Problem: HMI Cannot See When an H-Station CPU Goes to STOP
In a SIMATIC S7-400H redundant station, two CPUs of the same type (for example, CPU 412-3H, CPU 414-4H, CPU 416-5H, CPU 417-4H, or the newer CPU 410-5H process automation CPU) run in hot-standby redundancy. At any moment only the master CPU holds the role of active CPU and updates the process image; the reserve CPU remains synchronized but does not execute the user program in write mode.
A Comfort Panel or WinCC Runtime running in TIA Portal V12 is connected to the H-station through one or more S7 connections. When the project is created in the non-integrated environment (WinCC TIA V12 paired with STEP 7 V5.5/SPx), the H-station cannot be configured directly inside TIA Portal. The workaround is the Tag Converter, which converts STEP 7 V5.5 symbols so that WinCC TIA can read them. Because the H-station contains two physical CPUs, two connections must be imported - one targeting CPU 0 and one targeting CPU 1.
The operator must be able to see at a glance which CPU is in RUN, which is in STOP, and which is currently the active master. Operators also need to switch the displayed connection manually using HMI buttons so that diagnostics and process values are always read from the live CPU.
The default system event 14001 "Connection to PLC failed" only fires when the connection breaks entirely, typically after a power-off, cable pull, or rack failure. A CPU transition to STOP caused by OB omission, programming error, or operator-initiated stop switch does not drop the S7 connection, so event 14001 is never raised. Clock memory bytes cannot be configured on an H-station in the same way as on a standard S7-300/400, because the OB1 clock-bit generator is part of the H-system firmware and is not exposed for user selection in the non-integrated path. A dedicated STOP-detection mechanism is therefore required.
Root Cause: H-Station Connection Model vs. Standard S7
On a standard S7-300/400 station, the HMI polls tags and infers status from the response. The TIA Portal system diagnostics view and the WinCC channel diagnostics both rely on the connection state. As stated in the Siemens function manual Showing diagnostic information on an HMI device:
If at least one CPU indicates an error, the overall status also indicates an error. The system diagnostics view reflects the current operating state of the CPUs and modules.
For an H-station, however, the HMI connection can remain alive even when the active CPU transitions to STOP, because the reserve CPU continues to acknowledge the connection at the CP/IE level. The HMI sees a healthy channel and a healthy partner - it just does not see that the program is no longer executing user code on the CPU it is bound to.
Three mechanisms must therefore be evaluated:
- Reading the CPU operating-state bits (RUN/STOP/STARTUP/HOLD) directly from the CPU's system area.
-
Evaluating the H-system status word via FB523
STATUS_H(Siemens standard library). -
Reading the diagnostic buffer via SZL/WRK16 or SFC51
RDSYSSTto surface the cause of the STOP.
Solution 1: Read CPU RUN/STOP with a WinCC TIA PLC Status Tag
The simplest method requires no additional FB. Both H-CPU firmware variants expose the operating state in the system status list (SZL) at SSL 0x0019 / Index 0xxy. A user-defined WinCC PLC status tag can be configured on the connection so the runtime polls SZL 0x0019 and returns the byte that contains the current operating state. The same approach is documented in the Siemens application note "Evaluation of the PLC Status 'RUN/STOP' with a SIMATIC S7" (entry ID 109481628):
The HMI tag is updated until the CPU goes into the STOP status. In this way it can be determined at what time the CPU went into the STOP status.
Configuration Steps in WinCC TIA
- Open the WinCC TIA project that uses the imported STEP 7 V5.5 connections (CPU 0 and CPU 1).
- Right-click HMI tags → Add new tag. Select the connection that points to the CPU you want to monitor (use both connections - one tag per CPU).
- In the tag properties, set Acquisition mode = Cyclic in the background with a 1 s cycle.
- Set PLC status tag = <tag name>. This binds the connection's internal status flag to the tag.
- Verify in the runtime that the tag flips between
0(RUN) and2(STOP) when the CPU is toggled. The numeric encoding is defined by the SIMATIC S7 protocol and is documented in the WinCC Information System under "Connection status / PLC status".
| PLC status tag value | CPU operating state | HMI interpretation |
|---|---|---|
| 0 | RUN | Healthy - connection active, user program executing |
| 1 | STARTUP | Warm/cold restart in progress |
| 2 | STOP | CPU halted - request master switch or investigate cause |
| 3 | HOLD | Test/debug - breakpoints active in STEP 7 |
| 4 | Connection failed | Cable/CP/power issue - separate from STOP |
Solution 2: FB523 STATUS_H from the SIMATIC H Standard Library
For a richer H-specific status that distinguishes master vs. reserve, link-up state, and self-test results, use FB523 STATUS_H from the SIMATIC H - Standard Library. The FB is part of the standard delivery of STEP 7 V5.5 and is installed under Library → SIMATIC H → Standard Library → STATUS H.
FB523 Interface
| Parameter | Declaration | Type | Description |
|---|---|---|---|
| DB_STAT | INPUT | BLOCK_DB | Instance DB - must be created when FB523 is inserted |
| CH_OK | OUTPUT | BOOL | TRUE = optical fiber link OK between both H-CPUs |
| MASTER | OUTPUT | BOOL | TRUE = CPU on which FB523 runs is the active master |
| RESERVE | OUTPUT | BOOL | TRUE = CPU on which FB523 runs is the reserve |
| STOPPED | OUTPUT | BOOL | TRUE = CPU has stopped or is not linked up |
| HALTED | OUTPUT | BOOL | TRUE = self-test failure on this CPU |
| FORCE | OUTPUT | BOOL | TRUE = at least one variable is forced on this CPU |
| REDUND | OUTPUT | BOOL | TRUE = system is in redundant mode |
| EXT_F | OUTPUT | BOOL | TRUE = external error (link-down, partner missing) |
| DB_STAT_NO | OUTPUT | INT | Diagnostic status number |
Recommended Wiring
Call FB523 once per CPU in OB1 with a dedicated instance DB:
CALL "STATUS_H" , DB_STAT_CPU0 // on CPU 0 side
CH_OK := M 100.0
MASTER := M 100.1
RESERVE := M 100.2
STOPPED := M 100.3
HALTED := M 100.4
FORCE := M 100.5
REDUND := M 100.6
EXT_F := M 100.7
CALL "STATUS_H" , DB_STAT_CPU1 // on CPU 1 side
CH_OK := M 110.0
MASTER := M 110.1
RESERVE := M 110.2
STOPPED := M 110.3
HALTED := M 110.4
FORCE := M 110.5
REDUND := M 110.6
EXT_F := M 110.7
These flag bytes are then imported via the Tag Converter into WinCC TIA as two separate tag groups (one per CPU connection). On the Comfort Panel, render two status panels side by side and show the STOPPED, MASTER, and REDUND flags as colored indicators:
- Green background = RUN + MASTER + REDUND
- Yellow background = RUN + RESERVE + REDUND
- Red background + flashing border = STOPPED
- Gray background = CH_OK = FALSE (fiber link failure)
Solution 3: Surface the Cause via the Diagnostic Buffer
When the operator sees a STOP indication, the next action is to identify the cause. The CPU stores up to 200 diagnostic entries in its internal buffer. Read them with SFC51 RDSYSST using SZL ID W#16#0131 (SSL 0x00A0 partial list - diagnostic buffer).
A typical pattern is:
CALL "RDSYSST"
REQ := TRUE
SZL_ID := W#16#0131 // Diagnostic buffer
INDEX := W#16#0001
RET_VAL:= MW 200
BUSY := M 202.0
SZL_HEADER. := P#M 204.0 BYTE 20
DR := P#DB_STAT_BUF.DBX0.0 BYTE 2400
Each 20-byte event is parsed in OB1 or a cyclic alarm OB to extract event ID, timestamp (10-byte date/time in BCD), and the OB that failed. WinCC TIA can then display the most recent event in plain text on the panel - "OB85 missing - priority class 1", "Stop because programming error in OB1", "Stop by mode selector".
Manual Master Switch from the HMI
Because TIA Portal V12 cannot fully model the H-station, master-switch commands must be implemented at the program level. Two common approaches exist:
Approach A: Switch Using the H-System Control Tag
Configure a WinCC tag that writes to a Boolean marker, e.g. DB_HMI.SWITCH_REQ. In OB1 on the reserve CPU, evaluate this flag and call FC 100 "H-SWITCH_REQUEST" from the SIMATIC H library when it rises - this triggers a controlled master swap without loss of redundancy state.
Approach B: Toggle the HMI Connection
In WinCC TIA V12, two connections (CPU 0 and CPU 1) coexist. Use a script on a button press to change the active connection pointer of the screen from connection A to connection B. The HMI tags remain defined once; only the binding switches. This is the preferred approach when the operator wants diagnostics about the failed CPU without losing the ability to read the surviving one.
- Define all display tags twice - once on each connection.
- On the master screen, expose a "Show CPU 0" / "Show CPU 1" selector button.
- Wire the selector to a tag that re-binds the screen via a WinCC VBS script:\li>
' VBS - switch the active connection group on button click
Sub OnClick(ByVal item)
Dim cur
cur = SmartTags("HMI.ActiveCPU") ' 0 or 1
If cur = 0 Then
SmartTags("HMI.ActiveCPU") = 1
HMIRuntime.Trace "Switched view to CPU 1"
Else
SmartTags("HMI.ActiveCPU") = 0
HMIRuntime.Trace "Switched view to CPU 0"
End If
End Sub
Pair this with the STOPPED indicator so the operator knows which connection is currently the meaningful one.
Step-by-Step Commissioning Procedure
- Verify firmware. CPU 41x-3H/4H/5H must be at firmware V5.x or higher; CPU 410-5H must be V8.x or higher to support the diagnostic buffer extensions.
- Open STEP 7 V5.5 on the project for the H-station. Insert FB523 in OB1 of each CPU with separate instance DBs.
-
Compile and download both CPUs. Confirm in STEP 7 online that
CH_OK,MASTER,REDUNDrise correctly. - Run the Tag Converter on the STEP 7 symbols. Import the result into WinCC TIA V12.
- Create two S7 connections in the WinCC TIA project: one targeted at CPU 0 rack/slot, one at CPU 1 rack/slot.
- Configure two PLC status tags, one per connection. Set the cycle to 500 ms.
- Build the status screen with two panels (CPU 0 / CPU 1) showing PLC status + FB523 flags.
-
Add manual switch buttons with confirmation dialog. Wire to
HMI.ActiveCPU. - Add the diagnostic buffer viewer using SFC51 RDSYSST + a WinCC text list.
- Simulate STOP by toggling the mode selector on each CPU and verify the panel flips the status icon within 1 s.
-
Simulate link loss by disconnecting one fiber. Verify
CH_OKflag changes on both CPUs and the alarm is raised on the HMI.
Verification Matrix
| Scenario | Expected panel state | FB523 flags | PLC status tag | Connection health |
|---|---|---|---|---|
| Both CPUs RUN, master = CPU 0 | Green CPU 0, yellow CPU 1 | MASTER=1 / RESERVE=1, REDUND=1, STOPPED=0/0 | 0 / 0 | OK / OK |
| Master switch via mode selector | Yellow CPU 0, green CPU 1 | MASTER swap, REDUND stays 1 | 0 / 0 | OK / OK |
| CPU 0 in STOP after OB omission | Red CPU 0 (flashing), green CPU 1 | STOPPED=1 on CPU 0, STOPPED=0 on CPU 1 | 2 / 0 | OK / OK |
| Fiber link broken | Gray CPU 0, gray CPU 1 + alarm | CH_OK=0 / CH_OK=0, EXT_F=1 | 0 / 0 (no STOP) | OK / OK |
| CPU 0 powered off | Gray CPU 0, green CPU 1 | CPU 0 unreachable | 4 / 0 (only after timeout) | FAIL / OK (system event 14001 on connection 1) |
| CPU in HOLD (test mode) | Blue CPU panel + "TEST" badge | MASTER=1, STOPPED=0 (HOLD not exposed in FB523) | 3 | OK |
Troubleshooting Common Pitfalls
| Symptom | Likely cause | Resolution |
|---|---|---|
| Status tag never updates to 2 even after CPU STOP | Acquisition cycle too long, or PLC status tag not bound | Reduce cycle to 500 ms; verify the tag property "PLC status tag" is set to its own name |
| FB523 STOPPED never goes TRUE on CPU 0 | FB523 instance DB not downloaded to the right CPU | Use STEP 7 "Target system → Download to target device → Selected CPU" for each instance DB |
| System event 14001 raises but operator still sees live tags | Connection defined on the wrong CP (Ethernet vs. PROFIBUS), partner CPU answers | Bind connection to the specific rack/slot of CPU 0 or CPU 1 |
| Tag Converter drops some FB523 outputs | Symbol table contains only the start address; outputs are not exported individually | Export symbols as "with absolute addresses" or use the symbol table view to flag each output as "usable for HMIs" |
| Clock memory byte request rejected | H-station does not expose the clock memory dialog in the same way as S7-300 | Implement a software clock generator in OB1 using a 200 ms cyclic interrupt instead |
| Master switch button does nothing | FC 100 H-SWITCH_REQUEST not available in the configured standard library | Install the SIMATIC H option package for STEP 7 V5.5; FC 100 is included there |
| Diagnostic buffer empty after STOP | Buffer read issued before STOP committed | Add a 2 s delay between SFC51 REQ rising edges; or trigger the read on the falling edge of STOPPED |
Why Not Rely Solely on System Event 14001
System event 14001 is generated by WinCC only when the S7 channel driver detects the connection is broken (no ACK on TPDU within the configured timeout). The default timeout is typically 5-15 s, which is acceptable for a power-off but masks a STOP. In redundancy, the H-system keeps the partner CPU reachable for protocol-level ACKs even when one CPU halts its user program, so the channel never reports failure. The PLC status tag and FB523 outputs remain the authoritative sources for STOP detection.
Alternates and Field-Proven Tips
On very large HMI projects where the master switch must be transparent to scripts and recipes, define the connection in WinCC TIA as a multiplexed tag group bound to HMI.ActiveCPU. The multiplexing automatically re-resolves each tag's source connection whenever the selector changes, so the script layer does not need to touch individual tag bindings.
For WinCC Professional / WinCC Unified in TIA Portal V16 or later, the H-station is supported natively, and the system diagnostics view can be embedded directly on the panel without FB523. The principles above still apply, but the PLC status tag and diagnostic buffer handling can be replaced by the built-in "System Diagnostics" control.
For panel-class HMIs (Comfort Panel TP700/TP900/TP1200, WinCC RT Advanced), the script VBS shown above is the recommended implementation. Avoid C scripts in TIA V12 - they are deprecated and unsupported in subsequent TIA versions.
FAQ
Why does WinCC system event 14001 not fire when an S7-400H CPU goes to STOP?
Event 14001 is raised only when the S7 channel detects a connection failure (TPDU timeout, no ACK). A CPU transition to STOP keeps the protocol layer alive because the reserve CPU continues to acknowledge frames. Use a PLC status tag or FB523 STATUS_H instead.
Can I use a clock memory byte on an H-station?
No. The clock memory dialog is not exposed for H-CPUs. Implement a software clock generator in OB1 or use a cyclic interrupt OB (OB30-OB38) to toggle a free marker at the desired frequency.
What is the difference between FB523 STATUS_H and the PLC status tag?
FB523 returns rich H-specific information (master/reserve, link state, forced variables, self-test status). The PLC status tag returns only the operating state of the bound CPU (RUN/STARTUP/STOP/HOLD) as a numeric value. Use both for full visibility.
How do I switch the active CPU on a Comfort Panel without losing tags?
Define all tags on both connections (CPU 0 and CPU 1). Bind them to a multiplexer controlled by an HMI tag such as HMI.ActiveCPU. Toggle the tag from a button with a VBS script that writes 0 or 1.
Where is the diagnostic buffer read for an S7-400H?
Use SFC51 RDSYSST with SZL_ID = W#16#0131 on the active master CPU. The buffer is local to each CPU, so issue the read on the CPU you want to investigate, or after a master switch re-issue on the new master.