YRC1000 Profinet to EtherNet/IP Conversion: Configuration Guide

Daniel Price11 min read
Industrial NetworkingTutorial / How-toYaskawa
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Overview

The Yaskawa YRC1000 Micro controller supports multiple industrial Ethernet protocols on the same hardware platform, but the active industrial network must be declared in the controller's management-mode configuration before any data exchange will occur. Migrating a cell from PROFINET (typically paired with a Siemens S7-1500/S7-1200 PLC) to EtherNet/IP (typically paired with an Allen-Bradley CompactLogix or ControlLogix PLC) is a common North-American retrofit. The migration is primarily a configuration exercise on the robot side, not a hardware swap, provided the correct option board is installed in the YRC1000.

This reference covers the recommended sequence for a field retrofit, the controller-mode procedure that declares the new protocol, the I/O mapping practices that prevent the "weird I/O" behavior reported by integrators, and the verification steps required to bring the new scanner-to-adapter handshake up cleanly.

Critical: Always back up all job files, parameter files, ladder files, and the controller configuration to an offline location before changing the active communication protocol. A corrupted configuration can force a full controller re-image.

Prerequisites

Item Specification
Controller Yaskawa YRC1000 Micro (FS100 firmware lineage compatible)
EtherNet/IP option board Yaskawa-installed EtherNet/IP scanner adapter (board declared via management mode)
Pendant YPP (Yaskawa Pendent Programming) with management-mode access enabled
Engineering PC Yaskawa MotoCom32 or current Yaskawa controller programming software, plus RSLogix 5000 / Studio 5000 for the new scanner
Ethernet infrastructure Managed switch supporting IGMP snooping (DLR ring optional) and QoS for CIP Motion traffic
Documentation Snapshot of existing PROFINET slot mapping, GSD file version, and PROFINET device name

Architecture Background: PROFINET vs. EtherNet/IP on the YRC1000

Both PROFINET (Process Field Network) and EtherNet/IP are real-time Ethernet fieldbus protocols used for discrete I/O and safety integration in robotic cells. PROFINET, governed by PROFIBUS International, is dominant on Siemens architectures, while EtherNet/IP (CIP over TCP/UDP, defined by ODVA) is dominant on Allen-Bradley/Rockwell architectures. Yaskawa publishes both stacks as optional firmware loads for the YRC1000, but only one industrial-Ethernet personality is active per controller at a time.

The Yaskawa PROFINET reference page documents the protocol stack available on Yaskawa drives and controllers, including supported RT classes and conformance classes. For EtherNet/IP integration with PC-based controllers, the Yaskawa Knowledge Center article on YRC1000 EtherNet/IP and CODESYS demonstrates the implicit/explicit messaging model and assembly layout used when the YRC1000 is paired with a CODESYS soft PLC. The same assembly structure applies when the scanner is a Rockwell Logix controller.

Migration Strategy: Direct vs. Gateway

There are two field-proven approaches to a PROFINET→EtherNet/IP migration on a YRC1000 cell:

Approach Mechanism Use When
Direct YRC1000 personality switch Change the active protocol on the robot controller itself via management mode and reload the EtherNet/IP option firmware/files. Customer wants a clean native EtherNet/IP connection to the new Logix scanner. Existing PLC and robot both move to EtherNet/IP.
External protocol gateway Install a third-party gateway (e.g., ProSoft Technology EtherNet/IP-to-PROFINET IO Device Gateway) between the PLC and the robot. Preserving the PROFINET-side robot personality is required (e.g., shared cell with other PROFINET masters, or CIP Motion constraints).

The ProSoft Technology EtherNet/IP-to-PROFINET IO Device Gateway supports multiple I/O connections, allowing independent RPIs for control and diagnostic data so that low-priority diagnostics do not consume the high-priority control bandwidth. This is the typical choice when the YRC1000 firmware load cannot be changed.

Step-by-Step: Direct Conversion on the YRC1000

  1. Document the existing PROFINET configuration. Capture the device name, IP address, GSDML revision, slot/module assignment (input and output), and any user-defined slot mapping. The YRC1000 default PROFINET slot map is documented in the controller manual, but most integrators customize slot assignments in the I/O configuration (Fn060-Fn070 range, depending on firmware). Export these to PDF before any changes.
  2. Back up every file on the controller. Use the pendant's external storage menu to copy all jobs (.JBI), parameter sets (.PRM), ladder logic, and the system configuration to USB. Confirm the backup is restorable before continuing.
  3. Enter Management Mode. From the top menu navigate to SETUP → FUNCTION ENABLE → MANAGEMENT. The default password is typically 99999999 (eight 9s) on a virgin unit; customer passwords must be obtained from the end user. Management mode is required to alter the active communication protocol; standard operator access will grey out the relevant menus.
  4. Declare the EtherNet/IP option board. In Management Mode, go to SETUP → FUNCTION ENABLE → FIELD NETWORK (or COMMUNICATION SETUP on firmware versions that group these menus differently). Select EtherNet/IP as the active protocol. This is the same menu path used to initially declare a PROFINET board at first commissioning.
  5. Load EtherNet/IP firmware/configuration files. Insert the USB containing the EtherNet/IP option files provided by Yaskawa. From SETUP → FUNCTION ENABLE → FIELD NETWORK → EtherNet/IP, select INSTALL. The controller will copy the EDS-compatible definitions and reboot.
  6. Configure the EtherNet/IP node parameters. Assign IP address, subnet mask, and (if used) gateway. Set the connection multipliers and RPI. The default assembly instances used by Yaskawa are typically:
    • Output Assembly (robot → PLC): Instance 102 (4 bytes status + user-defined I/O)
    • Input Assembly (PLC → robot): Instance 101 (4 bytes control + user-defined I/O)
    These instances must match the scanner configuration exactly or the CIP connection will be rejected with a connection error in the Logix I/O tree.
  7. Map I/O to controller variables. The YRC1000 maps each EtherNet/IP word/byte to a specific input or output register range. Document the mapping into the same register locations previously used for PROFINET so the existing application code on the scanner does not require extensive rewrites. Yaskawa's standard mapping provides a 1:1 correspondence for the most common I/O points, but the proprietary status and control words (typically the first four bytes of each assembly) are protocol-specific and must be re-mapped.
  8. Initialize the controller. After the new protocol and mapping are loaded, perform a full INITIALIZE from SETUP → CONTROLLER → INITIALIZE. This clears any residual PROFINET stack state that is known to cause "weird I/O" behavior—inputs latching, outputs toggling, or the scanner reporting a connection but receiving garbage—after a protocol personality switch. The initialize step is the single most reliable cure for these symptoms.
  9. Restore backed-up jobs and ladder files. Reload the application files from the backup, but keep the new EtherNet/IP configuration active. Verify that the ladder file references the same internal registers and that any conditional branches on PROFINET-specific status bits are either re-mapped or removed.

Ladder and Status-Bit Considerations

Application ladder logic on the robot side generally does not need to be rewritten for a PROFINET→EtherNet/IP migration provided the I/O register addresses (B-registers, I-registers, or named variables depending on the controller generation) remain in the same numeric range. The substantive differences are in the status and control word bits:

Bit Position PROFINET typical meaning EtherNet/IP typical meaning (YRC1000)
0 PROFINET AR established CIP Class 1 connection active
1 Watchdog timeout I/O connection timeout (RPI multiplier exceeded)
2 Provider/consumer fault Explicit message fault
Bit Position Control word Control word
0 Servo on (PROFINET control byte 0) Servo on (EIP control byte 0)
1 Start / hold cancel Start / hold cancel
7 Fault reset Fault reset

Bits 0–7 are functionally identical between the two protocols on the YRC1000; the difference is the message that carries them. Bits 8–15 differ and should be reviewed against the new scanner's tag structure before energizing I/O.

Scanner-Side Configuration (Allen-Bradley Example)

  1. Add the Yaskawa YRC1000 EDS file to RSLogix 5000 / Studio 5000 (Tools → EDS Hardware Installation Tool).
  2. Add the YRC1000 to the Ethernet/IP I/O tree. Configure the Connection parameters to match the robot: Instance 101 (O→T) and 102 (T→O), the RPI value, and the connection type (Exclusive Owner, Listen Only, or Input Only as required by the application).
  3. Create the input and output controller-scope tags. The default tag names will follow the module's connection name. Verify that the tag length matches the assembly length from the robot.
  4. Confirm that the scanner's IP address is in the same subnet as the robot and that no managed switch is blocking CIP multicast (IGMP snooping without querier will silently break EtherNet/IP).

Verification Procedure

  1. From the YRC1000 pendant, navigate to STATUS → FIELD NETWORK. Confirm the link is up, the connection state reads "Connected", and the I/O counters are incrementing in both directions.
  2. From RSLogix 5000 / Studio 5000, right-click the YRC1000 module and view Module Diagnostics. The Connection Status should be "Running" with no faults. Any 0x0318 (Connection Timeout), 0x0312 (RPI Mismatch), or 0x0204 (Duplicate IP) error should be addressed before continuing.
  3. Toggle a discrete output from the scanner and verify the corresponding input bit latches on the robot. Toggle a discrete input on the robot and verify the corresponding output bit latches on the scanner. This bidirectional test confirms that the assembly mapping is correct in both directions, not just one.
  4. Force the scanner into Program mode and verify the robot enters Hold state, and conversely that placing the robot in Hold from the pendant causes the scanner's status word to reflect the change within one RPI interval.
  5. Cycle power on the robot controller. Verify the EtherNet/IP connection re-establishes automatically without manual intervention. This validates the configuration persistence after the initialize step.

Common Fault Codes and Remedies

Fault Code Likely Cause Remedy
YRC1000 AL-4130 Field network option board not detected Re-seat the option board; confirm firmware version installed matches the board hardware revision.
YRC1000 AL-4142 Duplicate IP address on the EtherNet/IP network Change the YRC1000 IP or the conflicting device; ping sweep the subnet.
Studio 5000 0x0312 RPI mismatch between scanner and adapter Align the RPI on both sides; default is 20 ms but can be lowered to 5 ms on most YRC1000 hardware.
Studio 5000 0x0318 Connection timeout (RPI × timeout multiplier exceeded) Verify cable, switch port, and IGMP snooping config. Increase the timeout multiplier as a temporary diagnostic only.
Symptom Likely Cause Remedy
I/O latched or garbage after personality switch Residual PROFINET stack state in non-volatile memory Perform full controller INITIALIZE from Management Mode, then reload configuration.
Field network menu greyed out Not in Management Mode Re-enter Management Mode; password defaults to eight 9s on virgin units.
Connection refused immediately on scanner Assembly instance mismatch Verify 101/102 instances; confirm scanner configuration uses O→T = 101, T→O = 102 (or the custom instances if configured on the YRC1000).

Field-Commissioning Checklist

  • YRC1000 backup verified restorable on a second device.
  • PROFINET slot map, GSDML revision, and device name archived.
  • EtherNet/IP option firmware version noted (record the EX. version, e.g., EX-M2.x, for support tickets).
  • Management Mode entered, EtherNet/IP personality declared, files installed.
  • Controller fully initialized after the protocol switch.
  • Application ladder/jobs restored.
  • Scanner EDS installed, module added, RPI and assemblies configured.
  • Bidirectional I/O verification passed.
  • Hold/servo-on handshake validated end-to-end.
  • Power-cycle test passed; reconnection automatic.

Safety Considerations

Safety-rated I/O and PROFIsafe / CIP Safety networks are out of scope for this protocol personality switch. Safety functions must remain on their original, certified network and must be re-validated by a qualified safety engineer after any hardware or configuration change. The E-stop wiring on the YRC1000 is hardwired and independent of the industrial Ethernet protocol; do not route E-stop signals through EtherNet/IP unless the safety network architecture has been formally re-certified.

Does the YRC1000 Micro support both PROFINET and EtherNet/IP on the same hardware simultaneously?

No. The YRC1000 Micro supports one active industrial Ethernet personality per controller at a time. To change protocols, enter Management Mode, declare the new option board, install the corresponding firmware/files, and initialize the controller. If both protocols must remain available, use an external gateway such as the ProSoft EtherNet/IP-to-PROFINET IO Device Gateway.

Will I have to rewrite my existing ladder logic on the robot when migrating from PROFINET to EtherNet/IP?

Generally no, provided the internal register mapping remains in the same numeric range. The substantive changes are in the status/control word bits (typically the first four bytes of each assembly), which must be re-mapped to match the new scanner's tag structure. Application logic that reads discrete bits above bit 7 should be reviewed before energizing I/O.

Why does the I/O behavior look wrong immediately after switching the protocol, and how is it fixed?

Residual PROFINET stack state in non-volatile memory can cause latched inputs, toggling outputs, or a "connected but garbage" appearance after a personality switch. The reliable fix is a full controller INITIALIZE from Management Mode (SETUP → CONTROLLER → INITIALIZE), followed by restoring the application files. The scanner must be placed in Program mode during the initialize step.

What are the default assembly instances for the YRC1000 over EtherNet/IP?

Default assemblies on the YRC1000 are typically Input (PLC → robot, O→T) Instance 101 and Output (robot → PLC, T→O) Instance 102, with the first four bytes of each assembly carrying the Yaskawa status/control word. Custom instances can be configured on the robot but must match exactly on the scanner side or the CIP connection will be rejected.

What is the correct menu path to enable the new protocol in Management Mode?

From the pendant top menu: SETUP → FUNCTION ENABLE → MANAGEMENT (enter the management password), then SETUP → FUNCTION ENABLE → FIELD NETWORK (or COMMUNICATION SETUP on some firmware versions). Select EtherNet/IP, install the option files from USB, and complete the configuration. The same path is used to initially declare the PROFINET board at first commissioning.

Back to blog