mismatch.
  • WinCC Runtime is interrupted within seconds of activation.
  • The error persists after a full OS recompile and download.
  • Recompiling the S7 program has no effect on the Runtime error.
  • Message counter increases at each restart attempt.
Note: The visible tag count (412) in the error text is the actual loaded runtime tag count, not the project power-tag count. Compare the number with Licens_Info.log, not with the WinCC Configuration Studio tag list.

2. WinCC Licensing Architecture

WinCC Runtime licensing is split across multiple independent counters. PCS 7 V7.0 SP1 enforces each counter separately at startup. Understanding the split is essential to reading the error correctly.

WinCC Runtime License Counters (PCS 7 V7.0 SP1)
Counter Meaning Default (no license) Smallest purchased bundle
Power Tags (RC PO) Process variables visible in pictures, scripts, and archives (the source of the tag the operator sees) 128 256 / 512 / 1024 / 2048 / 4096 / 8192 / 16384 / 65536
Archive Variables Tags configured in Tag Logging to be stored in process value archives or alarm archives 512 1500 (5,000 / 10,000 / 25,000 / 50,000 / 100,000 / 150,000 also available)
Screens Process pictures and screen windows 0 (no screens without license) Dependent on picture count
Server / Client OS server vs. OS client (multi-station) and web option Single station only Server, Client, Web Navigator

A project can have 412 Power Tags (well within a 2000-tag RC PO license) and still fail with an RC PO error if the number of archive variables exceeds the limit allowed by the archive counter.

2.1 How Archive Variables Are Counted

An archive variable is created when a tag is referenced in the WinCC Tag Logging editor. Each Tag Logging archive tag occupies one license slot, regardless of whether it is part of a process value archive, a compressed archive, or an alarm archive. The counter is incremented at project compilation and verified at Runtime startup.

3. Root Cause Analysis

The reported error text does not identify the counter that has been exceeded. Siemens stores the actual license diagnostics in Licens_Info.log under the WinCC Diagnose folder.

3.1 Reading the Licens_Info.log

  1. Open C:\Program Files\SIEMENS\WINCC\Diagnose on the OS server.
  2. Locate Licens_Info.log.
  3. Search for the strings PowerTag and Archive:
Number of PowerTags (incl. archive): 412 / licensed: 2000      -> OK
Number of archive variables:        521 / licensed:   512      -> FAIL

If the archive variable line reports a value greater than 512, the Data Manager will refuse to load Runtime and emits the RC PO error. The 412 figure visible in the popup is the total PowerTag count used to compute screen / script visibility; the archive counter is what is failing.

Critical: The default free archive variable allowance is 512, not 2000. The 2000 figure shown in the error belongs to the RC PO (Power Tag) counter, which the project honors. Operators and engineers regularly misread the error as a Power Tag problem because the only count shown on the popup is 412. Always confirm against the log file.

3.2 Why the Error Appears After a Compile

Adding I/O, adding CFCs, or editing existing CFCs forces Tag Logging to recompute the archive membership. When a new tag is added under an existing archive, the archive counter grows by one. Compiling a chart that references a previously unarchived variable can also promote it to an archive tag. Therefore, a clean compile that grows the project by a small number of tags is sufficient to cross the 512 limit.

4. Diagnostic Procedure

  1. Stop WinCC Runtime on the affected OS server.
  2. Open the Windows Event Viewer (eventvwr.msc) and inspect WinCC entries. Look for events with source CCDataMgr and description containing the string PO Error.
  3. Open C:\Program Files\SIEMENS\WINCC\Diagnose\Licens_Info.log in a text editor and confirm the archive variable count.
  4. Open C:\Program Files\SIEMENS\WINCC\Diagnose\WinCC_SysLog.log and search for entries with severity ERROR around the Runtime start time.
  5. Open the WinCC Configuration Studio and navigate to Tag Logging. Expand Archives and note the count of variables per archive. The sum across all archives is the licensing-relevant value.
  6. Compare the count from step 5 with the value reported in Licens_Info.log to confirm there is no stale count in the project database.

5. Resolution Path A: Reduce Archive Variables to 512 or Fewer

If the project does not require a purchased archive license, the supported approach is to bring the archive variable count down to 512 or less. The following steps are performed in the WinCC Configuration Studio of the affected OS server.

5.1 Identify Unused or Redundant Archive Tags

  1. Open Tag Logging in the WinCC Configuration Studio of the OS server.
  2. Sort the tag list by Last Used (right-click column header → Sort).
  3. Tags that have not been archived in the last 30 days are candidates for removal.
  4. For each candidate, open the trend view in Runtime (or in the WinCC online trend control) to verify the tag carries process value information of operational interest.

5.2 Remove Tags From Archives

  1. Right-click the tag in Tag Logging and choose Remove from archive.
  2. Confirm the dialog. The tag remains in the project as a power tag (so pictures, scripts, and alarm routing still work) but is no longer counted as an archive variable.
  3. Repeat for all candidates until the total count of archive variables is ≤ 512.

5.3 Re-Compile the OS

  1. Open WinCC Explorer on the ES.
  2. Right-click the OS server and select Compile OS → Complete compilation.
  3. Download the project to the OS server.
  4. Restart WinCC Runtime and confirm the RC PO error is gone.
Engineering tip: Tags used in @... archive scripts and tags automatically created by PCS 7 APL blocks (for example CTRL_... block archive parameters) count toward the archive variable total. Removing an APL block from the CFC removes its archive tags. Always verify the resulting picture and trend behavior in a test OS before downloading to production.

6. Resolution Path B: Purchase an Archive Variable License

If the operational requirement needs more than 512 archive variables, purchase a WinCC archive license and install it on every Runtime machine (per Siemens license terms).

6.1 License Bundles (PCS 7 V7.0 SP1 Era)

WinCC / PCS 7 Archive Variable License Options
License Article (example) Archive Variables Notes
6AV6371-1DV07-0AX0 1500 Smallest purchased bundle, sufficient for small OS stations.
6AV6371-1DV17-0AX0 5000 Mid-size OS server typical for unit cells.
6AV6371-1DV27-0AX0 10000 Plant-wide OS server.
6AV6371-1DV37-0AX0 50000 Large process value archive plant.

Each Runtime machine requires its own license. In a redundant OS server pair, two licenses are required. Floating license servers (centralized license service) are supported and recommended for multi-station plants.

6.2 Installing the License

  1. Copy the license file (*.zip or *.LIC) to a USB or network share accessible by the OS server.
  2. Run the Automation License Manager on the OS server (Start → Siemens Automation → Automation License Manager).
  3. If the license is a dongle license, install the dongle before launching the Automation License Manager.
  4. Click Edit → Connect Target System, select the local OS server, and confirm the connection.
  5. Drag the new license file onto the target system in the License Manager, or use License → Install to import the file.
  6. Verify the archive variable count row in the Used / Licensed panel shows the new capacity.

6.3 Restart and Verify

  1. Close WinCC Runtime completely on the OS server.
  2. Re-start WinCC Runtime. The Data Manager should now load the full archive set without an RC PO error.
  3. Confirm with Licens_Info.log that the archive counter is satisfied (the log entry will read OK).

7. Verification

Post-Resolution Verification Checklist
Check Expected Result Method
WinCC Runtime starts Data Manager completes load, Runtime enters main screen OS server console / WinCC Explorer
No RC PO popup No archive- or power-tag-related system message WinCC message list filter on system messages
Licens_Info.log — PowerTag Number of tags used ≤ licensed Inspect log
Licens_Info.log — Archive Number of archive variables ≤ licensed (either 512 or purchased bundle) Inspect log
Trend display Curves render for all configured archive tags Open a WinCC Online Trend Control on the OS client
Event log No PO Error events after restart Windows Event Viewer → WinCC source

8. Preventive Measures

  • Use a project-wide Tag Logging review at every major CFC release. The WinCC Configuration Studio provides an Archive Statistics report that lists tag counts per archive.
  • Maintain a delta log when adding I/O. Each new S7 tag added to a CFC chart may add a Tag Logging entry automatically if the chart uses standard PCS 7 archive blocks.
  • Apply archive tag housekeeping before reaching the 80% threshold of the current license (for example, stop at ~400 tags on a 512 free counter).
  • Use the Automation License Manager centrally and document the licensed limits in the project quality plan.
  • Consider splitting long-term process values into a separate process historian (for example, PCS 7 Information Server) so the WinCC OS station archive remains within license limits.

9. Edge Cases and Related Errors

Related WinCC Startup Errors and How to Distinguish Them
Symptom Likely Cause Diagnostic File Action
RC PO error with archive count > 512 Archive license exceeded Licens_Info.log Reduce archive variables or buy license
RC PO error with power-tag count > licensed Power Tag license exceeded Licens_Info.log Buy larger PowerTag bundle or remove tags
Connection lost to server, repeated reconnect attempts OS server OS client connection issue WinCC_SysLog.log Check network, SIMATIC shell, and project redirection. See Reaction to system errors (RT Professional) for client behavior
Tag Logging does not start, no archive licenses in log Tag Logging service not running Windows services Restart CCArchiveServer service
Trend values missing after restart, but no RC PO error Archive segments on disk full or path unreachable WinCC_SysLog.log — DISK_FULL messages Free disk, adjust archive path or backup cycle

The reference link to Reaction to system errors (RT Professional) documents the WinCC client behavior when the server is unreachable. While the link targets WinCC RT Professional in TIA Portal V20, the underlying system-error handling and reconnection model apply analogously to PCS 7 V7 WinCC Runtime.

10. Field Notes for PCS 7 V7.0 SP1

  • PCS 7 V7.0 SP1 is part of the legacy SIMATIC PCS 7 line. The licensing model is shared with the WinCC V7.x family, so the 512-archive default and 1500-archive smallest bundle apply.
  • Migration to PCS 7 V8.x or V9.x preserves the existing archive variable count and license files. Customers adding a large I/O scope often use the migration window to consolidate or split archive sets.
  • Customer-specific archive tags (created with User Archive tables or CSV export scripts) do not count toward the 512-archive variable limit. They count toward the User Archive table license, which is a separate counter.
  • APL block self-archiving: starting with PCS 7 V8, several APL block types can be configured to disable automatic archive generation, which is the recommended pattern for keeping archive count down.

11. FAQ

Why does the RC PO error show 412 tags with a 2000 limit if my archive license is the problem?

The 412 / 2000 figures belong to the Power Tag (RC PO) counter, which the project honors. The error is triggered by the separate archive variable counter, which defaults to 512 free archive variables. Confirm the actual failing counter in C:\Program Files\SIEMENS\WINCC\Diagnose\Licens_Info.log.

How many archive variables do I get for free in WinCC V7 / PCS 7 V7.0 SP1?

512 archive variables per Runtime station. Adding a single archive tag automatically (for example, by enabling a PCS 7 APL block archive parameter) can push you over the limit and stop WinCC Runtime from starting.

What is the smallest archive variable license I can buy?

The smallest bundle is 1500 archive variables, sold under article 6AV6371-1DV07-0AX0 for the WinCC V7 era. Larger bundles (5,000 / 10,000 / 50,000) are also available. Each Runtime machine, including a redundant server pair, requires its own license.

Will removing a tag from Tag Logging delete its historical data?

Yes. The archive segment is removed and the historical values are deleted. To preserve history, export the segment to CSV (or migrate to PCS 7 Information Server) before removing the tag.

Do I need to recompile the OS after removing archive tags?

Yes. Recompile the OS server (right-click → Compile OS → Complete compilation) and download the project, then restart WinCC Runtime. The new archive count is enforced at the next Data Manager load.

Back to blog