Problem Overview
The SINUMERIK 840D MMC103 (Man-Machine Communication) panel has historically been shipped with two distinct backup pathways: the legacy VALITEK cassette streamer used with early MMC100/MMC102/MMC103 units running Windows 3.11, and the GHOST disk-imaging workflow used from SW 3.x onward. When a service organization must restore a VALITEK-only archive onto a replacement HDD, the restoration typically fails with error patterns that are not seen on the newer PCU50 GHOST-based hardware. Field reports collected across multiple service organizations describe the same envelope of symptoms:
- The replacement HDD is recognized at BIOS POST, but the SINUMERIK runtime starts only after a long delay and the machine window fails to initialize.
- Regie/main window reports
ERROR: Device unavailableshortly after SINUMERIK starts loading. - Before SINUMERIK reaches its main window, the panel posts
Corrupt Swap File Warning (Virtual memory). - The Regie window logs
WARNING Application 'param' didn't post InitComplete !and the HMI stops responding. - User screens cannot be opened; navigation back to the operator area returns a fault dialog, even when the user folders
DH,N840D,NOVAare present atC:\840D-System. - The same
.ghoimage boots cleanly on a desktop PC running Windows XP, demonstrating that the archive itself is intact.
The combination of "clean on PC, broken on MMC" plus "all HDD candidates behave identically" rules out bad media and isolates the fault to the MMC103 hardware or its commissioning sequence. This article documents root causes, the step-by-step recovery procedure, and the verification checks compiled from the Siemens support database and practitioner field notes.
Affected Hardware and Software Stack
| Component | Order Number (MLFB) | Notes |
|---|---|---|
| MMC103, VALITEK variant | 6FC5210-0DA20-1AA0 | Original VALITEK support; runs Windows 3.11 with FAT16. |
| MMC103, VALITEK variant | 6FC5210-0DA20-1AA1 | Earlier production variant; mirror of -1AA0. |
| MMC103, VALITEK variant | 6FC5210-0DA20-2AA1 | Hardware revision with extended firmware. |
| MMC103, GHOST variant | 6FC5210-0DA21-2AA1 | GHOST-supported replacement; cannot read VALITEK tapes. |
| MMC103, latest revision | 6FC5210-0DB21-3AA1 | Newest variant; confirm VALITEK support with Siemens before ordering for legacy machines. |
| Siemens Spare HDD MMC103 | 6FC5247-0AA36-0AA1 | HDD with mounting plate and damper; preconfigured to match the ordered MMC variant. |
The MLFB suffixes -1AA0, -1AA1, -2AA1, -3AA1 denote progressive hardware revisions. Only revisions explicitly carrying VALITEK support can read VALITEK cassettes; later -DA21/-DB21 units in field stock sometimes arrive with GHOST-only firmware even when ordered as the VALITEK variant. Always confirm the suffix matches the suffix of the donor unit before commissioning.
| Software Stack | Version | Notes |
|---|---|---|
| SINUMERIK system software | 03.06.10 | Standard version on VALITEK MMC103; FM-NC/810D/840D. |
| SINUMERIK system software | 03.07.10 | SW 3.7 line; verify VALITEK loader is present. |
| Embedded OS | Windows 3.11 | FAT16 primary + one logical partition; 2 GB HDD typical. |
| Backup medium | VALITEK cassette tape | Tape backup life is short (a few years); verify before relying on archive. |
| Backup medium | GHOST image (.gho) |
Created from donor HDD via 2.5" IDE-USB bridge. |
| Imaging host OS | Windows XP SP3 | Hiren's Boot CD + Norton Ghost 32 verified combination. |
Root Cause Analysis
Four independent root causes have been reproducibly identified when a VALITEK-era MMC103 fails to boot from a fresh HDD:
| # | Root Cause | Symptom | Resolution Path |
|---|---|---|---|
| 1 | MMC103 BIOS set to MANUAL MODE; new HDD geometry not in the saved entry. | HDD detected at POST; SINUMERIK runtime fails to mount partitions or reports Device unavailable. |
Enter BIOS setup, switch HDD detection from MANUAL to AUTO, save and exit. |
| 2 | Image written via Windows XP IDE-USB bridge modified the MBR/boot sector or assigned a different drive letter. | Image boots on desktop PC but MMC103 firmware cannot locate the active partition. | Re-restore using Ghost in pure DOS environment with native IDE controller, or use Siemens DD disk pre-formatted for VALITEK MBR. |
| 3 | MPI/PROFIBUS disconnected during bench test; NCK link never established. | User screens report 'param' didn't post InitComplete and the operator dialogue fails. |
Connect MPI/PROFIBUS cable and power the NCU before powering the MMC. |
| 4 | User folders (DH, N840D, NOVA) copied without their registry references; SINUMERIK does not register the screens. |
User-area menu items appear but navigation produces a fault dialog. | Use the machine builder's commissioning tool (840D-System\setup.exe or equivalent regie.exe /install) instead of copy-paste. |
The official Siemens KB article "SINUMERIK 840D MMC103: A replacement hard disk is not recognized" identifies root cause #1 specifically and prescribes the BIOS remedy documented in this article. See the citation at the end of the recovery procedure.
Pre-Recovery Inspection
Before commissioning any spare HDD on a VALITEK-era MMC103, perform the following inspections. Skipping any of these will reintroduce the same fault mode after the next power cycle.
- Confirm the MLFB of the donor MMC103. The -AA0/-AA1/-AA2/-AA2/-BA2 suffixes differ in firmware and supported backup medium. Cross-check the MLFB plate on the rear of the unit.
- Verify the spare HDD matches the variant. A 6FC5247-0AA36-0AA1 spare HDD ordered from Siemens will match the variant declared at order entry. If a third-party 2.5" IDE HDD is used, capacity must remain within the original 2 GB / 10 GB / 20 GB / 30 GB window that the firmware expects; newer 80 GB+ drives are unsupported on MMC103 firmware.
- Open the cabinet, confirm the IDE cable is 44-pin 2.5" type and the jumper on the HDD is set to
Master. The MMC103 hosts no slave device. - Inspect the dampers. The MMC103 spare HDD ships with rubber dampers (P/N included with 6FC5247-0AA36-0AA1) that absorb spindle vibration; without them, repeated read errors surface as
Device unavailableafter 30-60 minutes. - Power the MMC103 once with the spare HDD attached and note the BIOS string. If the BIOS reports
HDD type: USERorHDD type: MANUAL, the BIOS is in the failure mode described in the Siemens KB.
HDD Selection and Validation
Field experience shows that VALITEK-era MMC103 firmware accepts only a narrow range of IDE HDDs. Use the following accepted candidates:
| Capacity | Verified Model | Notes |
|---|---|---|
| 2 GB | IBM Travelstar 2.5" | Original equipment on -AA0 boards. |
| 10 GB | Hitachi DK239A-10 | Common donor image source. |
| 20 GB | Toshiba MK2018GAP | Spare approved for -BA2 boards. |
| 30 GB | Fujitsu MHS2030AT | Largest size accepted; do not exceed. |
| Siemens preconfigured | 6FC5247-0AA36-0AA1 | Recommended spare; delivered with mounting plate and damper. |
Step-by-Step Recovery Procedure
- Power down the MMC103 and disconnect the mains. Remove the four screws holding the front bezel and slide the HDD carrier out.
- Connect the donor 2.5" IDE HDD to a workshop PC using a 44-pin IDE-USB adapter set to
Master. Set the donor's jumper toMaster; never useCable Selecton the MMC103 carrier. - Boot the workshop PC from Hiren's Boot CD (Windows XP PE) and verify the donor HDD appears as a fixed disk under Disk Management. Note the drive letter; do not use it as a bootable system drive.
- Launch Norton Ghost 32 from the Hiren's menu. Choose
Local > Disk > To Imageand select the donor HDD. Save the image to a network share asmmc103_donor_YYYYMMDD.gho. - Attach the target (replacement) HDD to the workshop PC on the second channel of the IDE-USB bridge or via a second adapter. Initialize the disk using
diskpartand create the same primary FAT16 partition plus one extended/logical partition layout as the donor, sized to the capacity of the target HDD. - In Ghost, choose
Local > Disk > From Imageand restore the donor image to the target HDD. Allow Ghost to resize the partitions if the target is larger; never shrink a 30 GB image onto a 2 GB disk. - Disconnect the target HDD from the workshop PC. Reinstall it into the MMC103 carrier with the dampers and mounting plate; verify the IDE connector is fully seated.
- Power up the MMC103. Press
DEL(or the BIOS hotkey shown on POST) to enter the BIOS setup utility. - Navigate to
Standard CMOS Features > Primary IDE Master. Confirm the setting isAUTO. If the field readsUSERorMANUAL, change it toAUTO, save (typicallyF10) and exit. The BIOS will redetect the target HDD geometry on the next POST. - Reboot. The SINUMERIK runtime should now mount the FAT16 partitions and proceed to the operator window.
- Connect the MPI/PROFIBUS cable between the MMC103 and the NCU before applying mains to the NCU. Power the NCU; verify the NCK link is established on the HMI diagnostic page.
- Reinstall the machine builder's user folders (
DH,N840D,NOVA) using the builder's commissioning tool, not by manual copy. Restart the HMI service.
Recovery Flow
Specific Error Resolutions
2.1 BIOS Reports HDD type: MANUAL or USER
This is the documented Siemens failure mode. Even when the spare HDD is electrically healthy and recognized at POST, a BIOS stored in MANUAL mode means the firmware enumerates the disk using the geometry table from the original donor—geometry that no longer matches the spare. Result: the boot sector is read but the FAT16 partition table cannot be located, and SINUMERIK silently abandons startup. Per the Siemens KB article "SINUMERIK 840D MMC103: A replacement hard disk is not recognized", the remediation is to set the BIOS drive type to AUTO and rescan. See Siemens Support Entry 32985711 for the canonical description.
2.2 Corrupt Swap File Warning (Virtual memory)
This warning is posted when the SINUMERIK runtime attempts to enable the Windows 3.11 swap file at C:\WIN311\386SPART.PAR but the partition's free space is below the configured swap size. The warning is not a disk fault—it is a sizing fault. The Ghost image is restored with the swap file configured for the donor's geometry; when the partitions are resized for the spare, the swap-file size is preserved but the available space shrinks. Resolution:
- Boot the MMC103 to the operator window despite the warning.
- Open
Regie > Setup > HMI > Memory. - Reduce
Permanent Swap Fileto a value equal to or less than the smallest free partition. - Reboot. The warning will not appear if the swap file fits.
2.3 ERROR: Device unavailable
This is the generic failure when SINUMERIK cannot establish the NCK link. On a freshly restored MMC103 it almost always indicates that the MPI/PROFIBUS cable is not connected or that the NCU is unpowered. The runtime proceeds far enough to enumerate drives then blocks on the NCK handshake. Connect the MPI cable, apply mains to the NCU, restart the HMI service.
2.4 WARNING Application 'param' didn't post InitComplete !
The param application is the SINUMERIK parameter handler. It waits on the NCK to publish its configuration before it can finish its initialization handshake. If MPI/PROFIBUS is missing, param never receives InitComplete and the warning is logged. With the NCK link restored, the warning clears on the next HMI restart.
2.5 User Screen Fault Dialog
When the user folders are copied manually to C:\840D-System without registering them, the operator menu lists the screens but the registry keys in HKEY_LOCAL_MACHINE\SOFTWARE\SINUMERIK\UserData point to the old path. Two remediation paths exist:
- Restore the registry hive from the machine builder's commissioning backup.
- Reinstall the user folders using the builder's
setup.exewith the original installation media; this regenerates the registry entries.
Do not use Windows Explorer to copy user folders; the SINUMERIK installer is the only supported deployment path.
MPI/PROFIBUS Re-Commissioning
The most common oversight on the bench is to power the MMC103 alone without the NCU. The Regie window will appear, but every NCK-dependent service will fail. Before fault-tracing user-screen failures, confirm the following:
- PROFIBUS connectors at the MMC103 (X101) and the NCU (X126) are latched.
- Terminating resistors at both ends of the PROFIBUS segment are in the
ONposition. - The MPI/PROFIBUS baud rate on the MMC103 (default 1.5 Mbit/s) matches the NCU configuration.
- The NCU reports
COMM OKon its seven-segment display prior to MMC boot.
Once the MPI/PROFIBUS link is established and the user folders are properly registered, user screens load on demand and the operator dialogue resumes without fault dialogs.
Software Stack Validation
| Check | Expected | How to Verify |
|---|---|---|
| System version | 03.06.10 or 03.07.10 | Regie > Commissioning > System Info |
| HMI version | Matches system version | Regie > Help > About HMI |
| NCK version | Build matched at machine commissioning | Regie > Commissioning > NCK Version |
| Drive version | Simodrive 611D or Sinamics S120 per machine | Regie > Commissioning > Drives |
| PLC version | Simatic S7-300 with FM-NC/810D/840D firmware | Regie > Commissioning > PLC |
| VALITEK loader | Present in C:\Tools\Valitek
|
Explorer > C:\Tools > Valitek |
If the HMI reports a system version older than the spare HDD's image, the loader will refuse to register; this is one of the documented causes of the param initialization warning when the spare HDD ships with a newer SW build than the rest of the controller stack.
Verification Procedure
- Power up the NCU, then the MMC103. Verify POST completes and BIOS reports
AUTOdrive detection. - Confirm the SINUMERIK main window loads without
Corrupt Swap FileorDevice unavailableerrors within 90 seconds. - Open Regie and verify
System Infodisplays the expected SW 3.6 / SW 3.7 build, not a partial string. - Navigate to the operator area; select each user screen and confirm the screen renders without fault dialog.
- Trigger an axis jog from the HMI and observe the NCK response on the drive trace. If the axis responds within 200 ms, the MPI/PROFIBUS handshake is healthy.
- Cycle mains and re-boot; the panel must reach the operator window within 90 seconds on cold start.
Device unavailable within months.Spare HDD Sourcing Notes
Siemens currently supplies the MMC103 spare HDD under MLFB 6FC5247-0AA36-0AA1. When ordering:
- Quote the original MLFB of the donor MMC103 alongside the spare HDD order; Siemens will pre-configure the firmware loader to match.
- If the donor is
-DA21-2AA1or-DB21-3AA1, request a GHOST-formatted spare; the VALITEK tapes will not load on these variants. - If the donor is
-DA20-xAA1, request a VALITEK-formatted spare and the supporting cassette drive if it is no longer on-site. - Always order two spare dampers; the rubber loses elasticity after 10+ years and must be replaced when the HDD is changed.
The Siemens KB entry "SINUMERIK 840D MMC103: A replacement hard disk is not recognized" (Siemens Support Entry 32985711) remains the canonical reference for the BIOS detection issue and is the source of the procedure documented in this article. For general HDD diagnostic methodology, see the Microsoft Learn reference Internal HDD troubleshooting on Microsoft Q&A.
Frequently Asked Questions
Why does the same Ghost image boot on a desktop PC but fail on the MMC103?
The Windows XP IDE-USB bridge writes a generic MBR and assigns drive letters based on the workshop PC's controller, both of which are compatible with Windows XP. The MMC103 firmware expects the original MBR signature and a fixed drive geometry; a clean PC boot proves the image is intact, while the MMC103 failure points to a BIOS/geometry mismatch on the MMC side rather than a bad image.
What is the correct Siemens order number for a VALITEK-supported spare HDD on an MMC103?
Order MLFB 6FC5247-0AA36-0AA1. When ordering, also quote the original MMC103 MLFB so Siemens pre-loads the matching firmware and confirms VALITEK support; substitute models 6FC5210-0DA21-2AA1 and 6FC5210-0DB21-3AA1 are GHOST-only and will not read legacy VALITEK tapes.
How do I clear Corrupt Swap File Warning (Virtual memory) after restoring a Ghost image?
Open Regie > Setup > HMI > Memory and reduce the Permanent Swap File size to a value no greater than the smallest free FAT16 partition. Restart the HMI. The warning is sizing-driven, not disk-driven, and clears once the swap file fits the partition.
Do I need MPI/PROFIBUS connected during bench testing of the restored MMC103?
Yes. The param application waits on the NCK link before posting InitComplete; if the cable is disconnected the runtime logs WARNING Application 'param' didn't post InitComplete ! and user screens refuse to load. Connect the MPI/PROFIBUS cable, terminate both ends, and power the NCU before the MMC103.
What is the maximum HDD capacity the MMC103 will accept?
30 GB. Drives of 80 GB or larger trigger a CHS translation overflow in the MMC103 BIOS, which silently skips the boot partition. Approved donors are 2 GB, 10 GB, 20 GB, and 30 GB only; the Siemens spare 6FC5247-0AA36-0AA1 is shipped in the matching size for the ordered firmware.