Overview
The Siemens SIMATIC S7-300 does not provide a single keystroke or operator action that zeros the entire flag (M) memory and all data block (DB) memory while the CPU is in RUN. A 'clear all' can be performed during a cold restart or factory reset, but at runtime the engineer must execute a block that overwrites the memory range with a defined pattern. The standard system function for this job is SFC21 "FILL" from the Standard Library, which copies the contents of a short source area (the pattern) into a destination area repeatedly until the destination is full. When the source pattern is a single byte or word with value 16#00, SFC21 effectively zeros the destination.
This reference covers the practical implementation of SFC21 on a CPU 314C-2 DP running STEP 7 V5.x, with attention to:
- Correct declaration of the
BLKANY pointer that targets M and DB ranges - Time-out behaviour when the destination block exceeds a few hundred bytes
- Use of SFC20 (BLKMOV) and SFC81 (UBLKMOV) as alternatives
- Operator-triggered execution from the program (input edge, HMI button)
- Verification of the cleared memory via VAT and online watch
Prerequisites
| Item | Detail |
|---|---|
| Controller | SIMATIC S7-300, e.g. CPU 314C-2 DP (MLFB 6ES7 314-6CG03-0AB0 or compatible 6ES7314-6xxx) |
| Firmware | CPU 31xC firmware V2.x or later (FILL is present in every standard S7-300/400 firmware version) |
| Programming tool | STEP 7 V5.5 (or STEP 7 Professional V14+ in TIA Portal with S7-300 selected). The STL examples use STEP 7 V5.5 syntax. |
| Library | 'Standard Library' → 'System Function Blocks' (SFC21 ships with the S7-300 operating system, no install needed) |
| Block containers | OB1 (or any cyclic OB) for unconditional clearing, OB100 (startup) for once-only clearing, or a dedicated FC/FB triggered from the HMI |
| Input trigger (optional) | A digital input, an HMI tag, or a bit in the process image used as a one-shot to call SFC21 |
Confirm SFC21 availability in the project offline view: Program blocks → System blocks → SFC21 'FILL'. If the block is shown as '---' or missing, recompile the system data via PLC → Compile and Download Objects and download the HW Config.
SFC21 'FILL' Technical Details
SFC21 belongs to the IEC 61131-3 group of 'fill' or 'initialize' operations. The S7-300/400 operating system supplies the function block in the Standard Library, and it is callable from any priority class (OB1, OB35, OB82, OB100, etc.) without licensing.
Formal interface
| Parameter | Declaration | Data type (legacy) | Meaning |
|---|---|---|---|
| BVAL | INPUT | ANY | Pointer to the source area whose contents are copied repeatedly into the destination. Typically a single byte or word containing the fill value. |
| RET_VAL | OUTPUT | INT (WORD) | Return value. W#16#0000 on success. Non-zero is an error code. |
| BLK | OUTPUT | ANY | Pointer to the destination memory area to be overwritten. |
The block copies the BVAL content into BLK byte-by-byte (or word-by-word depending on the BVAL declaration) until the BLK length is exhausted. SFC21 does not stop at a DB boundary; the BLK ANY pointer may span multiple DBs only if the underlying data is contiguous in the work memory of the CPU. For S7-300, the maximum BLK length per call is 16 384 bytes (16 KB). Larger targets must be split across multiple SFC21 calls.
RET_VAL error codes
| RET_VAL (W#16#) | Meaning | Corrective action |
|---|---|---|
| 0000 | No error | — |
| 8091 | Destination (BLK) length exceeds the maximum (16 384 bytes) | Split into multiple SFC21 calls of ≤ 16 384 bytes each |
| 8092 | BLK ANY contains an illegal specification (wrong DB, wrong length, etc.) | Recompute length and DB number; ensure the DB exists in the online program |
| 80A1 | BVAL source area invalid (e.g. points to the local L stack in an uninitialised state) | Initialise a temp BYTE/WORD before the call and pass its address as BVAL |
| 80B1 / 80B2 | Source or destination is in the peripheral I/O area; access is not allowed | Restrict SFC21 to M, DB, and Q process-image areas |
| 80B5 | BLK destination is write-protected (e.g. a DB opened with read-only attribute) | Edit the DB properties and re-download the block |
The complete error list is documented in the S7-300/400 System and Standard Functions reference manual, sections describing SFC20, SFC21, SFC81.
Memory Layout on the S7-300
Before writing the SFC21 call, the engineer must know the absolute address ranges that need to be zeroed. For an S7-300, the M area starts at byte 0 and extends to the configured M byte count (default 256 bytes; configurable up to 8192 bytes on most CPU 31xC). Data blocks are addressed by DB number; the default project may have DB1 (or DB2) plus user-created blocks.
| Area | Address syntax (legacy ANY) | Default size | Note |
|---|---|---|---|
| Flag (M) | P#M 0.0 BYTE n | MB0..MB(n-1) | Default 256 bytes, configurable 0..8192 in HW Config → CPU → Addresses |
| Data block | P#DBn.DBX 0.0 BYTE m | Per DB definition | DB must be compiled and downloaded; 'unlinked' or read-only DBs cannot be written |
| Outputs (Q) | P#Q 0.0 BYTE q | 0..8192 | Can be cleared but verify against actuator safety |
The CPU 314C-2 DP supports 64 KB code / 64 KB data work memory on later firmware (FW V3.x); FW V2.x has 32 KB code / 16 KB data. Clearing memory does not change program size but releases the process-image representation. Retentive M or DB variables must be identified before clearing: the S7-300 retains the configured retentive range across POWER OFF / POWER ON, so a runtime SFC21 clear sets those locations to zero only until the next STOP-RUN transition, when retentivity restores the saved values.
Step-by-Step: Clearing M and DB Memory with SFC21
Step 1 – Define the trigger condition
Open OB1 (or a dedicated FC/FB) and declare a local or global bit, e.g. "Clear_Memory_REQ" : BOOL. Drive it from an HMI button or a digital input processed with positive-edge detection:
// STL — edge-detected request from a button
A "DI_Reset_Button" // raw input
FP "Edge_Reset_Trigger" // flag bit, edge memory (BOOL)
S "Clear_Memory_REQ"
For a one-shot automatic clear on warm restart, set Clear_Memory_REQ in OB100 (startup OB):
// OB100 STL
SET
S "Clear_Memory_REQ"
Step 2 – Call SFC21 for the M area
Insert SFC21 'FILL' from the Standard Library. The pattern is a temporary local variable declared as BYTE initialised with B#16#00:
// Declaration in OB1 / FC1 / FB1 TEMP section
VAR
FillByte : BYTE; // value 16#00 used as the pattern
END_VAR
// STL call — clear 256 bytes of M
A "Clear_Memory_REQ"
JCN END_FILL
L B#16#00
T #FillByte
CALL "FILL" ( // SFC21
BVAL := #FillByte,
RET_VAL := "Fill_RET_M",
BLK := P#M 0.0 BYTE 256
);
END_FILL: NOP 0
The ANY pointer P#M 0.0 BYTE 256 clears MB0 through MB255. Increase the length to match the configured M area. Keep the length under 16 384 bytes per call.
Step 3 – Call SFC21 for each DB
Each DB must be cleared individually. The engineer can use a loop with a STAT variable for the DB number, or hard-code each DB. Example with three data blocks (DB10, DB11, DB20):
// STL — clear DB10 (200 bytes), DB11 (50 bytes), DB20 (400 bytes)
CALL "FILL" (
BVAL := #FillByte,
RET_VAL := "Fill_RET_DB10",
BLK := P#DB10.DBX 0.0 BYTE 200
);
CALL "FILL" (
BVAL := #FillByte,
RET_VAL := "Fill_RET_DB11",
BLK := P#DB11.DBX 0.0 BYTE 50
);
CALL "FILL" (
BVAL := #FillByte,
RET_VAL := "Fill_RET_DB20",
BLK := P#DB20.DBX 0.0 BYTE 400
);
Use a single #FillByte instance for all calls; SFC21 reads it once and repeats the pattern internally.
Step 4 – Limit the call to one cycle (avoid time-outs)
On CPU 314C-2 DP, OB1 runs at the configured cycle time (default 150 ms). A single SFC21 call clearing 16 KB can exceed the OB1 cycle, causing a priority class 26 'OB1 cycle time exceeded' diagnostic event if the cyclic OB has a short watch-dog. Mitigations:
- Run the clear in OB100 (startup) where the cycle watchdog is suspended
- Split the clear into slices processed in OB35 (cyclic interrupt)
- Temporarily extend the OB1 maximum cycle time in HW Config → CPU properties → Cycle / Clock Memory
- Trigger the clear only on operator command and gate with a 'Clear in progress' bit to avoid repeating the fill every scan
Step 5 – Reset the request
Reset Clear_Memory_REQ when the last SFC21 call returns W#16#0000:
// STL
A "Clear_Memory_REQ"
JCN NO_RESET_REQ
L "Fill_RET_DB20" // return of the last SFC21 call
L W#16#0
<>I
JC NO_RESET_REQ // wait until all calls return 0
CLR
S "Clear_Memory_DONE" // completion flag for HMI
R "Clear_Memory_REQ"
NO_RESET_REQ: NOP 0
Ladder Logic Equivalent
For engineers maintaining FBD/LAD code, the same logic is built as a network with a normally-open contact on Clear_Memory_REQ driving the SFC21 block. The BVAL input is wired to a memory byte initialised with 0; the BLK input is entered directly as the ANY pointer (e.g. P#M 0.0 BYTE 256). LAD supports SFC/SFB boxes directly; FBD uses a standard block instance. The DB blocks in the network should be placed in the same network so the execution order is deterministic; avoid interleaving FILL calls with logic that depends on the DB content mid-clear.
Alternative Methods
SFC20 'BLKMOV' (block move)
SFC20 copies a contiguous source area to a destination of identical length. To zero memory with BLKMOV, declare a temporary WORD holding W#16#0000 and use BLKMOV with that WORD as source and the M/DB region as destination. BLKMOV also respects the 16 KB limit per call. Use BLKMOV if you also need to copy non-zero patterns (e.g. preset a recipe from a saved block).
SFC81 'UBLKMOV' (uncoordinated block move)
SFC81 performs the same copy as SFC20 but without coordinating updates to the process image. UBLKMOV is preferred when the destination is a peripheral output (PAA) that should not cause an intermediate 'all outputs high' glitch when the source is shorter than the destination. SFC81 has the same ANY restrictions as SFC20/SFC21.
Data block re-initialisation
If the goal is to restore a DB to its initial (load) values, STEP 7 provides a 'Initialise Data Block' command (right-click DB in SIMATIC Manager → 'Initialise Data Block'). This re-loads the values defined in the offline program. This is faster than byte-wise zeroing for very large blocks but requires the offline project to be in the correct state and briefly stops the data block while the initial values are written.
- Open SIMATIC Manager → S7 Program → Blocks
- Right-click the DB → 'Initialise Data Block'
- Confirm the prompt (this writes the current offline values to the CPU)
- Alternative: download the entire S7 program (CPU STOP required)
CPU 314C-2 DP Specific Notes
The CPU 314C-2 DP supports the same SFC21 call interface as any other S7-300 CPU. Specific considerations:
- Work memory 64 KB code / 64 KB data on later firmware (FW V3.x); earlier FW V2.x has 32/16 KB. Plan the use of temporary variables accordingly and avoid 16 KB ANY in FB instances that already use significant static data.
- The integrated DP interface and onboard I/O occupy M areas; consult HW Config → CPU → Addresses to see the exact M bytes used by the onboard digital and analogue I/O. Avoid clearing bytes that map to live inputs or onboard outputs that feed actuators.
- Onboard counters and timers map to their own SFBs (SFB36..SFB39 for IEC counters; SFB40..SFB43 for IEC timers). SFC21 must not be used to clear the C/T area; it does not address it, but the engineer should be aware of the address gap and the system-side M bytes reserved by the CPU firmware.
Refer to the S7-300 CPU 31xC and 31x Operating Instructions for cycle-time, retentivity, and integrated I/O behaviour.
Verification
- Trigger the clear. Set the input or HMI button. Confirm that the OB enters the SFC21 call path using STEP 7 online → 'Monitor/Modify' on the request bit.
-
Watch RET_VAL. All return values should reach
W#16#0000within one cycle (for a 256-byte M area and small DBs) or several cycles (for a multi-kilobyte DB). - Inspect the memory. Open a Variable Table (VAT) with the M and DB addresses of interest. Force 'Monitor' mode; every entry should read 0.
- Check the HMI acknowledgement. The 'Clear_Memory_DONE' bit should latch on, providing operator feedback.
- Review the diagnostic buffer. CPU → Diagnostic buffer. There should be no 'OB1 cycle time exceeded' event during the clear. If there is, apply one of the mitigations from Step 4 above.
- Confirm retentivity state. On a STOP-RUN transition, observe whether previously retentive M bytes or DB variables return to non-zero values. If so, the retentive range must be reduced in HW Config or in the DB properties.
Troubleshooting Matrix
| Symptom | Likely cause | Remedy |
|---|---|---|
| RET_VAL = W#16#8091 | BLK length > 16 384 bytes | Split into multiple SFC21 calls |
| RET_VAL = W#16#8092 | Illegal ANY pointer (wrong DB number, wrong offset) | Verify DB number and offset; ensure the DB is downloaded |
| RET_VAL = W#16#80A1 | BVAL points to local L stack in an uninitialised state | Initialise FillByte with L B#16#00 / T #FillByte before CALL; do not pass an L-stack variable |
| RET_VAL = W#16#80B1 | BLK in peripheral area | Restrict to M / DB / Q process image |
| DB still contains non-zero values after clear | DB is retentive; values restored on next STOP-RUN | Disable retentivity in DB properties or clear again on each warm restart |
| 'OB1 cycle time exceeded' after the clear | Clear runs in fast OB1 and exceeds the 150 ms watch-dog | Run in OB100 / OB35 or extend the OB1 cycle watch-dog in HW Config |
| Clear button has no effect | Edge detection not wired; or Clear_Memory_REQ is reset by another part of the program |
Verify edge bit; check for competing R statements |
| Only part of the M area is cleared | BLK length smaller than the configured M area | Recompute BLK length; check HW Config → CPU → 'Address' for actual M byte count |
| SF LED on, diagnostic buffer shows area length error | ANY pointer targets a DB whose actual online length is smaller than declared | Re-compile and re-download the DB; check for online/offline size mismatch |
Retention and Restart Behaviour
After SFC21 clears the M area and the DBs, the values remain zero only as long as the CPU stays in RUN. On the next STOP / RUN transition:
- Retentive M bytes (defined in HW Config → CPU → 'Retentivity' → M area from byte .. to byte ..) are restored from the retentive memory.
- Non-retentive DB variables are initialised from the DB's initial values (not necessarily zero unless the offline initial value is zero).
- Retentive DB variables are restored from the retentive memory.
If the application requires that the cleared zero state persist across restarts, set every M byte and every DB variable as non-retentive, or clear the retentive range in OB102 (cold restart) before user code runs. Note that OB102 is only executed on a cold restart (CRST); after a warm restart (WRST) or hot restart (HRST, only on S7-400) the retentive range is automatically restored before the user OBs run.
Performance Numbers (typical, CPU 314C-2 DP FW V3.x)
| Block size (bytes) | Approximate SFC21 execution time | Note |
|---|---|---|
| 256 | < 1 ms | Negligible |
| 1024 | 2..3 ms | Fits in OB1 default cycle |
| 8192 | 15..20 ms | May push OB1 close to 150 ms watch-dog if combined with other code |
| 16384 (max per call) | 30..40 ms | Run in OB100 / OB35 for safety |
These are order-of-magnitude figures; actual times depend on scan load, communication (PG/OP, S7 communication, DP cycle), and OB1 priority assignment. Always verify with the on-line 'Cycle time' statistics after commissioning and check that the maximum OB1 cycle remains within the configured watch-dog.
Field-Proven Patterns
Pattern A — Operator-triggered one-shot
Most common. Edge-detected HMI button, runs SFC21 once, latches the 'Clear_Memory_DONE' flag, and is suppressed by the operator until the next event. Watch the request bit to ensure it is not set on every scan.
Pattern B — Mode-change clear
Clear M and DB ranges when the machine transitions from RUN-AUTO to RUN-MANUAL, or from a recipe change. Gate the SFC21 call with a 'Mode changed' edge bit. The advantage: deterministic — it runs only when the operator initiates a mode change, not on every restart.
Pattern C — Sliced clear in OB35
For DBs larger than 16 KB, call SFC21 repeatedly in OB35 with a different BLK slice each time (e.g. 4 KB per call, 4 calls for a 16 KB block). A counter in STAT tracks the next slice. The cyclic interrupt OB35 runs independently of OB1, so OB1 cycle time is preserved.
// OB35 STL — sliced clear of a 16 KB DB using 4 slices of 4 KB
L "Clear_DB_Slice_Counter" // INT, 0..3
JL END_SLICE
JU SL0
JU SL1
JU SL2
JU SL3
SL0: CALL "FILL" (BVAL := #FillByte, RET_VAL := "Fill_RET_SL0", BLK := P#DB100.DBX 0 .0 BYTE 4096);
JU INC_SLICE
SL1: CALL "FILL" (BVAL := #FillByte, RET_VAL := "Fill_RET_SL1", BLK := P#DB100.DBX 4096 .0 BYTE 4096);
JU INC_SLICE
SL2: CALL "FILL" (BVAL := #FillByte, RET_VAL := "Fill_RET_SL2", BLK := P#DB100.DBX 8192 .0 BYTE 4096);
JU INC_SLICE
SL3: CALL "FILL" (BVAL := #FillByte, RET_VAL := "Fill_RET_SL3", BLK := P#DB100.DBX 12288.0 BYTE 4096);
L 0
T "Clear_DB_Slice_Counter"
S "Clear_Memory_DONE"
JU END_SLICE
INC_SLICE: L "Clear_DB_Slice_Counter"
+ 1
T "Clear_DB_Slice_Counter"
END_SLICE: NOP 0
What is the difference between SFC20 'BLKMOV' and SFC21 'FILL'?
SFC20 copies a single source block to a destination of identical length. SFC21 copies a short source pattern (BVAL) repeatedly to fill a longer destination (BLK). Use SFC21 when you want to write the same value (e.g. zero) across a large range with minimal declaration, and SFC20 when source and destination are the same length or you need to copy distinct source bytes.
Can SFC21 clear retentive memory permanently?
No. SFC21 writes zero into the process image, but the CPU restores retentive bytes from the retentive memory on the next STOP-RUN transition. To make the cleared state permanent, mark the area as non-retentive in HW Config or in the DB properties, or clear in OB102 (cold restart) before user OBs run.
Why do I get RET_VAL W#16#8091 when clearing a 20 KB block?
SFC21 accepts a maximum BLK length of 16 384 bytes per call on S7-300. Split the destination into two ANY pointers of 16 384 and 6 144 bytes and call SFC21 twice, or run a sliced clear in OB35. The same 16 KB limit applies to SFC20 and SFC81.
Is it safe to call SFC21 from OB1 every scan?
Yes, technically — the values remain zero — but it adds avoidable scan load and, on borderline cycle time, can trigger the OB1 watch-dog. Gate the call with a request bit and run it once per operator action or once in OB100 (startup). For large blocks, use OB35 (cyclic interrupt) and slice the work.
Which Siemens KB article covers SFC20 / SFC81 / SFC21 considerations?
Siemens Support entry ID 22297151 ('What should you watch out for when you use the SFC20 BLKMOV, SFC81 UBLKMOV or SFC21 FILL blocks?') is the canonical reference and lists the most common runtime pitfalls, including the 16 KB length limit and the prohibition against peripheral-area access.