Siemens LOGO! Network Input and Output Configuration Guide
Siemens LOGO! 8 logic modules (6ED1052-xxxx-xBAx family) expose a feature that the older LOGO! generations did not: network inputs (NI) and network outputs (NO) carried over the on-board Ethernet port. NI/NO blocks let a local program read a digital state from a remote LOGO! or expose a local digital state to a remote LOGO! without writing S7 code, sending e-mails, or building a remote I/O island. The result is a flat, peer-to-peer shared I/O image across every LOGO! on the same IP subnet.
This reference walks through the exact configuration flow used to map I1 on LOGO! 1 (IP 192.168.0.2) to output Q1 on LOGO! 2 (IP 192.168.0.3), including the version-specific menu path inside LOGO!Soft Comfort V8.x, the project transfer checklist, and the field-proven troubleshooting matrix that resolves the "simulation works, hardware does not" or "symbol shows but Q1 does not change" symptoms that surface in most commissioning calls.
...-0BA8) and the LOGO! CMR2020/CMR2040 communication modules. If you are still running LOGO! 6 (0BA6) or LOGO! 7 (0BA7) base modules, network I/O is limited or unavailable; check the device revision with LOGO! > Diagnostics > IP Address on the on-board display before you start.1. Network I/O Concept on LOGO! 8
LOGO! 8 ships with an on-board Ethernet interface (192.168.0.0/24 default) that supports up to 16 S7 connections. A subset of those connections is reserved for the LOGO!-to-LOGO! shared I/O mechanism. From a programmer's view:
- A Network Input (NI) block is a Boolean tag inside the local program whose value is read from a remote LOGO!'s digital output, marker, or network output.
- A Network Output (NO) block is a Boolean tag that the local LOGO! broadcasts to any peer that has mapped a corresponding NI to it.
- The transport is Siemens S7 communication over TCP/UDP port 102. No router, NAT, or VPN is involved; both peers must be reachable on the same Layer 2 broadcast domain.
The capacity limits (per the LOGO! 8 System Manual, 06/2021 edition, section 4.4) are:
| Parameter | LOGO! 8 (0BA8) | Notes |
|---|---|---|
| Network inputs per device | up to 64 (NI1..NI64) | Counted per receiving LOGO! |
| Network outputs per device | up to 64 (NO1..NO64) | Counted per publishing LOGO! |
| Peers per device | up to 8 LOGO! peers | BM (base module) only; CMR counts separately |
| Update cycle | 100 ms typical, 200 ms worst case | Deterministic, not synchronized |
| Transport | S7 protocol, port 102 | Same subnet only |
| Maximum payload | 1 bit per NI/NO | Analog NAI/NAQ also available (16/32-bit) |
Network I/O is fully bidirectional, so a single peer relationship can carry many NI/NO pairs. Each NI/NO is identified in the project by a 1-based index (NI1..NI64) and bound to a peer's IP plus a source/target tag.
2. Prerequisites
Before you open LOGO!Soft Comfort, confirm the following are in place. Skipping any of these is the single most common cause of "the block is red, value stays 0" during simulation.
2.1 Hardware
- Two or more LOGO! 8 base modules, each with firmware
FS:04(or laterFS:05). OlderFS:01-FS:03firmware has NI/NO bugs that were corrected in FS04; check with the on-board menu LOGO! > Diagnostics > FW Version. - Standard Cat5e/Cat6 Ethernet cabling to a common switch or direct crossover (modern NICs auto-MDIX; crossover is not strictly required).
- 24 V DC power supply sized for the LOGO! current draw (base module 12 V/24 V variants draw 1.2-2.4 W; see the rating plate).
2.2 Software
-
LOGO!Soft Comfort V8.3 (or later) installed on the engineering PC. The project file extension is
.lsc; V8.x projects are forward-compatible with newer V8 releases, but never save a newer-version project as an older version. - Ethernet access from the PC to both LOGO! base modules. A
ping 192.168.0.2andping 192.168.0.3must succeed before you start configuration.
2.3 IP Addressing Plan
By default, every LOGO! 8 ships with IP 192.168.0.2. The first device on the network keeps the default; every additional device must be re-addressed to avoid an IP collision. A four-device example:
| Device | Role | Default IP | Assigned IP | Subnet |
|---|---|---|---|---|
| LOGO! 1 | Publisher (owns I1) | 192.168.0.2 | 192.168.0.2 | 255.255.255.0 |
| LOGO! 2 | Subscriber (owns Q1) | 192.168.0.2 | 192.168.0.3 | 255.255.255.0 |
| LOGO! 3 | Subscriber (optional) | 192.168.0.2 | 192.168.0.4 | 255.255.255.0 |
| LOGO! 4 | Subscriber (optional) | 192.168.0.2 | 192.168.0.5 | 255.255.255.0 |
3. Project Setup in LOGO!Soft Comfort
- Launch LOGO!Soft Comfort V8.3 and choose File > New. Select LOGO! 8 (0BA8) as the target device in the project tree.
- Open Tools > Options > Ethernet Connections and add both peer IP addresses. The dialog caches the addresses used by the NI/NO configuration wizard.
- Save the empty project as
net_io_demo.lscon a local drive (network shares can break the license check on older V8 builds).
4. Configuring the Network Output (Publisher Side)
The publishing LOGO! is the device that owns the physical input you want to share. In the example, LOGO! 1 at 192.168.0.2 owns I1 and must publish it as a network output.
4.1 Insert the NO Block
- In the programming window, drag a Network Output (NO) block from the special-function palette onto a free rung. (Shortcut: type
NOin the search box.) - Wire the block's input to a marker that mirrors
I1. The simplest implementation is a direct assignment using a digital flag:\li>
Network 1:
I1 ----[ NO1 ]---- (output side unconnected)
| ^
| |
+-- B001 (feedback marker, optional)
- Double-click the NO block to open the property dialog. Confirm:\li>
| Property | Setting | Notes |
|---|---|---|
| Block number | NO1 | First free index |
| Comment | "I1 published to peers" | Optional but recommended |
| Retentivity | / | Not applicable to NI/NO |
| Source signal | Boolean from I1 | Drives the published value |
4.2 Declare the Peer in the NI/NQ Table
LOGO!Soft Comfort maintains a separate table that binds NO/NI blocks to peer IP addresses. Open it from Tools > NI/NQ Configuration (in some V8.x builds the menu label is Network Project > NI/NQ Table):
- Click Add Peer and enter
192.168.0.3(LOGO! 2's IP). - Under Local NO, select NO1. The Remote NI field on the peer side is informational only; the remote project is configured independently.
- Click Apply. The peer line turns green if the destination IP is reachable from the engineering PC.
5. Configuring the Network Input (Subscriber Side)
The subscribing LOGO! is the device that should react to the published value. In the example, LOGO! 2 at 192.168.0.3 must turn on Q1 whenever the peer's I1 is high.
5.1 Insert the NI Block
- Open the project for LOGO! 2 (or, in a multi-device project, switch the active target in the project tree).
- Drag a Network Input (NI) block onto the rung that drives
Q1:
Network 1 (LOGO! 2):
NI1 ----( Q1 )
- Double-click NI1. In the property dialog, fill in:
| Property | Setting | Notes |
|---|---|---|
| Block number | NI1 | Subscriber-side index |
| Source IP | 192.168.0.2 | LOGO! 1, the publisher |
| Source tag | NO1 | Must match the publisher's NO index |
| Update supervision | Enabled (default) | Drives Q1 to 0 if the link drops |
| Comment | "Q1 follows LOGO!1:I1" | Optional |
5.2 Save and Compile
- Press F5 or use File > Compile > Compile All to rebuild the project. Any unresolved NI/NO references show in the message window as warnings (yellow) or errors (red).
- Confirm that the message window reports
0 errors, 0 warnings. If you see "Reference to undefined NI/NO index", reopen the NI/NQ table and verify the index numbers match on both sides.
6. Transfer and Commissioning
- Connect the PC to the switch that fans out to both LOGO!s. Verify reachability with
ping 192.168.0.2andping 192.168.0.3. - Power on LOGO! 1 and LOGO! 2. Wait until the on-board display shows LOGO! ready (no Ethernet icon flashing red).
- In LOGO!Soft Comfort, select Tools > Transfer > Transfer to Device. The dialog lists every reachable LOGO!; choose the device that matches the project (verify the serial number, not just the IP).
- Repeat the transfer for the second project on the second LOGO!.
- Switch both devices to RUN. The status bar should show Online: connected and the Ethernet icon on the on-board display should be solid green.
7. Verification
Three independent checks should pass before you sign off the system.
7.1 Online Monitor
Select Window > Online Monitor in LOGO!Soft Comfort. The NI1 block on the subscriber should track the NO1 block on the publisher with a latency between 80 ms and 200 ms. If the trace is flat, jump to the troubleshooting matrix below.
7.2 Physical Output Toggle
Force I1 on LOGO! 1 with a wire link (24 V on terminal I1) and measure Q1 on LOGO! 2 with a multimeter. The relay contact (or transistor output, depending on the LOGO! variant) should close within 200 ms.
7.3 LED Indicators
LOGO! 8 base modules with Ethernet have a dedicated LINK LED per port. Steady green = link up; flashing green = traffic. Steady off = cabling or IP mismatch. The RUN/STOP LED flashing red at 1 Hz means the program is in STOP due to a fault; flashing red at 2 Hz indicates a missing or unreadable micro SD card.
8. Troubleshooting Matrix
The following table maps the most common field complaints to root causes and corrective actions, drawn from the LOGO! System Manual and observed support cases.
| Symptom | Likely Root Cause | Corrective Action |
|---|---|---|
| NI1 stays 0; Online Monitor shows "not connected" | Source IP in NI block does not match publisher IP | Open NI block properties, re-enter 192.168.0.2, recompile, retransfer |
| NI1 stays 0; Online Monitor shows green | Source tag is wrong (e.g., NO2 vs NO1) | Verify publisher's NO index; on the subscriber, set Source tag = NO1 |
| Simulation works, real hardware does not | Project not transferred or in STOP on one side | Re-transfer to both LOGO!s; confirm RUN state on both displays |
| Q1 chatters at ~1 Hz | Update supervision toggles the output on link flaps | Replace cable, check switch port, disable supervision only if fail-safe is handled elsewhere |
| LOGO!Soft Comfort cannot find a device | Windows firewall blocks UDP discovery (port 50005/50006) | Add LOGO!Soft Comfort to the firewall exception list, or enter the IP manually in Tools > Options > Ethernet |
| Compile error: "NI/NO index out of range" | Project targets LOGO! 6/7 device family | Change target device to LOGO! 8 in the project tree |
| Behaviour correct for 30 s, then Q1 drops | Watchdog timer on LOGO! 1 hits because of an I/O scan stall | Check for runaway counters; reduce program complexity or split across two devices |
| NI block appears red in the diagram | NI/NQ table not saved before transfer | Open Tools > NI/NQ Configuration, click Apply, save the project, retransfer |
9. Analog Network I/O (NAI/NAQ)
LOGO!Soft Comfort V8.2 and later also support Network Analog Input (NAI) and Network Analog Output (NAQ) blocks. They share the same NI/NQ table but carry 16-bit or 32-bit integer payloads. Use NAI/NAQ for sharing analog inputs (e.g., AI1 temperature on LOGO! 1) across the same Ethernet. The configuration flow is identical to digital NI/NO except that the block carries a numeric value; the receive side scales the value with the same gain/offset used on the publish side. See the LOGO! 8 System Manual, section 4.4.3.
10. Security and Network Hardening
LOGO! 8 ships with no password protection enabled by default. For industrial deployments, configure the following before the system leaves the commissioning site:
- Program access password. Tools > Options > Password. Set a non-trivial password to prevent upload of the LSC project.
- Network separation. Place the LOGO! subnet on a dedicated VLAN with no path to the corporate network. NI/NO traffic is unauthenticated.
- Disable unused services. On the on-board menu (LOGO! > Network > Services), disable the FTP server and Web server unless they are required for the application.
- Firmware updates. Periodically check the Siemens Industry Online Support portal for the latest LOGO! 8 firmware (currently FS05 as of the FS05 release note). Apply via micro SD card to avoid the network outage that the online update can cause.
11. Limits and Migration Notes
When you design a system that depends on network I/O, account for the following constraints, all of which are documented in the LOGO! 8 System Manual:
- Up to 8 LOGO! peers can be addressed by a single LOGO! base module. Exceeding this requires a CMR2020/CMR2040 router that adds its own peer slots.
- Total NI + NAI + NAI-word blocks cannot exceed the available program memory. The 0BA8 base module offers 8500 function-block words; NI/NO blocks consume one word each.
- Network I/O does not survive a power cycle in volatile mode. If the application requires the last published value to be restored after a brown-out, store the value in a retentive marker and re-publish it on the first RUN cycle.
- Mixing LOGO! generations is not supported. A LOGO! 8 cannot read NI/NO from a LOGO! 7 or 6 base module.
12. Frequently Asked Questions
How many network inputs and outputs does a LOGO! 8 support?
Each LOGO! 8 (0BA8) base module supports up to 64 digital network inputs (NI1..NI64) and 64 digital network outputs (NO1..NO64), with up to 8 peer LOGO! modules. Analog network I/O (NAI/NAQ) shares the same table but carries 16- or 32-bit integer payloads.
Why does the simulation work but the real hardware does not switch Q1?
Most often the project was not transferred to one of the LOGO! devices, or one device is in STOP mode. Re-transfer both projects with LOGO!Soft Comfort V8.3, confirm the Ethernet icon is solid green on both displays, and re-test with the Online Monitor active.
What is the update time for a LOGO! network input?
The cyclic S7 update on the on-board Ethernet port is 100 ms typical and 200 ms worst case, depending on network load and the number of active peers. Use NI/NO for non-time-critical interlocking; use the LOGO! CMK2000 communication module or hard wiring for sub-50 ms response.
Can I share an NI value across a router or across VLANs?
No. LOGO! 8 network I/O uses S7 communication on TCP/UDP port 102 without routing, NAT, or VLAN tagging. Both peers must be on the same IP subnet and the same Layer 2 broadcast domain. For multi-site systems, deploy a LOGO! CMR2020 or CMR2040 cellular router and treat each site as an independent NI/NO island.
Does LOGO! 8 firmware version affect NI/NO behaviour?
Yes. Firmware FS:01 to FS:03 (early 0BA8 builds) had several NI/NO bugs that were corrected in FS:04 and refined in FS:05. Always run the latest released firmware for production systems; check the device FW version via LOGO! > Diagnostics > FW Version on the on-board display, and apply updates via micro SD card.