Overview
Field technicians regularly hit the I/O ceiling on a Siemens LOGO! base module before the mechanical scope of the machine is finished. The classic symptom is a fully populated LOGO! 8 (6ED1052-xxx08-0BA8) or older 0BA6/0BA5 controller with all 16 digital outputs assigned and a new conveyor, light stack, or solenoid valve still to add. The hardware manual confirms the absolute limits in the LOGO! system manual: a maximum of 24 digital inputs and 20 digital outputs when expansion modules are stacked, but in practice most base units ship with 4 outputs and grow to 16 or 20 through DM8/DM16 modules (LOGO! 8 System Manual, entry ID 109741041).
When the controller cannot be replaced, cannot be networked, and budget rules out a SIMATIC S7-1200, the only practical option is to multiply the load capacity of an existing output. The cleanest way to do this on a relay-output LOGO! is to drive multiple low-power DC contactor coils from a single dry contact, then use the contactor's own auxiliary contacts to provide status feedback to free LOGO! inputs. The remainder of this article is the engineering reference for that fix: rating math, inrush analysis, wiring topology, safety interlock strategy, and verification.
Prerequisites
Before touching the panel, confirm the following:
- Current LOGO! base module part number (e.g. 6ED1052-1MD08-0BA8 = LOGO! 8 12/24 RCE with relay outputs).
- Whether outputs are relay (R) or transistor (T). Relay outputs are required for this technique, since you are switching multiple DC coils in parallel.
- Coil voltage of every contactor on the new conveyors. Mixing 24 VDC coils with 230 VAC coils on a single dry contact is a fault and must not be attempted.
- Steady-state and inrush current of every coil, taken from the manufacturer datasheet, not estimated.
- Available free LOGO! inputs for the safety and overload feedback path. If none are free, the technique is not viable without an expansion DM8 module.
LOGO! Output Ratings: Base vs. Expansion
The contact rating of a LOGO! relay output is not uniform across the system. The base unit and each expansion module type carry different UL/IEC ratings for resistive, inductive (AC-15 / DC-13), and motor loads. Pulling a single number from the front of the manual is a common field error.
| Module | Resistive (cos φ = 1) | Inductive (AC-15 / DC-13) | Motor (per IEC 60947) | Notes |
|---|---|---|---|---|
| LOGO! 8 RCE base (Q1..Q4) | 10 A @ 24 VDC / 240 VAC | 3 A @ 240 VAC (AC-15) 2 A @ 24 VDC (DC-13) |
Refer to manual derating curve | AgSnO2 contact, single pole |
| LOGO! DM8 12/24 R (expansion) | 5 A | 3 A @ 240 VAC 2 A @ 24 VDC |
Derated | Smaller footprint relay |
| LOGO! DM16 24 R | 5 A per output | 3 A / 2 A | Derated | 16 relays, 5 A each |
| LOGO! AM2 / AM2 RTD | N/A | N/A | N/A | Analog, not relevant to this technique |
For the parallel-contactor fix the only number that matters is the resistive rating of the relay you are actually using, because DC contactor coils look substantially resistive once saturated. Always derate from the published figure by 20% for sustained service and 50% if the contact drives a mixed cluster of inrush-heavy loads.
Steady-State Current Calculation
The driving problem, as posted on the source thread, is four new spine conveyors each fed by a 24 VDC contactor, with the contactors currently intended to be tied to individual LOGO! outputs. Because the LOGO! has only 16 outputs and 12-14 are already in service, the proposal is to drive 3 or 4 contactors in parallel from a single output.
Per-coil data given by the integrator:
- Coil voltage: 24 VDC
- Steady-state current: 197 mA per coil
Aggregate steady-state current for the four-coil cluster:
I_total = N_coils x I_coil
I_total = 4 x 0.197 A
I_total = 0.788 A
This is well under the 10 A base-module rating. The cluster is using only 7.88% of the contact's continuous capacity. Headroom is therefore not the concern; inrush and fault discrimination are.
Inrush Current Analysis
DC contactor coils present a transient load that is significantly higher than steady state at the moment the contact closes. The coil is a wound inductor; at turn-on the only opposition to current is the winding's DC resistance (Rcu), because the inductance opposes the rate of change of current, not the current itself. The current climbs exponentially toward V_coil / R_cu with a time constant of tau = L / R.
A typical inrush multiplier for a 24 VDC contactor coil is 2x to 4x steady state, settling in 30-150 ms depending on coil construction. For a conservative field estimate, assume 3x:
I_inrush_per_coil = 3 x 0.197 A = 0.591 A
I_inrush_cluster = 4 x 0.591 A = 2.36 A
Even with the worst-case 4x multiplier, total inrush is 3.15 A. The LOGO! relay handles this comfortably; the contact's I^2t let-through is the more relevant limit for sub-10 ms surges, and a 3 A surge on a 10 A rated AgSnO2 contact is in spec.
Wiring Topologies: Parallel vs. Cascade
Two field-proven topologies are viable. Pick based on whether each contactor must be individually controllable, or whether the cluster is genuinely all-on / all-off.
Topology A: Direct Parallel
All contactor coils wired coil-to-coil across the LOGO! output. The single dry contact closes, all coils energize.
+24 VDC +24 VDC
| |
+--[A1 K1]--[A1 K2]--[A1 K3]--[A1 K4]
| | | |
| [K1] [K2] [K3] [K4] (coils)
| | | | |
+--[A2 K1]--[A2 K2]--[A2 K3]--[A2 K4]
|
LOGO! Qx (relay COM)
Pros: simplest, lowest component count, no interlock logic. Cons: loss of one coil disables fault discrimination. If any one contactor fails to pull in, the LOGO! cannot tell which one.
Topology B: Cascade Through Auxiliary Contact
Each downstream contactor is fed through the normally-open (N/O) auxiliary contact of the previous contactor. The first contactor is fed directly by the LOGO!; subsequent contactors pull in only when the upstream one is sealed in.
LOGO! Qx ---- [A1 K1 A2]
|
+-- (K1 N/O aux) ---- [A1 K2 A2]
|
+-- (K2 N/O aux) ---- [A1 K3 A2]
|
+-- (K3 N/O aux) ---- [A1 K4 A2]
|
(run feedback to LOGO! Iy)
Pros: built-in sequential start reduces simultaneous inrush by up to 4x. Provides a free run feedback input wired from the last contactor's auxiliary. Cons: cascade is sequential, so the fourth contactor is delayed by the cumulative pickup time (typically 20-40 ms per stage — usually acceptable for conveyor start-up).
For the integrator's case of 4 spine conveyors on a common run command, Topology B is preferred. It trades 100 ms of start latency for a single wire back to a free LOGO! input that confirms the entire chain is sealed in.
Safety Interlock Strategy
Dropping a single output that drives 4 contactors means dropping 4 conveyor segments at once. The most important consequence is the emergency-stop response and the individual motor overload (O/L) response. Treat both as hard requirements, not as nice-to-haves.
Emergency Stop Wiring
The E-stop must open the LOGO! output command path, but the LOGO! scan time and the relay drop-out time (typically 15-25 ms) is acceptable because the contactor's own N/C auxiliary wired in series with the coil provides a hardware-grade disconnect independent of the controller. Recommended:
- Wire one N/C pole of the contactor in series with the coil it controls. This guarantees that if the contactor welds, downstream power is broken.
- Route an additional N/O pole of the last contactor back to a free LOGO! input, configured in the program as the "spine run" permissive. If the input goes low without a Qx command going low, the LOGO! raises a fault.
- Bring the E-stop pushbutton into the LOGO! as a hardwired NC loop through a safety relay or directly into the LOGO! input as called out in the program — never rely on the LOGO! relay contact alone for category-1 stop.
Overload Feedback to Free Inputs
If the panel already has individual thermal overload relays on each conveyor motor, the O/L's N/C "trip" contact is the perfect feedback source. Wire one O/L trip output per spine conveyor to a free LOGO! input, and let the program latch the specific fault. This is the "individual O/L outputs for fault indication" requirement raised in the field discussion.
If free inputs are exhausted, replace one DM8 expansion module with a DM16 and reclaim 8 inputs, or use a wired-OR diode matrix on a single input at the cost of fault resolution. The diode matrix is a serviceable field expedient but never a substitute for individual signaling in a maintenance-heavy plant.
Step-by-Step Implementation
- Inventory and derate. List every coil that will share the output, with steady-state and inrush current. Verify aggregate inrush < 50% of the relay rating.
- Verify mixed-voltage compatibility. All coils on one output must share the same nominal voltage. Mixing 24 VDC and 230 VAC is not allowed.
- Verify free inputs. Confirm at least one free LOGO! input exists for the cascade run-feedback signal. Confirm additional inputs for O/L trip feedback if fault discrimination is required.
- Stop the program and isolate power. Lock out the 24 VDC logic supply and the contactor-coil supply. Verify zero energy.
- Wire the first contactor from the LOGO! output (Q1..Q16). Use the relay's common (COM) and normally-open (NO) terminals, not a solid-state output, and observe the polarity of the suppression diode if the coil is DC.
- Cascade the remaining contactors through the upstream N/O auxiliary blocks. Confirm auxiliary contact rating ≥ coil current; most contactor auxiliaries are 10 A thermal / 1-3 A inductive and are fine.
- Wire run feedback from the last contactor's N/O auxiliary to a free LOGO! input, configured with a 100 ms debounce filter in LOGO! Soft Comfort.
- Wire O/L trip contacts to additional free inputs, one per conveyor. Use NC contacts from each O/L relay.
- Update the program in LOGO! Soft Comfort to treat the spine run input as a permissive: if Qx is high and Iy is low for > 500 ms, latch a fault bit. If any O/L input opens, latch a specific fault word identifying the conveyor.
- Add a 1 A or 2 A fuse per coil in the +24 V feed. This isolates a shorted coil from the cluster and prevents total loss of the parallel run.
- Re-energize and download the program.
Verification & Commissioning
Commissioning the parallel cluster requires three passes, each one verifying something the previous step cannot.
Pass 1: Cold Visual and Continuity
- Confirm no coil A1/A2 is reversed, no diode is backwards, no fuse is missing.
- Continuity-check the cascade path: with Qx off, all downstream contactors must show open coil resistance only at the first contactor.
Pass 2: Energized Functional
- Force Qx low. All four contactors should release within 30 ms.
- Force Qx high. All four contactors should seal in, in cascade order, within 200 ms total. Run feedback input should go high.
- Pull one O/L contactor manually (or via a test pushbutton wired to the O/L N/C). The corresponding LOGO! input should drop within one scan. The program should latch the fault.
Pass 3: Dynamic Inrush
- With a clamp meter on the LOGO! output wire in inrush mode, cycle Qx 20 times. Peak inrush should be consistent cycle-to-cycle; a trend upward indicates a failing contact.
- Measure the 24 VDC rail during inrush. A sag of more than 10% indicates the power supply is undersized for the cluster; reduce the simultaneous-start population or add a soft-start NTC.
Alternatives Worth Considering
| Alternative | Cost | When It Wins | When It Loses |
|---|---|---|---|
| Add LOGO! DM8 / DM16 expansion | Low (one module) | You have free slot space in the stack and just need 4-8 more outputs | You are already at the 16- or 20-output hard ceiling for that variant |
| Add a second LOGO! base unit | Medium | You need more program memory, more I/O, and can hand off a few flags through hardwired I/O | You need to share a peer-to-peer fieldbus; LOGO! cannot master a network, only act as a LonWorks or AS-Interface slave |
| Migrate to SIMATIC S7-1200 | High initial, low lifecycle | Plant growth is expected, you need PROFINET, or you need PID, motion, or data logging | Capex is blocked; you need a stop-gap for 6-12 months |
| Add an interposing relay row | Low | You have a single high-current load (solenoid valve bank) and want to keep the LOGO! relay fully isolated | You are trying to gain outputs; an interposing row only buffers, it does not multiply |
The decision tree in practice: if the LOGO! is undersized for the long term, the second LOGO! or the S7-1200 is the right answer. If it is a 3- to 6-month capacity blip, the parallel-contactor technique documented above is the cheapest correct fix.
Troubleshooting Matrix
| Symptom | Likely Root Cause | Diagnostic | Corrective Action |
|---|---|---|---|
| All four contactors chatter at start | 24 VDC rail sagging under inrush | Scope the 24 V rail during Qx on | Upgrade PSU; add soft-start NTC; switch to Topology B cascade |
| Three contactors pull in, fourth does not | Fuse blown on that branch, or auxiliary contact upstream failed | Measure voltage at the failed coil's A1-A2 | Replace fuse; inspect aux contact for pitting |
| Run feedback input stays low after Qx is high | Cascade break; downstream contactor did not seal | Walk the cascade with a meter, start at Qx | Check aux contact wiring and mechanical interlock |
| LOGO! Qx contact welds closed after a few months | Aggregate inrush far higher than calculated; short-circuited coil | Inspect welded contact; measure cold resistance of each coil | Replace LOGO! base, add fuse per coil, re-rate cluster |
| One conveyor O/L trips the entire spine run | O/L N/C wired in series with the LOGO! Qx run, not as a feedback input | Trace O/L wiring; should land on a digital input, not in series with the coil | Rewire to a free input; treat the O/L as a status, not a stop |
| LOGO! program faults on first scan | Free input was assigned to a non-existent expansion slot | Check the I/O configuration in LOGO! Soft Comfort | Re-run the hardware detect; verify expansion addressing |
Design Checklist Before Energizing
- All coils on the shared output share the same nominal voltage.
- Aggregate inrush ≤ 50% of relay rating.
- Per-coil fuse installed.
- Run feedback input wired and configured with debounce.
- O/L trip contacts wired to individual inputs (or to a diode-OR matrix with documented compromise).
- Free diodes (1N4007 or equivalent) across each DC coil, cathode to +24 V.
- LOGO! Soft Comfort program updated and downloaded with fault-latch logic.
- E-stop response verified under no-load and loaded conditions.
FAQ
Can I parallel 24 VDC and 230 VAC contactor coils on a single LOGO! relay output?
No. Mixing coil voltages on a single dry contact places both voltage sources on the same conductor and creates a direct short through the coil returns. All coils tied to one output must share the same nominal voltage, polarity, and supply reference.
What is the actual maximum number of digital outputs on a fully expanded LOGO! 8?
20 digital outputs (4 on the base + 16 across two DM8 expansion modules), or 24 outputs if you stack one DM16 and one DM8. The system manual (entry ID 109741041) lists the matrix; older 0BA5/0BA6 hardware caps at 16 outputs.
Is the LOGO! relay output rated 10 A on the expansion modules too?
No. The base LOGO! RCE relay is rated 10 A resistive. The DM8 and DM16 relay expansion modules are rated 5 A per output. Always check the specific module's rating before sizing a parallel load cluster.
Can two LOGO! controllers be networked together to share flags?
Not natively as peers. A LOGO! can act as a slave on LonWorks or AS-Interface, and the LOGO! 8 added an Ethernet port for S7 communication and LOGO! Cloud, but it cannot master a multi-master peer fieldbus. For shared I/O across two controllers, wire physical I/O between them or migrate to an S7-1200 with PROFINET.
Why is cascade wiring preferred over direct parallel for a 4-coil cluster?
Cascade reduces simultaneous inrush by spreading the contactor pickups across their mechanical close times, gives a single hardwired run-permissive input back to the LOGO! for fault detection, and isolates each contactor mechanically so a single welded contact cannot fail-open the whole spine conveyor line.