S7-400H WinCC Redundancy: Selecting Softnet IE RNA vs RedConnect

David Krause16 min read
Industrial NetworkingSiemensTechnical Reference
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Overview of S7-400H and WinCC Network Redundancy

SIMATIC S7-400H is a fault-tolerant PLC platform where two AS 410 / AS 400H CPUs run synchronized via fiber-optic redundancy links. When WinCC stations must visualize the H-system across a plant LAN, the question is no longer "can WinCC talk to S7-400H" but "how do you make that communication survive a single cable, switch, NIC, or PC failure without operator intervention."

Siemens offers two complementary software layers to achieve this on the PC side:

  • SIMATIC NET SOFTNET-IE RNA – the layer that fuses two physical Ethernet adapters into one logical adapter using the PRP (Parallel Redundancy Protocol, IEC 62439-3).
  • SIMATIC NET SOFTNET-IE S7 RedConnect – the layer that establishes and supervises high-availability S7 connections on top of that redundant path, including automatic switchover and reconnection after a fault.

The selection between these two products, the choice between software and hardware (SCALANCE X204RNA) redundancy nodes, and the licensing model are the three most common sources of error when engineering a S7-400H ↔ WinCC system. This reference consolidates the selection criteria, catalog numbers, supported CP modules, and configuration workflow for an S7-400H plant with V13 / V13 SP1 era WinCC stations.

Engineering scope: This article addresses the plant-side (PC/network) redundancy of an S7-400H system as observed from a WinCC station. It does not describe the S7-400H CPU pair redundancy itself, the fiber-optic sync modules, or Y-Link topology – only the LAN path between WinCC and the H-CPUs.

Plant Network Topology Fundamentals

An S7-400H station contains two H-CPUs and typically two Industrial Ethernet CPs (e.g., CP 443-1) per CPU rack, or one CP per CPU when a SCALANCE X204RNA is used as the PRP redundancy box. From the network perspective there are two physical subnets (SubNet A and SubNet B). The WinCC station can connect to the H-system in three structural ways:

  1. Two separate NICs, two separate IP addresses – classical approach using RedConnect high-availability S7 connections and S7-RECONN/S7-OPC for failover.
  2. Two NICs bonded by RNA into one virtual adapter – the WinCC station sees only one IP but receives frames on both subnets simultaneously (PRP, zero-loss).
  3. One NIC through a SCALANCE X204RNA – SCALANCE performs the PRP duplication in the network, PC sees a single LAN.

Methods (1) and (2) place the redundancy node in the PC. Method (3) places the redundancy node in the switch. The engineering, commissioning, and licensing implications differ in all three cases.

PRP and HSR terminology

PRP (Parallel Redundancy Protocol) duplicates each Ethernet frame on two physically isolated LANs and discards the duplicate at the receiver. Both frames are transmitted simultaneously, so there is zero switchover time on failure – the receiver simply keeps using the surviving frame stream. This is the protocol used by SCALANCE X204RNA and by SOFTNET-IE RNA. HSR (High-availability Seamless Redundancy) is a ring variant of the same IEC 62439-3 standard, used inside the S7-400H backplane network and not relevant to the PC connection.

SOFTNET-IE RNA versus SOFTNET-IE S7 RedConnect

Both products are part of the SIMATIC NET family and can co-exist on the same WinCC station, but they solve different problems.

Criterion SOFTNET-IE RNA V13 SOFTNET-IE S7 RedConnect VM V12
Catalog number 6GK1711-1EW13-0AA0 6GK1704-0HB13-0AA0
OS support Windows 7/10/Server 2012 R2/2016/2019 (per V13+SP1 release notes) Windows 7/10/Server 2012 R2/2016 (32 & 64-bit per V12 release notes)
Function Bonds two physical NICs into one PRP virtual adapter, transparent to the application Establishes and supervises high-availability S7 connections (failover S7 connections)
Layer Layer 2 / IEC 62439-3 PRP Layer 7 / S7 connection management (S7-RECONN)
Visible from WinCC One logical NIC, one MAC, one IP Two configured S7 connections (primary, standby) to the H-CPU pair
Switchover time Zero (parallel transmission) Typically 300 ms – 3 s depending on keep-alive and configured timeout
Independent of S7? Yes – any TCP/IP application benefits No – only S7 and OPC traffic; needs S7-400H as partner
VM use Not licensed for VM in V13; runs on physical host VM explicitly supported; license per VM instance
CP partner on PLC side CP 443-1 with PRP-capable firmware, or SCALANCE X204RNA between CP and PC CP 443-1 in H-system configured as S7-RECONN partner

Engineering rule of thumb: RedConnect alone gives you redundant S7 connections but the failure window is the S7-RECONN keep-alive cycle. RNA alone gives you lossless Layer-2 redundancy but the application still has only one S7 connection; if the S7 connection itself breaks the application has to recover it. The recommended S7-400H + WinCC engineering is to use both: RNA for the lossless LAN path, RedConnect on top for high-availability S7 connection supervision.

Recommended pairing on a WinCC station

  • Physical PC (not VM) – 6GK1711-1EW13-0AA0 (RNA) + 6GK1704-0HB13-0AA0 (RedConnect, host-OS install acceptable for non-VM use but most plants install the VM SKU uniformly for licensing simplicity).
  • WinCC running inside VMware/Hyper-V VM – the VM SKU of RedConnect (6GK1704-0HB13-0AA0) is mandatory, plus one RNA license per VM if RNA is also deployed in the VM (RNA cannot see host NICs in a VM; use two virtual NICs bridged to two host physical NICs).

SCALANCE X204RNA Integration

SCALANCE X204RNA (6GK5204-0BA00-2KB2 in current naming) is a managed Industrial Ethernet switch with four RJ45 ports and built-in PRP redundancy box function. It allows a device with a single Ethernet port (such as the on-board NIC of a WinCC IPC) to participate in a PRP network without installing RNA on the PC.

When SCALANCE X204RNA replaces PC-side RNA

The redundancy node moves from the PC to the network. The advantages and disadvantages are:

  • Pro: Zero software footprint on the WinCC station – no RNA install, no driver, no virtual adapter. Simpler for OEM image deployment.
  • Pro: Older WinCC versions without RNA support can still achieve Layer-2 redundancy.
  • Con: Redundancy now starts at the SCALANCE, not at the PC. A failure of the SCALANCE itself is not protected.
  • Con: Two SCALANCEs are required (one per SubNet A and SubNet B), and each must be paired with the corresponding PLC-side subnet.

Topology example with SCALANCE X204RNA

WinCC PC NIC 1 ─── Subnet A ─── SCALANCE X204RNA-A ──┐
WinCC PC NIC 2 ─── Subnet B ─── SCALANCE X204RNA-B ──┤
                                                        │ PRP trunk
                              CP 443-1 (CPU0) ─────────┤
                              CP 443-1 (CPU1) ─────────┘

Each SCALANCE X204RNA terminates one PRP subnet on the PC side and forwards over a single PRP trunk to the S7-400H rack. From the WinCC station's perspective there is still one IP address on its PC side, but the PC NIC count must be two (one per SCALANCE) unless the SCALANCE is configured as a DANP with a single uplink – which is not the supported pattern for S7-400H redundant connections.

Answer to the engineering questions

  • Can SCALANCE X204RNA be used instead of SOFTNET-IE RNA? Yes – it performs the same Layer-2 PRP bonding function in hardware. The trade-off is that redundancy coverage no longer extends to the PC NIC.
  • Can a single RJ45 on the motherboard be used? Only when redundancy starts inside SCALANCE X204RNA on the network side. A single PC NIC behind a SCALANCE is sufficient if the SCALANCE performs the PRP node function (DANP) and the partner side is also PRP-capable.

Communications Processor (CP) Selection

The CP modules installed in the WinCC station must be compatible with the chosen redundancy mechanism. Siemens explicitly excludes several HARDNET CPs from use with SOFTNET-IE RNA / RedConnect.

Module Type Status with RNA/RedConnect
CP 1612 SOFTNET (PCI) Supported in legacy systems; V13+SP1 supports via driver
CP 1613 HARDNET NOT supported with SOFTNET-IE RNA V13
CP 1616 HARDNET NOT supported with SOFTNET-IE RNA V13
CP 1623 HARDNET NOT supported with SOFTNET-IE RNA V13
CP 1628 HARDNET NOT supported with SOFTNET-IE RNA V13
CP 1604 HARDNET (Microbox) NOT supported with SOFTNET-IE RNA V13
Intel/Realtek on-board NIC SOFTNET Supported via standard NDIS driver
CP 1626 HARDNET PCIe Supported (firmware ≥ V2.5 for RNA)
Critical: HARDNET modules carry their own Layer-2 stack and cannot be bonded by SOFTNET-IE RNA. The RNA driver only operates against NDIS-compatible SOFTNET adapters (PCIe soft NICs, on-board NICs, or CP 1626 with SOFTNET mode). For HARDNET CPs, redundancy must be implemented in RedConnect-only mode (two separate IPs, no RNA), or the HARDNET CP must be replaced with SOFTNET-equivalent hardware.

Two-CP configurations in the PC

When two CPs are installed in the WinCC station, the rule is:

  • If both CPs are SOFTNET (e.g., two Intel NICs or CP 1626 in SOFTNET mode): install SOFTNET-IE RNA V13 to bond them, plus RedConnect VM V12 for S7 connection failover.
  • If CPs are HARDNET: do not install RNA; install RedConnect VM V12 only and configure two distinct S7 connections in WinCC (one to CPU0, one to CPU1) with RedConnect supervision.
  • Mixing one HARDNET + one SOFTNET: not supported by RNA driver; use RedConnect-only configuration.

Licensing Model

SOFTNET-IE RNA and SOFTNET-IE S7 RedConnect use a per-computer license model. The license is tied to the PC and is not per-CP, per-NIC, or per-subnet.

Scenario RNA licenses RedConnect licenses
One physical WinCC station, no VM 1 × 6GK1711-1EW13-0AA0 1 × 6GK1704-0HB13-0AA0
Two VMs on one host, each running WinCC 2 × 6GK1711-1EW13-0AA0 (one per VM) 2 × 6GK1704-0HB13-0AA0 (one per VM)
Redundancy in SCALANCE, no RNA on PC 0 1 × 6GK1704-0HB13-0AA0
WinCC server + separate WinCC client (both physical) 1 each 1 each

License files are stored in the standard Siemens license container (C:\ProgramData\Siemens\Automation\LicenseKey.bin on Windows 10/2016 or the equivalent AX NF ZZ directory on older OS). The Automation License Manager tool (almsrv.exe) must be running as a service for both products to start.

License transfer between PCs: Licenses can be returned to the license server via ALM and re-issued to a replacement PC. Do not simply copy LicenseKey.bin – it is bound to the PC SID/host ID. Use the official transfer/rehost workflow in ALM.

Configuration Procedure

The following step-by-step assumes a Windows 10 IoT Enterprise LTSC 2019 IPC running WinCC Professional V16, an S7-400H with two CP 443-1 EX30 modules, and the RNA + RedConnect combination.

Prerequisites

  • SIMATIC NET DVD V13 + SP1 installed (mandatory – V12 only is not sufficient for the current RNA V13 driver).
  • Two identical SOFTNET-compatible NICs installed and recognized by Windows (PCIe Intel i210 / i350 recommended).
  • Both CPs visible in Device Manager without yellow bang.
  • Automation License Manager (ALM) installed and shows both license keys as valid.
  • WinCC project closed; no STEP 7 / TIA Portal connection to the AS during NIC rebind.

Step 1 – Install the SIMATIC NET stack

  1. Mount the SIMATIC NET V13 SP1 DVD or run SIMATIC_NET_V13_SP1.exe.
  2. Select Custom Install and enable: SIMATIC NET PC Software, SOFTNET-IE RNA, SOFTNET-IE S7 RedConnect, OPC Server.
  3. Reboot when prompted. Confirm s7oiepn.dll and redpn.exe are registered (regsvr32 verification optional).

Step 2 – Configure the two NICs

  1. Open Control Panel → Network and Sharing Center → Change Adapter Settings.
  2. Rename the two NICs to SubNet_A and SubNet_B for clarity.
  3. Assign static IPv4 addresses:
    • SubNet_A: 192.168.10.101 / 255.255.255.0, no gateway, no DNS
    • SubNet_B: 192.168.11.101 / 255.255.255.0, no gateway, no DNS
  4. Disable IPv6 on both adapters (RNA V13 still uses IPv4 only in many firmware revisions).
  5. Disable Windows firewall on these two adapters, or add inbound rules for TCP port 102 (S7) and UDP ports for SIMATIC NET discovery.

Step 3 – Bind RNA

  1. Start SIMATIC NET Configuration → RNA Manager (Start menu → SIMATIC NET → Communication Settings → RNA).
  2. Select Add PRP Interface.
  3. Drag SubNet_A into the Adapter A slot, SubNet_B into Adapter B.
  4. Assign the virtual adapter IP: 192.168.10.200 / 255.255.255.0 (this is the IP WinCC will use).
  5. Click Apply, then Start RNA Service. The service SIMATIC NET RNA Service must be in state Running.
  6. From a command prompt run ping 192.168.10.10 -t (CPU0 CP443-1 IP) and simultaneously pull the SubNet_A cable. Pings must continue with zero loss.

Step 4 – Configure RedConnect in STEP 7 / TIA Portal

  1. Open the S7-400H station in STEP 7 V5.6 (or TIA V16 with S7-400H package).
  2. In NetPro / Devices & Networks, insert an S7 Connection with type S7 Connection High Availability from the WinCC PC (logical partner) to the H-CPU pair.
  3. Enter the Virtual RNA IP (192.168.10.200) as the partner endpoint.
  4. Enable RedConnect on the connection; STEP 7 inserts a second logical S7 connection as standby automatically.
  5. Compile and download to the H-CPU pair and to the PC station (via PC internal station or via S7PCT).

Step 5 – Verify in WinCC

  1. Open the WinCC project in WinCC Explorer / TIA Portal.
  2. In Tag Management → SIMATIC S7 PROTOCOL SUITE → Connections, the S7 connection name from Step 4 must appear with status icon green.
  3. Right-click → Connection Status: verify RedConnect Status = Active and Active Path = LAN A initially.
  4. Force a fault (disconnect LAN A cable). Status must switch to Active Path = LAN B within the configured timeout (default 3 s). Reconnect; status returns to LAN A after the configured recovery delay.

Commissioning Verification

A commissioned S7-400H ↔ WinCC redundant link must pass four scripted checks before plant handover.

Test ID Action Expected Result Pass Criterion
T1 – Baseline No faults induced, view a live WinCC tag from each CPU Values update at configured acquisition cycle (typically 500 ms – 2 s) Zero missed cycles over 5 min
T2 – SubNet A drop Disconnect LAN A patch cord at the patch panel RNA LED state changes to B only; ping continues with 0% loss to virtual IP Loss < 0.01% during fault, recovery within 1 s of reconnect
T3 – SubNet B drop Disconnect LAN B patch cord Symmetric to T2 on the B side Same pass criteria as T2
T4 – H-CPU failover Trigger MASTER-RESERVE switchover in S7-400H (via test mode toggle on CPU) WinCC continues to read values; tag quality remains Good (OPC: 0xC0) Switchover completes within configured RedConnect timeout

Document the timestamp, tag value before/after, and any WinCC alarm raised during T2-T4. The acceptance report should attach the RNA log file (%ProgramData%\Siemens\Automation\RNA\rna.log) and the RedConnect log (%ProgramData%\Siemens\Automation\RedConnect\rc.log) covering the test window.

Troubleshooting Matrix

Symptom Likely Root Cause Diagnostic Step Corrective Action
RNA Manager shows Adapter A/B not bound Driver mismatch; one NIC is HARDNET-class Device Manager → NIC properties → check vendor Replace with SOFTNET NIC (Intel i210 / i350) or CP 1626 in SOFTNET mode
RNA binds but pings show 50% loss One NIC has no link, or duplex mismatch on switch ethtool / NIC advanced properties → Speed & Duplex = 1000 Mbps Full Force 1 Gbps full duplex on both ends; verify cabling
RedConnect status Standby - No Partner S7 connection not downloaded to CPU pair NetPro → right-click H-station → Compile and Download Objects Re-download connection configuration to both H-CPUs
WinCC tag shows Bad Quality only after LAN drop RedConnect not activated on the S7 connection in WinCC WinCC → Connection properties → High Availability tab Enable RedConnect; rebuild WinCC runtime
License error 1026 (ALM) License not visible to the service account ALM → Show Licenses → search for 6GK1711 Re-install license on the actual logged-in user profile or SYSTEM
Virtual adapter IP not pingable from subnet RNA virtual NIC has same MAC as physical NIC → switch MAC flapping RNA Manager → Properties → check LAA (Locally Administered Address) Disable MAC learning on the SCALANCE port for that PC; or assign explicit virtual MAC
CPU redundancy OK but WinCC cannot establish HA connection H-CPU configured as S7-RECONN server but CP 443-1 firmware < V3.0 Web server of CP 443-1 → Firmware version Upgrade CP 443-1 firmware to V3.0.18 or later

Edge Cases and Field-Proven Caveats

  • Multiple VLANs on the same physical NIC: RNA does not support VLAN tagging in V13. Each RNA adapter must be on a single, untagged VLAN.
  • Wireless or USB NICs: Not supported by RNA driver – only wired PCIe NICs with NDIS 6.x drivers.
  • Hyper-V generation 2 VMs: The synthetic NIC is not always recognized; use the legacy network adapter for the two RNA-bound virtual NICs.
  • Antivirus: Some endpoint security products intercept the raw Ethernet frames that RNA uses for duplicate detection. Add the RNA service executable (s7oiepns.exe) to the AV exclusion list.
  • Switch recommendation: Use SCALANCE XC/XB/XR managed switches with PRP option enabled on the relevant ports. Unmanaged switches will work but eliminate the ability to diagnose SubNet-A vs SubNet-B via SNMP.
  • Time synchronization: Both subnets must use the same PTP/NTP source to avoid timestamp drift between LAN-A and LAN-B frames, which can affect S7-OPC sequence numbers during failover.

Comparison: All Three Approaches Side by Side

Aspect RNA + RedConnect (on PC) SCALANCE X204RNA + RedConnect RedConnect only (two IPs)
Redundancy layer Layer 2 (PRP) + Layer 7 (S7) Layer 2 in switch + Layer 7 on PC Layer 7 only
Failover latency Zero (PRP) + S7 reconnect Zero (PRP) + S7 reconnect S7 reconnect only (300 ms – 3 s)
PC NIC count 2 1 or 2 (depends on SCALANCE mode) 2
PC software RNA + RedConnect RedConnect only RedConnect only
Switch hardware Any IE switch (managed recommended) SCALANCE X204RNA Any IE switch
Licenses (per PC) RNA + RedConnect RedConnect only RedConnect only
Recommended for Mission-critical HMI with zero-loss SLA Plants standardizing on SCALANCE Brownfield upgrades without RNA licensing

Reference Standards and Official Documentation

Selection and parameter settings in this article are derived from the official Siemens Software Redundancy for SIMATIC S7 manual and the SIMATIC NET V13 + SP1 release notes. Always cross-check the WinCC / S7-400H manuals for the exact firmware revision in use at the plant.

  • SIMATIC S7 Software Redundancy – Configuration Manual (Siemens Support, entry ID 1137637)
  • IEC 62439-3 (PRP / HSR) – Clause 4 for PRP node and Clause 5 for HSR node behavior.
  • SIMATIC NET V13 + SP1 product release notes – list of supported CP modules and unsupported HARDNET CPs.
  • S7-400H – System Manual (Siemens), Section on S7-RECONN / high-availability S7 connections.
  • SCALANCE X204RNA – Operating Instructions, PRP redundancy box mode description.

What is the difference between SOFTNET-IE RNA and SOFTNET-IE S7 RedConnect?

SOFTNET-IE RNA (6GK1711-1EW13-0AA0) bonds two physical Ethernet adapters into a single PRP virtual adapter at Layer 2 with zero-loss failover (IEC 62439-3). SOFTNET-IE S7 RedConnect (6GK1704-0HB13-0AA0) supervises high-availability S7 connections at Layer 7 to an S7-400H pair, providing automatic S7 reconnect on failure (typically 300 ms – 3 s). For an S7-400H + WinCC plant Siemens recommends installing both, so that the LAN path is lossless (RNA) and the S7 connection is supervised (RedConnect).

Can a SCALANCE X204RNA replace SOFTNET-IE RNA on the WinCC PC?

Yes. SCALANCE X204RNA is a PRP redundancy box. It performs the same Layer-2 PRP bonding function in hardware, so the PC no longer needs SOFTNET-IE RNA installed. The trade-off is that redundancy now starts at the SCALANCE rather than at the PC NIC; a SCALANCE failure is not protected. One RedConnect license (6GK1704-0HB13-0AA0) is still required for the S7 high-availability connection.

Which HARDNET CP modules are NOT supported with SOFTNET-IE RNA V13?

The following HARDNET communications processors are explicitly not supported with SOFTNET-IE RNA V13: CP 1604, CP 1613, CP 1616, CP 1623 and CP 1628. Use SOFTNET-class adapters (on-board Intel NICs, CP 1626 in SOFTNET mode, or PCIe SOFTNET cards) instead, or implement redundancy with RedConnect only (no RNA).

How many licenses are required per WinCC PC?

One SOFTNET-IE RNA license and one SOFTNET-IE S7 RedConnect license per physical PC (catalog numbers above). If WinCC runs inside a virtual machine, one of each is required per VM instance. The licenses are not per-CP or per-network-interface, only per computer. RedConnect in VM environments uses the dedicated VM SKU (6GK1704-0HB13-0AA0).

Does SOFTNET-IE RNA work inside a VMware / Hyper-V VM?

RNA itself is licensed per computer and runs on the host OS; when used inside a VM, two virtual NICs bridged to two host physical NICs must be assigned, and the RNA virtual adapter is created inside the VM. RedConnect has an explicit VM-capable SKU. Each VM needs its own RNA and RedConnect license; the host's licenses cannot be shared with the VM.

Back to blog