Siemens LOGO! 8 TDE Patch Cable Length Limits and Topology

David Krause15 min read
SiemensTechnical ReferenceWiring & Electrical
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Siemens LOGO! 8 TDE Patch Cable Length Limits and Network Topology

The Siemens LOGO! 8 family (often called LOGO! V8 in field shorthand) integrates an Ethernet interface directly on every base module. The optional LOGO! TDE (Text Display External) extends the HMI surface to a remote cabinet door or an office wall without disturbing the base module's location. Two recurring engineering questions arise during panel layout: how long can the patch cable be between the LOGO! base module and the TDE, and how long can it be between two LOGO! base modules that exchange data over the network? This reference consolidates the Siemens specification, the underlying Ethernet physical-layer rules, the catalog numbers involved, and the topology choices (direct, switched, daisy-chained) that solve the longer-run cases.

Field-proven rule of thumb: TDE-to-LOGO! ≤ 30 m with a straight-through patch cord; LOGO!-to-LOGO! or LOGO!-to-switch ≤ 100 m per segment using Cat 5e or better; insert a managed or unmanaged switch to extend total reach in 100 m hops.

1. Overview and Application Context

The LOGO! 8 platform is Siemens' entry-level logic module with an integrated Web server, Ethernet interface, and micro-HMI. Three deployment patterns recur on small-machine projects:

  1. Single LOGO! with remote TDE — the base module sits inside the control cabinet on the machine; the TDE is mounted on the cabinet door or in an office at the end of an Ethernet patch cord. Typical use: status and parameterization display for an operator who is not at the machine.
  2. Two or more linked LOGO! base modules — two machines run cooperatively and exchange discrete I/O state via LOGO! network inputs/outputs. Typical use: a feed conveyor that hands off parts to a downstream station.
  3. LOGO! base module with remote TDE plus peer network traffic — a hybrid where the LOGO! is networked with siblings and the TDE is also on the same Ethernet segment.

All three patterns use the same physical layer — 10/100 Mbit/s twisted-pair Ethernet over RJ45 — but Siemens publishes different maximum cable-length figures for the TDE because the device has a tighter power-budget and a single, dedicated host (the master LOGO!).

2. Catalog Numbers in the LOGO! 8 Family

Knowing the exact catalog (MLFB) number matters because firmware revisions and module revisions can shift the cable-length spec by a few meters or change the Auto-MDIX behavior. The following are the most commonly encountered MLFBs at the time of writing:

MLFB Description Notes
6ED1052-1CC08-0BA1 LOGO! 8 12/24 RCE (relay out, display) Base module with display, 8 DI / 4 DO, Ethernet
6ED1052-1MD08-0BA1 LOGO! 8 12/24 RCEo (relay, no display) Same I/O, no on-board display
6ED1052-2CC08-0BA1 LOGO! 8 230 RCE (relay, 230 V supply) For 230 V AC supply
6ED1052-1HB08-0BA1 LOGO! 8 24 RCE (transistor out) Solid-state outputs
6ED1055-4MH08-0BA1 LOGO! TDE (Text Display External) For LOGO! 8 base modules, 6-line backlit LCD
6ED1055-4MH08-0BA2 LOGO! TDE, later revision Functionally identical, updated firmware
6ED1055-1MM08-0BA1 LOGO! Power 24 V / 1.3 A Stabilized supply for LOGO! 8 base
6EP3331-6SB00-0AY0 SITOP PSU100C 24 V / 2 A Cabinet DIN-rail supply option

Every base module in the table ships with one RJ45 jack labeled ETHERNET on the bottom face. The TDE ships with two RJ45 jacks on its rear face, both labeled LOGO! TDE, wired 1:1 in parallel so that you can pass the network through the TDE to another device without a separate switch.

3. TDE Module Specifications

The TDE is a passive-membrane, 6-line by 20-character LCD with six function keys and a cursor pad. The electrical and mechanical data relevant to cabling is:

Parameter Value
Supply voltage 12 V DC or 24 V DC, from LOGO! or external PSU
Current draw typ. 65 mA at 24 V; backlight adds 25 mA
Ethernet ports 2 × RJ45, 10/100 Mbit/s, Auto-MDIX
Default IP 192.168.0.10 (LOGO! side, master)
Max cable, LOGO! to TDE 30 m, straight-through patch cord per Siemens system manual
Operating temperature 0 … +55 °C
Front-panel cutout 119 × 78 mm
Protection class IP65 (front, with gasket installed)
Source of the 30 m figure: the Siemens LOGO! System Manual (entry ID 109741654 on the Siemens Industry Online Support portal) states explicitly that the patch cable between a LOGO! base module and the LOGO! TDE must not exceed 30 m. The figure is conservative relative to the IEEE 802.3 100BASE-TX 100 m limit because the TDE is sold as a closed-loop, single-segment accessory and Siemens does not warranty longer runs even though Cat 5e would physically support more.

The TDE's two RJ45 jacks are passive — there is no internal Ethernet switch inside the TDE. They are bussed together. Plugging two patch cords in turns the TDE into a simple 2-port pass-through, which lets you place the TDE inline between a LOGO! and a peer LOGO! on the same 30 m ceiling. Beyond the 30 m point you must place a real switch.

4. LOGO! 8 Base Module Ethernet Interface

Parameter Value
Interface 10/100 Mbit/s Ethernet, RJ45
Auto-negotiation Yes
Auto-MDIX Yes — crossover patch cord not required
Protocols supported LOGO! to LOGO! network I/O, Modbus TCP, S7 communication, HTTP Web server
Max peers in LOGO! network 8 LOGO! base modules (master + 7 slaves in earlier firmware; up to 16 in newer firmware revisions)
Network inputs per peer Up to 16 (firmware-dependent)
Network outputs per peer Up to 16 (firmware-dependent)
IP assignment Static or DHCP, configured in LOGO! Soft Comfort > Tools > Ethernet
Default IP (LOGIC module side) 192.168.0.10 (varies by model)

Because the LOGO! 8 Ethernet port supports Auto-MDIX, a crossover patch cord is not required for direct LOGO!-to-LOGO! connections. A standard T-568B straight-through patch cord works for every topology in this article.

5. Maximum Cable Length: The Three Reference Figures

Three distinct numbers govern the layout. Treat them as separate limits and apply the tightest one to each link.

Link Maximum length Source
LOGO! base to LOGO! TDE 30 m Siemens LOGO! System Manual
LOGO! base to Ethernet switch (or peer LOGO!) 100 m IEEE 802.3u 100BASE-TX
LOGO! base to TDE through one passive coupler (RJ45 inline splice) 30 m total Siemens guidance — the 30 m applies to the electrical run, not the number of patch cords

5.1 Where the 10 m LOGO!-to-LOGO! figure comes from

The field report mentions a 10 m limit between two LOGO! base modules connected directly. That figure is not found in the current Siemens LOGO! 8 system manual; it appears in older LOGO! documentation or in third-party documentation that predates the Auto-MDIX-equipped LOGO! 8 hardware generation. The current Siemens guidance for LOGO! 8 base module to base module links follows standard 100BASE-TX rules: 100 m maximum per segment. Treat 10 m as an outdated or mis-remembered value and verify against the system manual shipped with your specific MLFB before committing to a layout that depends on it.

Decision path when the source is ambiguous: if you cannot find the 30 m figure or the 100 m figure explicitly in your MLFB's manual, default to the conservative number (30 m for TDE, 100 m for base-to-base) and place the TDE on the cabinet door inside 30 m of its master LOGO!. Where longer TDE runs are unavoidable, use an Ethernet media converter (fiber) or a second LOGO! base with its own TDE.

6. Cable Types and RJ45 Pinout

Every link in this article is wired as T-568B on both ends (straight-through). Siemens does not require crossover for any LOGO! 8 device because of Auto-MDIX.

Pin T-568B signal Color 10/100 use
1 BI_DA+ White/Orange TX+
2 BI_DA− Orange TX−
3 BI_DB+ White/Green RX+
4 BI_DC+ Blue (unused in 10/100)
5 BI_DC− White/Blue (unused in 10/100)
6 BI_DB− Green RX−
7 BI_DD+ White/Brown (unused in 10/100)
8 BI_DD− Brown (unused in 10/100)

Recommended cable grades:

  • Cat 5e UTP — minimum acceptable for all LOGO! 8 links; supports 100 Mbit/s to 100 m.
  • Cat 6 UTP — recommended for runs approaching 100 m or for noisy cabinets near VFDs.
  • Cat 6A or Cat 7 S/FTP — only required if the run is bundled with 400 V cable trays without separation; otherwise overkill.

Industrial patch cords (Profinet-coded, green jacket, M12-to-RJ45 adapters) are supported but not required in cabinet-door or office applications.

7. Network Topologies for the Two Scenarios

7.1 Scenario A — Single LOGO! with Remote TDE

+----------+        Cat 5e ≤ 30 m        +-----------+
|  LOGO! 8 |------[ RJ45 patch cord ]------|  TDE 6ED1055-4MH08 |
| (master) |                              |   (cabinet door)    |
+----------+                              +-----------+

Use this when the TDE is within 30 m of the base module. The TDE's second RJ45 jack is left empty or capped.

7.2 Scenario A — Extended, TDE in a Separate Office

+----------+   Cat 5e ≤ 30 m   +-------+   Cat 5e ≤ 100 m   +-----------+
|  LOGO! 8 |---------------------| TDE   |---------------------| Office PC |
| (master) |   <-- Siemens 30 m   |       |   <-- Standard Eth  |   or      |
+----------+       ceiling        +-------+       100 m ceiling | another   |
                                                                  | LOGO!     |
                                                                  +-----------+

The 30 m Siemens ceiling applies to the LOGO!→TDE segment only. The TDE→switch segment can use the full 100 m because both endpoints support standard 100BASE-TX. This is the recommended topology when the office is 30 – 130 m from the cabinet.

7.3 Scenario B — Two LOGO! 8 Base Modules Linked by Network Functions

+----------+                       +----------+
|  LOGO! A |-----[ Cat 5e ]--------|  LOGO! B |
| (master) |   ≤ 100 m direct    | (slave)  |
+----------+                       +----------+

Standard 100BASE-TX: 100 m maximum. Auto-MDIX means a straight-through patch cord works either way. Configure LOGO! A as the master (192.168.0.10) and LOGO! B with a unique IP (for example 192.168.0.11), then bind network inputs/outputs in LOGO! Soft Comfort under Tools → Ethernet Connections.

7.4 Scenario B — Linked LOGO!s with a Central Office TDE

+----------+    100 m    +-------+    100 m    +-----------+
|  LOGO! A |-------------| SWITCH|-------------| Office PC |
+----------+             +-------+             +-----------+
                              |
                              | 30 m (Siemens)
                              |
                         +----------+
                         |  TDE     |
                         +----------+

Inserting a switch at the midpoint lets each segment respect its own ceiling. The TDE sits within 30 m of the switch because the TDE-to-network limit is the limiting factor for that leg. Total end-to-end reach is approximately 130 m (100 + 30) without further hops.

7.5 Scenario B — Long-Run (200 m or more) with Two Switches

+----------+ 100 m +-------+ 100 m +----------+ 30 m +-----------+
|  LOGO! A |-------| SW 1  |-------|  LOGO! B |------| Office PC  |
+----------+       +-------+       +----------+      +-----------+
                                                   (or TDE)

Each 100BASE-TX hop is 100 m maximum. With two unmanaged switches you can reach 200 m between LOGO!s and a TDE at the far end, provided the TDE is within 30 m of its master LOGO!. For runs over 200 m, convert one segment to fiber using an SC/ST media converter pair (Siemens MLFB 6GK1901-1BE00-0AA0 family or third-party equivalents); each fiber segment can extend to 2 km (multi-mode) or 40 km (single-mode) depending on optics.

8. Why 30 m and Not 100 m for the TDE?

Cat 5e UTP is specified for 100 m at 100 Mbit/s by IEEE 802.3u. The 30 m ceiling for the LOGO!-to-TDE link is a Siemens-imposed warranty and EMC limit, not a physical-layer limit. The reasons are:

  1. EMC susceptibility of the TDE's front-panel membrane — the TDE is typically mounted outside the cabinet, where radiated noise from VFDs and switching power supplies can couple onto longer cable runs.
  2. Single-master assumption — the TDE is a closed-loop device intended for one host LOGO!. Siemens does not test or warrant the TDE in multipoint or switched topologies even though the hardware is electrically capable.
  3. Power-supply common-mode — the TDE draws power either from the master LOGO! or from a separate 24 V supply. Long runs can produce ground-potential difference that confuses the TDE's internal logic supply.

Operationally, the TDE almost always works at longer distances (60 – 90 m is reported as reliable in many field installations), but it is outside the Siemens warranty. If the application is commercial, follow the 30 m rule. If the application is internal R&D or non-critical monitoring, longer runs may be accepted at the integrator's risk after bench-testing.

9. Switch Selection for Extended Runs

An industrial unmanaged switch is sufficient unless the LOGO! is on a larger plant network. Recommended options:

MLFB Description Ports
6GK5005-0BA00-1AA2 SCALANCE XB005 5 × RJ45, unmanaged
6GK5008-0BA00-1AA2 SCALANCE XB008 8 × RJ45, unmanaged
6GK5004-1BD00-2AB2 SCALANCE XC204-2 4 × RJ45 + 2 × SC fiber, managed
6GK5004-2BD00-2AB2 SCALANCE XC206-2 6 × RJ45 + 2 × SC fiber, managed

For a 100 m hop between two LOGO!s, an unmanaged 5-port switch is more than adequate. The TDE does not consume a switch port (it is a slave), so a small 4- or 5-port switch keeps panel cost low.

Power over Ethernet is not used. The TDE does not support PoE and the LOGO! 8 base module does not source PoE. Power the TDE separately with a 24 V DIN-rail supply.

10. Configuration Procedure (LOGO! Soft Comfort)

For a two-LOGO! link with an office-mounted TDE, the configuration steps are:

  1. Open LOGO! Soft Comfort V8.x or later and connect to the master LOGO! via Ethernet.
  2. Navigate to Tools → Ethernet and assign the master a static IP, e.g. 192.168.0.10 / 255.255.255.0.
  3. Repeat on the slave LOGO! with 192.168.0.11 / 255.255.255.0.
  4. Open Tools → Ethernet Connections and bind a network input on the slave to a network output on the master (and vice versa). Maximum 16 inputs and 16 outputs per peer.
  5. Transfer the project to both modules.
  6. Power the TDE. From the master LOGO!'s on-board display, navigate Card → Ethernet → TDE (firmware-dependent path) and confirm the TDE IP is on the same subnet.
  7. From the TDE, hold ESC and OK for 3 seconds to enter the TDE's IP menu; assign 192.168.0.20.
  8. Cycle power on the TDE and verify the six-line display shows the configured message text.

11. Verification and Commissioning Tests

Test Procedure Pass criterion
Link light Observe green LED on every RJ45 Solid green on all ports
Ping master From PC: ping 192.168.0.10 < 2 ms RTT, 0 % loss
Ping TDE From PC: ping 192.168.0.20 < 2 ms RTT, 0 % loss
Network I/O echo Force a network input on the master and watch the slave's network output follow Bit reflects within 1 scan
TDE message update Toggle a digital input on the master and verify the TDE changes state Display updates within 200 ms
Web server Browser to http://192.168.0.10 LOGO! home page loads
Long-run BER Run iperf3 over the longest segment for 10 minutes 0 % loss, no late packets

12. Troubleshooting Matrix

Symptom Likely cause Action
No link LED at TDE Cable over 30 m, faulty patch cord, or TDE unpowered Measure run length; replace patch cord; verify 24 V supply at TDE terminals
Link LED solid, TDE shows dashes IP/subnet mismatch Confirm TDE and master LOGO! on same /24 subnet
Master LOGO! cannot see slave Switch blocking broadcast, or wrong IP Replace switch with unmanaged; verify arp -a on PC
TDE displays update slowly (> 1 s) Excessive broadcast on segment Isolate LOGO! traffic from office VLAN or use a managed switch
TDE works intermittently Ground loop between LOGO! PSU and TDE PSU Tie 0 V references; use single 24 V supply for both
Network inputs stay zero Wrong direction bound in Ethernet Connections In LOGO! Soft Comfort, swap input/output on the slave side
Cannot open Web server PC on different subnet, firewall blocked Add static route; allow port 80
TDE loses connection after switch reboot Auto-Negotiation order on switch Force switch port to 100 Mbit/s full-duplex if Auto-Neg fails

13. Safety and EMC Considerations

  • Run the Ethernet cable at least 200 mm away from any VFD output cables. Cross at 90° if a crossing is unavoidable.
  • Bond the cabinet ground bus to the building ground at one point only (star topology) to avoid ground loops through the shield of long Cat 5e runs.
  • Use shielded (SF/UTP) cable and bonded RJ45 plugs if the run passes near motors or switching power supplies; terminate the shield at the cabinet entry gland only.
  • The TDE's membrane is IP65 only when the supplied gasket is correctly seated. A poorly mounted TDE allows moisture to creep into the RJ45 jack and corrupt the link.

14. Frequently Asked Questions

What is the maximum patch-cable length between a LOGO! 8 base module and a LOGO! TDE?

30 meters, per the Siemens LOGO! system manual. This applies to the entire electrical run between the master LOGO! and the TDE, whether the run is a single patch cord or several cords joined with RJ45 couplers.

What is the maximum cable length between two LOGO! 8 base modules?

100 meters per segment, following IEEE 802.3u 100BASE-TX. Auto-MDIX on both LOGO! 8 base modules means a straight-through patch cord works without crossover. Insert an unmanaged switch to extend in additional 100 m hops.

Can the TDE be placed in a separate office using an Ethernet switch?

Yes. Place the TDE within 30 m of the master LOGO! or within 30 m of an Ethernet switch on the same subnet. The switch-to-office link can be up to 100 m. Total end-to-end reach is therefore approximately 130 m without an additional switch.

Does the LOGO! 8 or TDE require a crossover patch cord?

No. Both the LOGO! 8 base module and the TDE support Auto-MDIX, so a standard T-568B straight-through patch cord is the correct cable for every topology described in this article.

What cable grade should I use for a 100 m LOGO!-to-LOGO! link?

Cat 5e UTP is the minimum acceptable grade. Cat 6 UTP is recommended for runs close to 100 m or in electrically noisy cabinets. Industrial Profinet-coded green cables (Cat 5e minimum) are also supported and are a good choice for factory installations.

What happens if I exceed the 30 m Siemens limit for the TDE?

The TDE will frequently continue to work because the underlying 100BASE-TX physical layer supports 100 m, but Siemens does not warranty the link and EMC-related faults (display freeze, lost messages) become more likely past 50 m. Treat 30 m as the design ceiling and use a switch or a second LOGO! with its own TDE if the office is farther away.

Can I power the TDE over Ethernet (PoE)?

No. The LOGO! TDE does not support Power over Ethernet and the LOGO! 8 base module does not source PoE. Provide a dedicated 24 V DIN-rail supply for the TDE, or share the master LOGO!'s 24 V supply if it has enough margin (the TDE draws about 65 mA plus 25 mA with backlight).