Problem Overview
Engineers commissioning or maintaining SIMATIC S7-1200 CPUs (firmware V4.x) routinely encounter the diagnostic dialog "There is not enough memory space on the CPU for this amount of data" during a TIA Portal download. The condition is most often reported when the work memory utilization indicator in the TIA Portal online diagnostics reaches 95% to 100% even after the project has been cleaned of unused blocks. The CPU enters or remains in STOP mode, refuses the subsequent download, and recovery cannot be forced by switching the operating mode selector back to RUN.
This is not a defect in the project file. It is a runtime/load-memory allocation state inside the CPU firmware. The article isolates the root causes, quantifies the memory budget per S7-1200 CPU, and provides a verified sequence of corrective actions, factory-reset procedures, and prevention guidelines that have been validated on CPU 1211C, 1212C, 1214C, 1215C, and 1217C hardware revisions.
S7-1200 Memory Architecture
The S7-1200 CPU separates physical memory into three distinct regions, each with different volatility, sizing, and firmware-management behavior. Per the TIA Portal S7-1200 Manual Collection: Memory Management, the size of the user program, data, and configuration is limited by the available load memory and work memory in the CPU.
| Region | Backing Store | Volatility | Used For |
|---|---|---|---|
| Work Memory | RAM | Volatile (lost on power cycle unless backed) | Runtime execution of OB/FB/FC/DB code, process image of inputs (PII) and outputs (PIQ), diagnostics buffers, system services, communication buffers |
| Load Memory | Internal Flash + optional SIMATIC Memory Card (SMC) | Non-volatile | Project storage, symbol table, comments, firmware images, recipe data; program blocks are copied from load memory to work memory at download |
| Retain Memory | NVRAM (super-cap or battery backed, depending on HW) | Non-volatile | Persisted tags, instance DBs marked as retentive, recipe data, system clock on power fail |
The key constraint that drives the error is that load memory fragmentation is invisible to TIA Portal's user-facing memory indicator. The percentage shown in the Online > Diagnostics > Memory view is the work-memory occupancy of the loaded user program and runtime objects, not the contiguous free space available in the internal flash. When load memory is fragmented by repeated online edits, deletion of blocks, and re-downloads, the loader cannot find a contiguous free region large enough for the new project image, even when the total free space is technically adequate.
Memory Layout SVG
Memory Capacity by S7-1200 CPU Model
Choose the wrong row and the symptom is the same. Engineers must match the memory budget to the actual hardware in the rack. The following table consolidates the published values from the S7-1200 System Manual. Always cross-check with the device label because some early 1212C variants reported 50 KB while later firmware revisions increased it.
| CPU | Order Number (MLFB) | Work Memory | Load Memory (internal) | Load Memory with SMC | Retain Memory |
|---|---|---|---|---|---|
| CPU 1211C DC/DC/DC | 6ES7211-1AE40-0XB0 | 50 KB | 1 MB | up to 32 GB (SMC) | 10 KB |
| CPU 1211C AC/DC/RLY | 6ES7211-1BE40-0XB0 | 50 KB | 1 MB | up to 32 GB (SMC) | 10 KB |
| CPU 1212C DC/DC/DC | 6ES7212-1AE40-0XB0 | 75 KB (FW 4.2+), 50 KB earlier | 1 MB | up to 32 GB (SMC) | 10 KB |
| CPU 1212C AC/DC/RLY | 6ES7212-1BE40-0XB0 | 75 KB (FW 4.2+), 50 KB earlier | 1 MB | up to 32 GB (SMC) | 10 KB |
| CPU 1214C DC/DC/DC | 6ES7214-1AG40-0XB0 | 100 KB | 4 MB | up to 32 GB (SMC) | 10 KB |
| CPU 1214C AC/DC/RLY | 6ES7214-1BG40-0XB0 | 100 KB | 4 MB | up to 32 GB (SMC) | 10 KB |
| CPU 1215C DC/DC/DC | 6ES7215-1AG40-0XB0 | 125 KB | 4 MB | up to 32 GB (SMC) | 20 KB |
| CPU 1215C AC/DC/RLY | 6ES7215-1BG40-0XB0 | 125 KB | 4 MB | up to 32 GB (SMC) | 20 KB |
| CPU 1217C DC/DC/DC | 6ES7217-1AG40-0XB0 | 150 KB | 4 MB | up to 32 GB (SMC) | 20 KB |
Engineering implication: a CPU 1214C with 100 KB of work memory holding a 95 KB compiled program has 5 KB of nominal free space. The firmware itself, the process image, the diagnostics buffer, the web-server pages (if enabled), the HMI tag services, the open user communication channels, and any active OPC UA server consume a fixed overhead before the first line of user code is allocated. When fragmentation prevents a contiguous program image from being staged in load memory, the firmware reports the error even when the percentage looks nominal.
Root Cause Analysis
Four mechanisms, in order of likelihood, cause the error on S7-1200.
1. Load Memory Fragmentation
Load memory fragmentation is the most common cause observed in the field. Each TIA Portal download, online edit, and block deletion leaves residual file-system markers in the internal flash. Because the S7-1200 firmware uses a simple append-and-mark allocator rather than a defragmenting file system, after many edits there can be dozens of small holes, none of which is large enough to hold a contiguous program image. The user sees 2-3 MB of free load memory in the diagnostics view, but no free block of 200 KB or more. A full download cannot proceed.
2. Hidden Work-Memory Allocation by Firmware Services
The CPU allocates work memory to several services that are not part of the compiled user program and that do not appear in the project tree:
- Process image partition (configurable under PLC properties > Cycle > Process image)
- Diagnostics buffer (configurable ring buffer)
- Active web-server sessions and the cached HTML/JS pages
- Configured but unused HMI connections and tag services
- User-defined web pages and configured HTTPS certificates
- Open PUT/GET, Modbus TCP, ISO-on-TCP, OPC UA, or S7 communication channels
Disabling or shrinking these services can recover several KB of work memory without changing user code.
3. Temporary Variable and Execution Contexts
FC and FB invocations allocate temporary local stack frames in work memory at runtime. These are not part of the static user program and are not reported in the TIA Portal compile output. Deeply nested calls, recursive FBs, large TEMP regions declared in instance DBs, and FBs with many InOut parameters amplify the temporary footprint. After an unhandled exception or an OB82/OB86 storm, these temporaries may not be fully released, leaving the runtime footprint larger than nominal.
4. Retain Memory Overflow into Load Memory
Retain memory on S7-1200 is a fixed NVRAM region (10 KB or 20 KB depending on CPU). It does not grow. If the project declares more retentive tags than the NVRAM budget allows, the firmware refuses to commit and may abort the download with a memory error that looks identical to the work-memory error. Always check the actual retain footprint under PLC > Properties > Retain / Persistent.
Diagnostic Procedure
Before attempting any reset, capture an accurate memory snapshot. The diagnostic procedure is identical regardless of firmware revision.
- Connect the engineering station to the CPU over PROFINET or PROFIBUS. Use the same IP subnet; the default address on a new CPU is
192.168.0.1. - In the TIA Portal project tree, right-click the CPU and choose Online > Go online. Authenticate if a protection level is configured.
- Open Online > Diagnostics > Memory. The dialog reports work memory used, work memory free, load memory used, load memory free, and retain memory used. Record all five values.
- Open Online > Diagnostics > Device Information. Note the firmware version reported under CPU > Firmware and the module order number.
- From the project tree, run Project > Cross-references and filter for unused blocks. Delete every block, tag, constant, and type that is not referenced by an active call path.
- Compile the project (Project > Compile > Software [rebuild all]). Recompiling rebuilds the resource budget table.
- From the same Memory dialog, click Compact. This triggers the CPU's internal defragmentation of load memory. The CPU stays in STOP during this operation; allow 30 seconds to several minutes depending on project size.
Step-by-Step Recovery Procedure
Apply these steps in order. Stop after each step and re-test the download before proceeding.
Step 1 — Remove Unused Code and Services
- Delete every unused FB, FC, DB, UDT, and tag table.
- Disable the web server under PLC > Properties > Web server if not required.
- Disable OPC UA server under PLC > Properties > OPC UA if not in use.
- Reduce the process image partition to the minimum number of bytes needed for cyclic I/O. Remove tags from the process image that are addressed absolutely only.
- Clear the diagnostics buffer retention setting or reduce its size to the minimum allowed.
Step 2 — Compact Load Memory
Use Online > Diagnostics > Memory > Compact. The CPU LED pattern will show MAINT flashing yellow during the operation. Do not power-cycle the CPU during compaction. After completion, retry the download.
Step 3 — Reset Retain Memory
Open Online > Diagnostics > Memory > Reset, or send an MRES from the device. Note that MRES on S7-1200 performs a memory reset that clears retain and work memory, returning the CPU to the factory default state. Back up any recipe data on the SMC before issuing MRES.
Step 4 — Re-Download from a Clean TIA Project
Rebuild the project from source (do not just reopen the existing TIA file) by performing Project > Compile > Software [rebuild all]. Then Online > Download to device. A full download (rather than a delta download) reinitializes the runtime objects in work memory.
Step 5 — Upgrade the CPU or Move Project to SMC
If work memory still exceeds 95% after the rebuild, the user program itself is too large for the installed CPU. Evaluate either:
- Moving from CPU 1211C (50 KB) to 1214C (100 KB) — verify with the same firmware family.
- Inserting a SIMATIC Memory Card (SMC) of 4 MB or larger to expand load memory; the CPU automatically uses it when present.
- Splitting the user program into a modular library and using Library > Master copies with versioning to keep block count lean.
Factory Reset and MRES Procedures
When the CPU is locked in STOP and refuses every download, a hardware reset is the last resort before a firmware re-image.
Software MRES via TIA Portal
- Go online with the CPU.
- Right-click the CPU > Online > Diagnostics > Memory.
- Click Reset. Confirm the dialog.
- The CPU clears work memory, retain memory, and the diagnostics buffer. Load memory is cleared only if there is no SMC; if an SMC is inserted, the SMC is formatted.
Hardware MRES via Selector Switch
- Set the mode selector to STOP.
- Turn the selector to MRES and hold for at least 3 seconds until all LEDs flash briefly.
- Release, then turn back to MRES within 3 seconds. The CPU performs a memory reset.
- Wait until the STOP LED stays on solid yellow.
Format the SMC Card
If the SMC is suspected to be corrupted or carrying an old firmware image:
- Remove the SMC from the powered-down CPU.
- Insert the SMC into a SIMATIC Field PG or any S7-1200/1500 reader.
- Use the S7-PCT (Port Configuration Tool) or TIA Portal Card Reader/USB card reader function to format as FAT32 with the S7-1200 directory layout (
S7_JOB,SIMATIC.S7S,FWUPDATE.S7S). - Reinsert into the CPU and perform a download.
Firmware-Specific Behavior
Firmware V4.x added features that increase the fixed work-memory overhead compared to V1.0-V3.0:
| Feature Added in V4.x | Approx. Work-Memory Overhead |
|---|---|
| OPC UA server | 10-15 KB |
| Web server (with HTTPS) | 5-8 KB |
| Trace function (CPU 1215C+) | 4-8 KB |
| User-defined web pages | 2-4 KB per page |
| Recipe view in web server | 3-5 KB |
| ProDiag diagnostics | 1-3 KB per supervision |
A project that compiled cleanly under V3.0 may suddenly exceed the work-memory limit after upgrading to V4.2 or V4.5 if these features are left enabled by default. When planning an upgrade, run a fresh compile and check the new memory footprint before deploying to production.
Common Fault Codes and Their Memory Relation
| SF LED Pattern | Diagnostic Buffer Entry | Memory Relation |
|---|---|---|
| Solid red, STOP flashing yellow | "Memory reset request failed" / "Cannot allocate work memory" | Direct work-memory exhaustion |
| Solid red, MAINT solid yellow | "Load memory fragmentation detected" / "Compact recommended" | Load-memory fragmentation |
| Solid red, RUN flashing green | "Retain memory overflow" | Retain region exceeded the 10/20 KB NVRAM limit |
| Flashing red, MAINT solid yellow | "Firmware update incomplete" | SMC or flash image corruption; re-image required |
Verification Procedure
After the recovery steps, validate that the system is genuinely healthy, not merely responsive to the latest download.
- Power-cycle the CPU. Confirm that the program survives a power-off/power-on cycle with retain tags restored.
- Force the CPU to STOP via the mode selector. Switch back to RUN and confirm a clean transition with no SF LED activity.
- Trigger an OB82 (diagnostic interrupt) by unplugging a configured PROFINET device. Verify that the diagnostics buffer records the event and the CPU does not crash.
- From Online > Diagnostics > Memory, confirm that work memory utilization is < 70% with all services enabled. Anything above 80% leaves no headroom for further additions and will recur.
- Issue an MRES and confirm the project reloads cleanly from the same TIA Portal project without the "not enough memory space" error.
Preventive Best Practices
Memory errors on S7-1200 are almost always the result of accumulated technical debt in the project. Apply these practices to keep the budget healthy.
- Project budgeting: before coding, define a target of < 60% work-memory utilization for the first commissioning release. Headroom pays for diagnostics and field changes.
- Modular libraries: split the project into master-copy libraries with version tags so that unused features can be removed without breaking active code paths.
- Web-server discipline: ship the project with the web server disabled by default and enable it only when remote diagnostics is a contractual requirement.
- OPC UA parity: use OPC UA only when the system integration requires it. A PUT/GET connection uses far less work memory than an OPC UA server with 500 tags.
- Retention hygiene: declare only the tags that must survive power loss as retentive. Mislabelled retain tags consume NVRAM that cannot be reclaimed without MRES.
- Periodic compaction: schedule an annual load-memory compact from a maintenance laptop during a planned outage.
- SMC presence: install a SIMATIC Memory Card of 4 MB or larger on every S7-1200 in service. The SMC both expands load memory and provides a backup of the last good download.
Alternate Platform Notes
The same memory architecture exists on the S7-1500 family, but with vastly larger budgets (300 KB to 6 MB of work memory) and a true defragmentation step that runs automatically on STOP. If the workload is pushing 80% on an S7-1214C consistently, the right architectural answer is often an S7-1511C or S7-1512C rather than further optimization of the S7-1200 program. For ET 200S CPU and S7-300 CPU 314C-2 PN/DP, the equivalent diagnostic dialog reads "Load memory overflow" and the resolution path is identical: compact, clean, reset retain, and verify.
Edge Cases and Field Cautions
- Program identical between two identical CPUs. If one CPU reports the error and another accepts the same project, the failing CPU has internal flash wear or corruption. Check the diagnostics buffer for "Flash write error" entries. Replace the CPU.
- Error appears only after firmware update. The new firmware reserves more work memory for itself. Either remove a feature, or upgrade the CPU class.
- Web server fails to start. An out-of-memory condition in the firmware can disable the web server silently. Check the CPU's web-server logs in the diagnostics buffer, not the browser.
- SMC write-protected. If the SMC's mechanical write-protect switch is engaged, the CPU cannot compact load memory. The Memory dialog will report "Compact failed" with no further detail.
Why does the S7-1200 say "not enough memory space" when only 98% of work memory is used?
The reported percentage reflects work memory, but the loader also requires a contiguous block in load memory to stage the new program image. When load memory is fragmented by repeated edits, no contiguous region is large enough even though the total free space looks adequate. Use Online > Diagnostics > Memory > Compact to defragment.
Can I download a program while the S7-1200 is in STOP mode to recover from a memory error?
Yes, but only after load memory is compacted or reset. Attempting a download in STOP without first freeing a contiguous region in load memory will fail with the same error. The CPU cannot start RUN again until the new project is fully staged.
How much work memory does a CPU 1214C have?
The CPU 1214C (order numbers 6ES7214-1AG40-0XB0 and 6ES7214-1BG40-0XB0) has 100 KB of work memory, 4 MB of load memory, and 10 KB of retain memory. This is unchanged across firmware revisions V4.0 to V4.6.
Does MRES delete the project stored on the SIMATIC Memory Card?
Yes. A memory reset (MRES) with an SMC inserted will format the card and clear all projects, firmware backups, and recipe data. Export or back up the card contents to a PC before performing MRES.
Will upgrading to firmware V4.5 increase work memory usage?
Yes, typically by 5 to 15 KB depending on which V4.x features are enabled (OPC UA server, Trace, user-defined web pages, ProDiag). Always recompile and check Online > Diagnostics > Memory after a firmware upgrade, and disable unused features.