Siemens LOGO! AM2 Module Destroyed: 4-20mA Wiring Error Diagnosis

David Krause12 min read
I/O ModulesSiemensTroubleshooting
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Siemens LOGO! AM2 Module Destroyed: 4-20mA Wiring Error Diagnosis and Recovery

When a Siemens LOGO! 8 AM2 analog input module (order number 6ED1055-1MA00-0BA2) is wired incorrectly to a 4-20 mA pressure transmitter or test source, the input channels can be destroyed within seconds. This reference documents the field failure mode reported on the Siemens support portal (entry ID 23425009), explains the root cause, and gives a step-by-step procedure for safe wiring, configuration, and verification.

Field scenario: A maintenance technician tested a new AM2 module by connecting a 24 V DC power supply through a discrete resistor to one of the analog inputs and measured 8 mA of loop current. After a few seconds the input stopped conducting. The technician moved to the second input; it failed identically. Both AI channels and the module base were rendered inoperable.

1. Affected Product and Identification

The component in this failure case is the LOGO! 8 AM2 expansion module, not the S7-200 EM modules. Confirm the part before applying any of the corrective steps below.

Attribute Value
Siemens order number (MLFB) 6ED1055-1MA00-0BA2
Designation LOGO! 8 AM2 — analog input expansion
Number of inputs 2 (AI1, AI2)
Compatible base LOGO! 8 BM (6ED1052-***08-0BA*) and later
Configuration tool LOGO! Soft Comfort V8.0 and later
Manual entry LOGO! 8 System Manual (109741041)

2. Symptoms and Field Observations

The reported failure presents a characteristic pattern that makes it possible to diagnose without bench instrumentation:

  1. Initial apparent success: When 24 V is applied through a current-limiting resistor, the meter briefly reads the expected current (8 mA in the case reported).
  2. Sudden loss of current: Within 1-5 seconds the loop current drops to zero, even though the supply voltage is still present and the external wiring is intact.
  3. Channel-to-channel propagation: Moving the test wiring to the second input reproduces the failure, indicating a module-level design issue rather than a single channel fault.
  4. Module base no longer recognized: After the event, the LOGO! BM either ignores the AM2 or reports a missing/defective expansion on the display.
Distinguishing symptom: If only the AI channel is dead and the BM still recognizes the AM2, the input protection has likely blown only the input shunt/protection network. If the BM reports the AM2 missing entirely, the internal 5 V/logic supply of the AM2 is also shorted — replace the module, do not attempt repair.

3. Root Cause Analysis

The Siemens community thread (entry 23425009) and the responder's clarification are the key diagnostic clues. The component the technician believed was a current-limiting resistor is, on the LOGO! AM2, an internal PTC fuse / protection element. The actual sequence that destroys the module is:

  1. The technician connects 24 V DC directly to the AM2 input terminal, in series with an external resistor sized for the loop current.
  2. The AM2 input is software-configured (or default-configured) for 0-10 V voltage mode, giving an input impedance of approximately 76 kΩ.
  3. Because the LOGO! 8 AM2 uses a single physical terminal block for voltage and current modes, the internal burden resistor is present at all times.
  4. When 24 V is forced into a voltage-mode input, the protection network (PTC + clamp) conducts heavily. The PTC heats and opens — appearing as "the resistor blew."
  5. If the 24 V is sustained for more than a few hundred milliseconds, the input clamp Zener/transorb is driven into thermal runaway, shorting the input bus internally.
  6. Once the input bus is shorted, the BM's 5 V expansion rail is pulled down, which is why the entire module drops off the backplane and the second channel cannot be used either.

3.1 Why 8 mA Was Measured Before Failure

The measured 8 mA is consistent with the AM2's input protection network during the first few hundred milliseconds. The math:

Vsupply = 24 V, Rext = 3 kΩ (technician's resistor), I = V / (Rext + Rprotection)

For 8 mA: Rext + Rprotection = 24 V / 0.008 A = 3 000 Ω, which implies Rprotection ≈ 0 Ω while the PTC is in its low-resistance (cold) state. The PTC then heats, opens, and the current collapses. The same thermal event destroys the silicon protection behind it.

4. AM2 Module Technical Specifications

Parameter Voltage mode (0-10 V) Current mode (0/4-20 mA)
Input range 0-10 V DC 0-20 mA or 4-20 mA
Input impedance 76 kΩ typical 250 Ω burden (internal)
Maximum overrange (no damage) 30 V DC continuous 30 mA continuous
Resolution 10 bits (0-1000 normalized) 10 bits (0-1000 normalized)
Conversion time ~50 ms per active channel ~50 ms per active channel
Configuration LOGO! Soft Comfort, AI block properties LOGO! Soft Comfort, AI block properties
Terminal used U+ (or I+), M (common) I+, M (common)
Galvanic isolation No (single-ended, M shared) No (single-ended, M shared)
Critical constraint: The AM2 has no galvanic isolation between AI1 and AI2. Both channels share the M terminal. Connecting two separately powered 4-20 mA transmitters without isolating them creates a ground loop that will bias the readings and may damage the inputs.

5. Correct 4-20 mA Wiring Topology

The AM2 expects a passive current input: the transmitter drives the loop, and the AM2's internal 250 Ω burden converts the current to a measurable voltage. You do not need an external burden resistor, and you do not apply 24 V across the input.

24 V DC Supply PSU +24V / 0V 4-20 mA Pressure Tx (2-wire or 3-wire) LOGO! AM2 AI1 terminal 250Ω internal + - + - Loop current flows from PSU -> transmitter -> AM2 I+ terminal -> internal 250 ohm burden -> AM2 M terminal -> PSU 0V. DO NOT add an external resistor. DO NOT apply 24 V to I+ directly.

5.1 Two-Wire (Loop-Powered) Transmitter

Power the transmitter from the same 24 V supply that powers the LOGO! BM. Connect transmitter + to +24V, transmitter - to AM2 I+, AM2 M to PSU 0V. Loop is closed through the internal 250 Ω burden.

5.2 Three/Four-Wire (Self-Powered) Transmitter

Connect the transmitter's signal + to AM2 I+, signal - to AM2 M. The transmitter's own supply and the LOGO! supply must share a common 0V; otherwise the M potential floats and the AM2 reads noise or out-of-range.

6. Configuration in LOGO! Soft Comfort

  1. Open the project in LOGO! Soft Comfort V8.0+ (download via LOGO! Soft Comfort V8.4).
  2. Drag an Analog Input (AI) block from the analog folder onto the diagram.
  3. Open the AI block properties. The Sensor Type pull-down offers:
    • 0-10 V
    • 0-20 mA
    • 4-20 mA
  4. Select 4-20 mA for a pressure transmitter.
  5. Map the AI to AI1 (or AI2) and assign the input number visible on the BM display (e.g. IW1 for AI1).
  6. Download to the LOGO! BM via Ethernet or micro-SD card.
  7. On the BM, navigate to Setup > AI1 / AI2 and verify the type shows "4-20 mA".
Mode change is not automatic. The AM2 hardware is identical for voltage and current; the only thing that changes is the scaling and whether the internal burden is selected. Re-typing the input in Soft Comfort is mandatory whenever you swap a sensor.

7. Step-by-Step Safe Wiring Procedure

7.1 Prerequisites

  • LOGO! 8 BM with AM2 already installed and recognized in the I/O list.
  • 24 V DC supply sized for the transmitter loop (typical 100 mA reserve).
  • Pressure transmitter with published 4-20 mA output, loop voltage rating ≥ 12 V.
  • Calibration multimeter (4-20 mA source/measure).
  • LOGO! Soft Comfort V8.0+ on a PC, with USB/Ethernet cable.

7.2 Procedure

  1. Power down the LOGO! BM and the 24 V supply. Wait 30 seconds for the AM2 input capacitors to discharge.
  2. Identify the AM2 terminals. From the BM outward: +24V (U), 0V (M), AI1 I+, AI1 M, AI2 I+, AI2 M. The same M is shared.
  3. Land the transmitter cable: signal + on AI1 I+, signal - on AI1 M. Shield to PSU 0V at one end only.
  4. Power the BM. From Soft Comfort, open the AI block and select 4-20 mA. Download.
  5. Apply the 24 V supply to the transmitter loop.
  6. Clamp the multimeter in mA mode in series with the loop. With the process at zero, the meter should read 4.0 mA. Apply full-scale pressure; the meter should read 20.0 mA.
  7. On the BM display, navigate to the AI value. Zero should show 0 (or your zero-scale raw count), full scale 1000.
  8. If the displayed value jumps, the polarity is reversed. Power down and swap I+ / M on the AM2 side only.

8. Verification and Commissioning

Test Procedure Pass criterion
Zero Apply 0 % process to transmitter, read BM AI value 0 / 1000 (or scaled minimum)
Span Apply 100 % process, read BM AI value 1000 / 1000 (or scaled maximum)
Linearity Apply 25, 50, 75 %; record AI value Within 1 % of expected linear
Loop voltage Measure V across transmitter terminals ≥ 12 V (per transmitter datasheet)
Worst-case burden Calculate Vburden_max = 20 mA × 250 Ω = 5 V PSU − burden − Tx Vmin ≥ 0
Reverse polarity Briefly reverse I+ / M with transmitter disconnected AM2 survives; reading shows out-of-range (0/1000) but no damage

The 5 V drop across the AM2's internal burden must be included in the loop voltage budget. A typical calculation for a 24 V supply and a 12 V minimum-drop transmitter:

Vtx_min = 12 V (transmitter requirement)
Vburden = 0.020 A × 250 Ω = 5 V
Vheadroom = Vpsu − Vtx_min − Vburden = 24 − 12 − 5 = 7 V (acceptable)

If the headroom is negative, the transmitter will not reach 20 mA. Either increase the supply to 26 V, use a transmitter with a lower minimum drop, or switch to a transmitter with a 1-5 V voltage output and configure the AM2 for 0-10 V.

9. Troubleshooting Matrix

Symptom Likely cause Corrective action
AI value = 0 with current flowing AI block configured for 0-10 V instead of 4-20 mA Change sensor type in Soft Comfort, redownload
AI value = 1000 with current flowing Polarity reversed OR loop > 20 mA (shorted burden) Power down, swap I+ / M, verify with multimeter
AI value jittery > 5 % Common-mode ground loop, no shield termination Land shield at PSU 0V end only, verify 0V bonding
AI reads 0 with no current, no loop voltage Broken wire, blown PTC in transmitter Measure loop voltage at Tx terminals; if < 5 V, fix Tx or supply
BM no longer sees AM2 Input shorted to 24 V, internal 5V rail collapsed Replace AM2; verify wiring before re-applying power
Reading stuck at 1000 even with Tx disconnected Input channel destroyed, internal short Replace AM2; check second channel as well

10. Preventive Measures and Field Tips

  • Document the mode per channel. Write "4-20 mA" or "0-10 V" next to each terminal on the panel legend. The AM2 terminals are identical for both modes and are a frequent source of miswiring.
  • Use a current calibrator for commissioning. A 4-20 mA source/simulator (e.g., Beamex MC6, Fluke 754) lets you verify the AM2 end-to-end before connecting the field transmitter.
  • Never apply 24 V to an AM2 input for any reason, including a continuity check. Use the loop's 4-20 mA signal or a controlled calibrator.
  • Install an inline 100 mA self-resetting PTC fuse on the field side if the cable run leaves the cabinet. This protects against wiring transients without affecting loop accuracy (voltage drop < 0.2 V at 20 mA).
  • For noisy plants, prefer 0-10 V or ±10 V (with the AM2 / AM2 RTD's voltage range) over current, because 4-20 mA loops are more susceptible to induced noise on long parallel cable runs.
  • Keep the AM2's configuration backup in LOGO! Soft Comfort and store the LSC file on the same micro-SD card as the BM firmware.

11. Related LOGO! 8 Modules and Cross-Reference

Module Order number Function Notes
AM2 6ED1055-1MA00-0BA2 2 AI, 0-10 V / 0/4-20 mA This article
AM2 RTD 6ED1055-1MA00-0BA3 2 AI for Pt100/Pt1000 Resistance input only; do not use for 4-20 mA
AM2 AQ 6ED1055-1MM00-0BA2 2 AO, 0-10 V / 0/4-20 mA Output counterpart; same burden issue when sinking loads

If the application requires 0-10 V output (e.g., to a variable-frequency drive), the AM2 AQ output can source 0-10 V directly without an external resistor. For 4-20 mA output, the AM2 AQ must source the loop current; ensure the receiver has a low-side return to the AM2's M terminal.

12. Frequently Asked Questions

What did I do wrong when I connected a 24 V supply through a resistor to the AM2 to test 4-20 mA?

The AM2's analog inputs are passive current sinks. You must not apply 24 V directly across the input. The "resistor" that appeared to blow was almost certainly the AM2's internal PTC protection, which opens within milliseconds when forced voltage exceeds the 0-10 V input range. The follow-on silicon damage destroyed the input channel. Power the AM2 from the loop supply and connect the transmitter's signal terminals to I+ and M only.

Do I need an external burden resistor for a 4-20 mA transmitter on the AM2?

No. The AM2 has a built-in 250 Ω burden resistor for both AI channels, selected in software when you configure the AI block as 0-20 mA or 4-20 mA. Adding a second external burden will double the voltage drop in the loop, can prevent the transmitter from reaching 20 mA, and may push the AM2 input outside its 30 mA safe limit during a fault.

How do I know if my AM2 is destroyed or just needs reconfiguration?

Disconnect all field wiring from the AM2 terminals. Power up the LOGO! BM. If the BM does not show the AM2 in the I/O list at all, the module is destroyed and must be replaced. If the BM sees the AM2 but the AI value is stuck at 0 or 1000 with nothing connected, the input protection is likely blown — replace the module. If the BM sees the AM2 and the AI value floats with no input, the channel is healthy and the issue is configuration or wiring.

Can I use the same AM2 for both voltage and current sensors?

Yes, AI1 and AI2 can be configured independently — one for 0-10 V and the other for 4-20 mA — provided you set the correct sensor type in each AI block in LOGO! Soft Comfort. Note that the M terminal is shared between both channels, so two separately powered 4-20 mA loops will create a ground loop unless one of them is isolated.

What is the maximum loop voltage I can feed into the AM2 current input?

The transmitter side of the loop is limited by the AM2's 30 mA absolute maximum rating. At 20 mA nominal the AM2 drops 5 V across the internal burden, so the transmitter must be able to operate with a supply of (Vpsu − 5 V). Most 4-20 mA pressure transmitters need at least 12 V at their terminals, which means a 24 V supply is the practical minimum for the AM2 in current mode.

Back to blog