Siemens SIMOREG DC Master SG70 DriveES Parameterization via PROFIBUS: CBP versus CBP2 Failure Mode
Problem Overview
A Siemens SIMOREG DC Master 6RA70 (SG70 frame size, basic-unit firmware v2.0) responds correctly to cyclic PROFIBUS-DP traffic from a SIMATIC S7 PLC. Setpoints are written, actual values are read, and the converter is fully controllable in the process. However, the engineering tool DriveES v5.5 cannot establish an online connection to the same drive for parameterization. DriveMonitor reports a persistent NC — not connected status, and no parameter values are read back into the project.
The fault pattern is asymmetric: a SIMOVERT MASTERDRIVE (AC drive) sitting on the same PROFIBUS segment connects to DriveES without issues. The same PC adapter, the same Set PG/PC Interface, and the same HW Config project both reach the bus. Only the SIMOREG refuses the acyclic class-2 handshake.
The root cause is the SIMOREG's communication module: the drive is fitted with a first-generation CBP (MLFB 6SE7090-0XX84-0FF0) instead of a CBP2 (MLFB 6SE7090-0XX84-0FF5). The CBP does not implement the full DPV1 class-2 acyclic service set that DriveES requires to enumerate and read/write parameters. The CBP2 does, and a hardware swap from CBP to CBP2 restores DriveES connectivity without any software change.
Affected Components and Versions
| Component | Version / Order Number | Role in the fault |
|---|---|---|
| SIMOREG DC Master 6RA70 | Basic-unit firmware v2.0 | Drive under commissioning |
| CBP (Communication Board PROFIBUS) | 6SE7090-0XX84-0FF0 | Original, suspect module |
| CBP2 (Communication Board PROFIBUS 2) | 6SE7090-0XX84-0FF5 | Replacement that resolves the fault |
| DriveES (SIMATIC) | v5.5 with matching SP | Engineering / parameterization tool |
| STEP 7 / HW Config | v5.5 + SPx | Bus and slave configuration |
| DriveMonitor (within DriveES) | v5.5 | Online parameter editor |
| PROFIBUS-DP segment | Standard DP, 1.5 Mbps typical | Shared with MASTERDRIVE; proven good |
Symptom Matrix
| Observed symptom | Likely cause |
|---|---|
| DriveMonitor shows NC — not connected on the SIMOREG only | Slave-side acyclic service set is missing (CBP) |
| Same DriveES connects to a MASTERDRIVE on the same physical bus | PC adapter and Set PG/PC Interface are correct |
| PLC writes process data successfully; DriveES cannot read parameters | Cyclic PZD works on CBP; acyclic PKW does not |
| P927 = "CB parameterization is enabled" set, no improvement | DriveES still cannot complete class-2 handshake |
| P051 = 40 set, no improvement | Parameter access level is necessary but not sufficient |
| PROFIBUS LED on CBP is solid green during PLC data exchange | Cyclic bus healthy; fault is higher up the stack |
| HW Config shows the slave with a generic DP GSD, not the DriveES profile | Acyclic PKW channel not exposed; re-insert from DriveES profile |
Root Cause: CBP versus CBP2 Service Profile
The SIMOREG CBP (suffix 0FF0) was designed for DPV0 cyclic operation. It supports process-data exchange (PZD) and a limited parameter-channel (PKW) implementation that was adequate for early SIMOREG commissioning tools. DriveES v5.5 (and later) use the full DPV1 class-2 acyclic services (MSAC2_Read, MSAC2_Write) to enumerate parameter numbers, read parameter values, and write parameter values back. The CBP firmware implements only a subset of those services. DriveES opens a class-2 connection to the slave, requests a parameter directory, and never receives a compliant response. The tool interprets the timeout as a connection failure and reports NC.
The CBP2 (suffix 0FF5) implements:
- Full DPV1 class-1 and class-2 acyclic services.
- PKW 4-word and PKW 8-word buffer modes (parameter-channel length 4 and 8).
- The GSD revision expected by HW Config when the SIMOREG is inserted from the DriveES HW Catalog.
- Improved diagnostic data exposed via the PROFIBUS diagnostics slot.
Once a CBP2 is fitted and the drive powers up, DriveES completes the class-2 handshake within a few seconds, DriveMonitor transitions to ONLINE, and the full parameter tree becomes available for upload, modification, and download.
Why the PLC keeps working on a CBP
Cyclic PZD is implemented on top of DPV0 services in both CBP and CBP2. As long as the PPO type selected in HW Config (1, 2, 3, 4, or 5) matches what the drive expects, the SIMATIC CPU exchanges setpoints and actual values without ever touching the acyclic class-2 channel. The PLC does not care that the CBP cannot enumerate parameters over PROFIBUS, because the PLC writes its own parameter requests via the SFB/SFC acyclic services using the WR_REC / RD_REC mechanism, which is a different path through the slave.
This is why a healthy S7 application coexisting with a dead DriveES link is the diagnostic fingerprint of a CBP-only limitation and not a wiring or address problem.
Diagnostic Procedure
Run the checks below in order before replacing the CBP. Most of the symptoms of a CBP failure can be reproduced by misconfiguration, and the CBP is a field-replaceable part that you want to confirm as the cause before swapping.
1. Verify the PROFIBUS physical layer and station address
- Inspect the PROFIBUS-DP cable and the D-sub connector on the SIMOREG. Confirm that the terminating resistor is ON at the two physical ends of the segment and OFF at every intermediate node.
- Confirm that the bus address set on the SIMOREG matches the HW Config slot. In this case,
P918 = 6(decimal) and the HW Config station address = 6. - Power-cycle the SIMOREG after a change of
P918; the value is latched on power-up.
2. Read the CBP / CBP2 LED
| LED state | Meaning |
|---|---|
| Green, solid | Cyclic data exchange active. Bus layer healthy. |
| Green, flashing or flickering | Intermittent connection, generally parameterization or configuration error. See PROFIBUS LED troubleshooting reference for general diagnostic guidance. |
| Red, solid | Configuration mismatch or hardware fault. |
| Red, flashing | No configuration received from the class-1 master. |
| Off | No bus traffic or no power to the CBP/CBP2. |
A solid green LED with the PLC running tells you the bus layer is healthy. If DriveES is still NC, the fault is at the acyclic layer or higher.
3. Validate Set PG/PC Interface
Open SIMATIC Manager > Options > Set PG/PC Interface. The access point S7ONLINE must point to the same CP or PC adapter used for the MASTERDRIVE. A misconfigured PC adapter is the most common software-side reason for a single-slave NC state on a bus where other slaves connect.
4. Verify the SIMOREG parameters
| Parameter | Required value | Purpose |
|---|---|---|
| P051 | 40 (parameter access all) | Unlocks read/write of all parameter levels; must be set during commissioning |
| P918 | Decimal slave address matching HW Config (here: 6) | PROFIBUS station number |
| P927 | Selection 1 — CB parameterization is enabled | Allows the CBP/CBP2 to participate in class-2 parameterization |
| P060 | 1 (backlight on, optional) | Convenience for verification at the PMU |
Setting P051 = 40 and P927 = 1 is necessary but not sufficient on a CBP. DriveES attempts a class-2 connection before the parameter-level protection is consulted, so a wrong P051 will look identical to a missing CBP2 service from the operator's perspective. Cycle L+/L- (electronics supply) after parameter changes so the new values are latched.
5. Confirm the slave is inserted from the DriveES HW Catalog
In HW Config, the SIMOREG must be inserted as a slave from the DriveES profile in the HW Catalog, not the generic PROFIBUS-DP catalog. The DriveES profile brings the correct GSD and exposes the acyclic parameter channel (PKW). If the slave was added from a generic Siemens catalog, the slot may show only PPO types 1–4 with no PKW slot, and DriveES cannot open a class-2 session because the slave never advertised the acyclic endpoint.
Procedure to re-insert correctly:
- Delete the SIMOREG slave from HW Config.
- Open the HW Catalog and navigate to
PROFIBUS-DP > Drives > SIMOREG > DriveES profile. - Drag the SIMOREG into the PROFIBUS subnet at the same station address.
- Recompile and download HW Config.
6. Try a known-good CBP2
If a CBP2 is available on site, swap the CBP for the CBP2 with the drive de-energized. Cycle the electronics supply, then re-attempt the DriveES connection. A clean connection on the CBP2 confirms the original CBP as the root cause and you can leave the CBP2 in service.
Step-by-Step Resolution
Prerequisites
- CBP2 communication board, MLFB 6SE7090-0XX84-0FF5.
- SIMATIC STEP 7 v5.5 with DriveES v5.5 SP installed and licensed.
- Online access (PROFIBUS or serial) to the SIMOREG to verify parameters after the swap.
- ESD wrist strap; CBP/CBP2 modules are sensitive to static discharge.
- Documentation of the existing PROFIBUS station address and the active PPO type.
Procedure
- De-energize the SIMOREG. Open the front cover and identify the electronics box. The CBP/CBP2 occupies slot C of the electronics box.
- Remove the existing CBP (suffix 0FF0). If a fiber-optic link runs between the basic unit and the CBP, note its orientation; the CBP2 occupies the same slot and uses the same fiber-optic connector.
- Insert the CBP2 (suffix 0FF5) into slot C. Seat firmly until the retaining clips engage and the board is flush with the surrounding guides.
- Reconnect the fiber-optic link between the basic unit and the CBP2 if it was detached.
- Close the front cover and re-apply control power (24 V on terminals L+ / L-). Wait for the CBP2 to complete its self-test; the PROFIBUS LED cycles briefly through red and settles.
- From the SIMATIC side, open HW Config. Right-click the SIMOREG slave, choose
Object Properties > Device Identification, and confirm the device is now reported as a CBP2 module. - Open DriveES. In the project tree, double-click the SIMOREG to bring up DriveMonitor. The status indicator transitions from NC to ONLINE within a few seconds.
- Perform an Upload to PG in DriveMonitor to back up the parameter set. Save the project archive for change control.
Parameters to verify after the swap
| Parameter | Action | Notes |
|---|---|---|
| P918 | Read; confirm matches HW Config | Unchanged; verify after reboot |
| P927 | Confirm = 1 (CB parameterization enabled) | Must be set for acyclic class-2 access |
| P051 | Set to 40 during commissioning, restore operational access at the end | Resets on power cycle only if saved |
| U953 | Trigger "parameter set save" | Persists the new settings to non-volatile memory |
| P060 | Optional: enable PMU backlight | Useful for hand-on verification at the panel |
Verification
Validate the fix in three layers.
- Tool layer. DriveMonitor shows ONLINE. Parameter values are read back from the drive and displayed in the parameter tree. No timeouts on individual parameter reads.
- Bus layer. The PROFIBUS LED on the CBP2 is solid green when the PLC is in data exchange. During a DriveES upload or download the LED may briefly flicker as acyclic traffic passes.
- Application layer. From DriveES, upload all parameters, modify a non-safety parameter (for example a ramp time), download the change, and verify the new value is active at the drive. Then restore the original value, save the parameter set, and confirm the change persisted across a power cycle.
If any layer fails, revisit the HW Config insertion path and confirm the slave was added from the DriveES profile. A CBP2 inserted from a generic DP catalog exhibits a behavior identical to a CBP inserted from the DriveES profile, so the catalog selection is the most common regression after the swap.
Preventive Measures and Field-Proven Caveats
- Stock a CBP2 spare. CBP modules are legacy; CBP2 is in production, firmware-upgradable, and increasingly hard to find on the used market. Keep at least one CBP2 on the shelf per site with SIMOREG drives.
-
Use the DriveES profile in HW Config from the start. New SIMOREG commissioning should insert the slave from
PROFIBUS-DP > Drives > SIMOREG > DriveES profile. This loads the correct GSD and exposes the acyclic parameter channel from the first download. - Repeat the DriveES test after every firmware update on the basic unit. A firmware upgrade on the 6RA70 (for example from v1.x to v2.x) can change how acyclic services are routed and may surface latent limitations of a CBP that previously worked.
- Document bus address, PPO type, and CBP/CBP2 part number in the project hardware list. Future engineers can correlate field behavior with the hardware revision in seconds.
- Have a serial fallback ready. If you must continue using a CBP, use the PMU on the door of the SIMOREG or the X300 / X351 serial interface with DriveMonitor over a serial cable. Acyclic access is fully supported over the serial link even when the CBP cannot expose the class-2 services on PROFIBUS.
- Confirm hardware compatibility before a CBP-to-CBP2 swap on older units. On older 6RA70 units (C98163-A1004-A1-xx hardware) a CBP2 may require an electronics-box update. Verify in the SIMOREG 6RA70 operating instructions before the swap.
-
Save the parameter set before and after the swap.
U953 = 1writes the active parameters to non-volatile memory. Skip this step and the next power cycle wipes any unsaved P051 / P927 changes.
Alternate Controller and Platform Notes
TIA Portal
DriveES for TIA Portal (V5.5 SPx and later) uses the same SIMOREG GSD revision as DriveES v5.5. The CBP2 hardware requirement is unchanged. If you migrate from SIMATIC Manager to TIA Portal, do not regress to a CBP — the failure mode is identical and the migration is the right time to replace the module.
Third-party PROFIBUS masters
Any PROFIBUS class-1 master (ABB AC500, Schneider M340, Beckhoff CX with PROFIBUS) will see the CBP or CBP2 identically for cyclic I/O. The acyclic limitation only affects class-2 masters, which includes DriveES, STARTER with DriveMonitor, and most asset-management tools. If you intend to use a third-party asset manager on a SIMOREG, plan for a CBP2.
PROFINET migration
The CBP2 has a PROFINET sibling, the CBE20 (MLFB 6SE7090-0XX84-0FF6). When retiring PROFIBUS segments, swap the CBP2 for a CBE20 and update the controller-side configuration. SIMOREG firmware that supports the CBP2 generally supports the CBE20 as well. The GSD for the CBE20 is shipped with TIA Portal; for SIMATIC Manager you must install the latest HSP for the SIMOREG 6RA70.
Diagnostic Quick Reference
| Check | Pass criterion | Failure action |
|---|---|---|
| PROFIBUS LED solid green during PLC data exchange | Cyclic bus healthy | Inspect wiring, address, PPO type |
| DriveMonitor shows ONLINE | Acyclic services OK | Replace CBP with CBP2; verify HW Config insertion |
| PLC read/write of control word / status word | Process data OK | Inspect HW Config slot mapping |
| P927 = CB parameterization enabled | Tool-side access OK | Set in DriveMonitor or PMU |
| GSD loaded from DriveES profile | Acyclic channel exposed | Re-insert slave from DriveES profile |
| P051 = 40 during commissioning | Read/write unlocked | Reset to required access level on exit |
| CBP/CBP2 part number logged in project | Hardware state documented | Update hardware list post-swap |
Troubleshooting Matrix
| Symptom | Probable cause | Action |
|---|---|---|
| NC on SIMOREG, ONLINE on MASTERDRIVE | CBP installed on SIMOREG | Replace CBP with CBP2 (0FF5) |
| NC on SIMOREG, no other slaves reachable | PC adapter or Set PG/PC Interface wrong | Verify S7ONLINE assignment |
| NC on SIMOREG, cyclic PZD from PLC works | Acyclic channel not exposed | Re-insert slave from DriveES profile |
| NC on SIMOREG, P051 = 0 and P051 cannot be written | Parameter access locked at the drive | Set P051 via PMU or serial |
| NC on SIMOREG, red PROFIBUS LED on the CBP | Bus fault or no configuration | Inspect HW Config, address, terminating resistors |
| NC on SIMOREG, green LED flickering | Configuration or parameterization error | Verify PPO type and DriveES GSD match |
| NC on SIMOREG after firmware update on 6RA70 | Basic-unit firmware changed acyclic routing | Match CBP/CBP2 firmware to basic-unit firmware per release notes |
| NC on SIMOREG, replacement CBP2 also fails | GSD revision or HW Config insertion wrong | Re-insert slave from DriveES profile; recompile |
Why does my SIMOREG connect fine to the PLC but DriveES shows NC — not connected?
The CBP (suffix 0FF0) supports cyclic PZD but does not implement the full DPV1 class-2 acyclic service set that DriveES needs to enumerate parameters. The PLC uses cyclic PZD and the SFB52/SFB53 (RD_REC/WR_REC) acyclic services, which is a different path. Replace the CBP with a CBP2 (suffix 0FF5) to restore the acyclic channel DriveES requires.
How do I identify whether my SIMOREG has a CBP or a CBP2?
Power down the unit and read the MLFB label on the communication board. CBP is 6SE7090-0XX84-0FF0 and CBP2 is 6SE7090-0XX84-0FF5. You can also confirm online in DriveMonitor under drive identification once the acyclic channel is up, or in HW Config under the slave's device identification after a bus scan.
Is changing the CBP to a CBP2 purely a hardware swap, or do I need to reconfigure the project?
The hardware swap is the only required action if the rest of the bus configuration is correct. HW Config re-reads the device identification on the next bus scan and the SIMOREG appears as a CBP2 slave. The existing PPO mapping, station address, and DriveES profile remain valid; no GSD change is required.
Can I keep using a CBP if I cannot source a CBP2?
Yes, but you lose the acyclic parameter channel over PROFIBUS. Use the PMU on the door of the SIMOREG or the X300 / X351 serial interface with DriveMonitor over a serial cable; both support full parameterization. DriveES parameterization over PROFIBUS will not work on a CBP.
Does the CBP or CBP2 affect SIMOREG firmware, or are they independent?
The CBP and CBP2 are independent of the basic-unit firmware, but the basic unit must support the board that is installed. SIMOREG 6RA70 basic-unit firmware v2.0 supports both CBP and CBP2. On older hardware revisions (C98163-A1004-A1-xx) consult the 6RA70 operating instructions before swapping a CBP for a CBP2; some early electronics boxes require a hardware update.
Why does P051 = 40 not fix the DriveES connection?
P051 unlocks parameter read/write at the drive once a class-2 connection is established. DriveES attempts the class-2 handshake first, and the CBP cannot complete that handshake because it does not implement the required DPV1 class-2 services. The tool reports NC before P051 is ever consulted. Set P051, but expect to replace the CBP to actually clear the NC state.