SIMOTION D vs S7-300 with SINAMICS S120 CU320-2: Motion Control

David Krause17 min read
Motion ControlSiemensTechnical Reference
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Architecture Overview: Two Paths to Multi-Axis Servo Control

When designing a multi-axis servo system with SINAMICS S120 drive components, engineers face an early architecture decision: pair the S120 cabinet with a separate SIMATIC PLC plus a CU320-2 control unit, or consolidate the PLC, motion control, and drive intelligence into a single SIMOTION D controller. Both architectures are field-proven, both can drive 1FK7 synchronous servo motors through Single Motor Modules, and both can be configured inside the TIA Portal. The decision hinges on axis count, synchronization complexity, programming style, and lifecycle cost. This reference compares the two architectures using a documented S120 configuration: an S7-300 CPU 315-2DP, a CU320-2 control unit, a 16 kW Smart Line Module, five Single Motor Modules, and five 1FK7 servo motors.

Reference Configuration and Component Identification

The reference project assembles a complete SINAMICS S120 booksize drive line-up, controlled by a SIMATIC S7-300 CPU 315-2DP. The components are:

Documented SINAMICS S120 booksize line-up
MLFB / Order Number Component Rating Quantity
6SL3000-0CE21-6AA0 Line Reactor 16 kW 1
6SL3000-0BE21-6DA0 Line Filter 16 kW 1
6SL3130-6TE21-6AA3 Smart Line Module (Active) 16 kW 1
6SL3120-1TE15-0AA3 Single Motor Module 5 A 4
6SL3120-1TE21-0AA3 Single Motor Module 9 A 1
1FK7060-5AF71-1DA0 1FK7 Synchronous Servo 1.48 kW, 4.70 Nm, AH 63 4
1FK7083-5AF71-1DG0 1FK7 Synchronous Servo 3.30 kW, 10.50 Nm, AH 80 1

The CU320-2 acts as the central drive controller for the S120 line-up. It hosts the drive firmware, manages DRIVE-CLiQ communication to the Smart Line Module and each Motor Module, and exposes the S120 as a PROFIBUS DP slave to the CPU 315-2DP. Each Motor Module in turn controls one 1FK7 servo motor through a DRIVE-CLiQ cable. The PLC handles the application sequence, while the CU320-2 executes the position, velocity, and current control loops for every connected axis.

CPU 315-2DP Role

The 6ES7315-2AH14-0AB0 (CPU 315-2DP) provides the PROFIBUS DP master interface, the application program in STEP 7, and the I/O scanning. The PLC transmits positioning commands to the CU320-2 over PROFIBUS using standard telegram types (typically telegram 1, 2, 3, or 105 for positioning) and reads back actual position, velocity, and status words. HMI and I/O exchange is handled in the same controller.

Architectural split: Logic in S7-300, drive control in CU320-2, sequence coordination over PROFIBUS DP. The CU320-2 manages up to 6 servo axes in a single control unit, expandable to 12 axes in V/f mode. A second CU320-2 can be linked for larger systems.

Decoding the SINAMICS S120 Order Numbers

Decoding the order numbers clarifies the system capability before any software is loaded:

  • 6SL3130-6TE21-6AA3 — Smart Line Module 16 kW, 6-pulse, internal air cooling, with regulated DC bus and line-side thyristor precharge. Supports regenerative feedback into the supply.
  • 6SL3120-1TE15-0AA3 — Single Motor Module 5 A, booksize format, internal air cooling, output for one servo motor at 3 AC 400 V.
  • 6SL3120-1TE21-0AA3 — Single Motor Module 9 A, booksize format, internal air cooling.
  • 1FK7060-5AF71-1DA0 — 1FK7 compact servo, 1.48 kW, 4.70 Nm continuous stall torque, 63 mm axis height, with absolute encoder (multi-turn, 22-bit).
  • 1FK7083-5AF71-1DG0 — 1FK7 high-inertia servo, 3.30 kW, 10.50 Nm, 80 mm axis height, with absolute encoder and shaft seal.

Each Single Motor Module pairs with one 1FK7 motor via a pre-fabricated MOTION-CONNECT DRIVE-CLiQ signal cable. The encoder is read through the DRIVE-CLiQ interface, eliminating the need for separate encoder cables back to the CU320-2.

SIMOTION D Architecture Overview

The SIMOTION D platform is a single hardware module that combines the functions of an S7-300 / S7-400 PLC, a CU320-2 drive controller, and a high-performance motion controller. The SIMOTION D4x5-2 series embeds the PLC runtime, the SIMOTION kernel, and the drive intelligence for a connected SINAMICS S120 line-up in a single rack-mounted device. The result is a smaller cabinet footprint, fewer PROFIBUS / PROFINET nodes, and one engineering tool (SCOUT, optionally integrated in TIA Portal V20) for the entire application.

SIMOTION D variants relevant to this comparison:

SIMOTION D4x5-2 platform comparison
SIMOTION D Max. Axes Min. Servo Cycle Communication Programming
D425-2 DP/PN 16 2 ms PROFIBUS + PROFINET MCC, ST, LAD/FBD
D435-2 DP/PN 24 2 ms PROFIBUS + PROFINET MCC, ST, LAD/FBD
D445-2 DP/PN 32 1 ms PROFIBUS + PROFINET MCC, ST, LAD/FBD
D455-2 DP/PN 64 0.5 ms PROFIBUS + PROFINET MCC, ST, LAD/FBD

The D455-2 is the direct replacement candidate for the S7-300 + CU320-2 architecture in machines that need electronic gearing, cam profiling, or cross-axis synchronization at sub-millisecond cycle times. For a step-by-step configuration of a D455-2 DP/PN with a CU320-2 PN over PROFINET IO, see the official TIA Portal SCOUT device configuration guide.

Inserting SIMOTION D455-2 DP/PN and SINAMICS S120 CU320-2 PN (TIA Portal V20 documentation)

What Integrated Means in Practice

SIMOTION D removes the boundary between PLC and drive. The same project tree contains the PLC program, the axis configuration, the cam editor, and the SINAMICS S120 drive parameters. The TO (Technology Object) axis block compiles directly with the PLC code; there is no PROFIBUS telegram mapping table to maintain. The drive firmware in the S120 line-up remains the standard SINAMICS V5.x, but the configuration download is orchestrated from SCOUT.

Functional Comparison: Single-Axis Position vs Synchronization

The two architectures answer different motion problems. The S7-300 + CU320-2 combination delivers a strong single-axis position controller; SIMOTION D adds native multi-axis synchronization as a first-class function.

Functional capability matrix
Capability S7-300 + CU320-2 SIMOTION D4x5-2
Single-axis point-to-point positioning Yes (MDI, traversing blocks up to 64) Yes (MCC _MOVE commands, TO positioning)
Traversing blocks (preset positions) Up to 64 per axis in CU320-2 Configurable per axis in TO
Electronic gearing (slave follows master axis) Limited, requires S7 logic + encoder on DP/PN Native (synchronous operation, _gear command)
Electronic cam (camming profile) Not native, requires extensive S7 math Native (cam editor, _cam command)
Master value coupling (virtual master) No Yes
Path interpolation (linear, circular) No (would require external controller) Optional with SIMOTION path object
Velocity synchronization between axes Approximate via PLC Hardware-locked, deterministic
PLC logic for machine sequence In S7-300 (LAD/FBD/ST) Inside SIMOTION (LAD/FBD, ST, MCC)

In the documented project, all drives run in sequence, single axis only — a classic point-to-point application. The S7-300 + CU320-2 combination is fully capable: the engineer programs a sequential startup in STEP 7, selects traversing block 1, then 2, then 3 inside the CU320-2, and reads the MELDW.3 acknowledgment bit. SIMOTION D would handle the same task but at higher hardware cost and with a steeper commissioning curve.

Decision trigger: Stay with S7-300 + CU320-2 if the requirement is sequential, single-axis motion. Migrate to SIMOTION D the moment a second axis must follow the first with deterministic phase, when a cam profile replaces mechanical gearing, or when a virtual master (line shaft, web tension loop) is introduced.

Programming Environments: STEP 7 vs SIMOTION SCOUT

The two stacks are configured in different tools. The S7-300 + CU320-2 path is a two-tool workflow: STEP 7 V5.5 (or TIA Portal with S7-300 plug-in) for the PLC, and STARTER or SCOUT for the SINAMICS S120 commissioning. The SIMOTION D path consolidates both into SCOUT (and, since TIA Portal V18/V20, optionally into the TIA Portal SCOUT plug-in).

Tooling comparison
Task S7-300 + CU320-2 SIMOTION D4x5-2
PLC programming STEP 7 V5.5 or TIA Portal SCOUT / TIA Portal SCOUT
Drive commissioning STARTER or SCOUT SCOUT (TIA integrated)
Axis configuration SINAMICS S120 parameter view (p-parameters) Technology Object (TO) configuration panel
Cam editor Not provided Graphical cam editor in SCOUT
Sequencer S7 GRAPH or ladder in PLC MCC (Motion Control Chart) within SCOUT
Commissioning download Two separate download steps (PLC + drive) One consolidated project archive
Project archive PLC project + drive project (manual merge) Single .zip containing PLC, axis, drive, HMI

The MCC (Motion Control Chart) language in SIMOTION is a flowchart-style editor designed for sequencing motion commands. Engineers transitioning from a STEP 7 GRAPH sequence often find MCC more direct for axis coordination. LAD, FBD, and ST remain available inside SIMOTION D for non-motion logic.

Typical SIMOTION D Sequence in MCC

// SIMOTION D MCC example: sequential single-axis positioning
PROGRAM MAIN_SEQUENCE
  IF bStartSequence THEN
    Axis1._MOVE(Position := 200.0, Velocity := 100.0, Acceleration := 50.0);
    WAITFOR Axis1._Status.State = STATE_HALT;
    Axis2._MOVE(Position := 50.0, Velocity := 80.0, Acceleration := 40.0);
    WAITFOR Axis2._Status.State = STATE_HALT;
    bStartSequence := FALSE;
  END_IF;
END_PROGRAM

The equivalent S7-300 + CU320-2 flow requires a STEP 7 FB that triggers traversing block selection on the CU320-2 via PROFIBUS (STW1 bit 13 = 1, STW1 bits 14-15 select block 0..63) and polls the MELDW.3 acknowledgment. The same physical movement takes more code in the PLC + drive split.

Communication Architecture and Telegram Mapping

The reference project uses CPU 315-2DP and therefore PROFIBUS DP at 12 Mbit/s. The CU320-2 in the S120 line-up is a PROFIBUS slave (with a CBP2 or CBE20 communication board depending on variant). SIMOTION D4x5-2 DP/PN variants offer both PROFIBUS DP and PROFINET IO; the -PN suffix exposes an integrated PROFINET interface with two ports (switch) on the SIMOTION D device itself.

Communication throughput for drive telegrams
Attribute PROFIBUS DP (S7-300 + CU320-2) PROFINET IO (SIMOTION D4x5-2)
Baud rate 12 Mbit/s 100 Mbit/s full duplex
Cycle time (typical drive) 1-5 ms 0.5-2 ms (IRT)
Determinism Good (token passing) Higher (IRT with cut-through switching)
Cable length 100 m at 12 Mbaud per segment 100 m copper, km on fiber
Diagnostic DP diagnostics PROFINET alarms, port statistics

For the documented 5-axis system with 16 kW SLM, PROFIBUS DP is fully sufficient. The bus load for 5 telegram 105 frames (servo) at 4 ms cycle is well under 30%. The switch to PROFINET is justified only if IRT synchronization between drives (sub-1 ms) or wider topology is required.

PROFIBUS Telegram Selection

For a 1FK7 servo on a CU320-2 controlled by an S7-300 or SIMOTION D, the standard telegram choices are:

Common SINAMICS S120 telegrams for 1FK7 servo
Telegram Resolution PZD Words Use Case
Telegram 1 16-bit position 2 / 2 Speed control only
Telegram 2 16-bit position 4 / 4 Speed + torque
Telegram 3 32-bit position 5 / 5 Positioning (32-bit resolution)
Telegram 5 32-bit position + DSC 9 / 9 Dynamic Servo Control
Telegram 105 32-bit position 10 / 10 Positioning with extension (default for SIMOTION)
Telegram 106 32-bit position + torque 14 / 14 Positioning with 2 encoders

For SIMOTION D integration, select Telegram 105 in the S120 drive configuration. The PZD map assigns STW1 (control word 1) and STW2 to the first two input words, with NSOLL (position setpoint), NIST (actual position), and G1_ZSW (status word) mapped into the remaining words. MELDW (message word) and POS_ZSW (position status word) provide the bit-level handshake the SIMOTION axis expects.

Parameter Read/Write via DPV1

To read or write individual S120 parameters from the S7-300, use the DPWR_DAT / DPRD_DAT pattern over PROFIBUS DPV1:

// S7-300 SCL: read r2560 (following error) from CU320-2
wDB  := 100;       // DP slave diagnostic address
wPKE := 16#1000 + 2560;  // read request for parameter 2560
wIND := 0;          // parameter index 0

// Issue DPV1 write with PKE/IND/PWE; poll DONE bit, then
// DPRD_DAT on the same slot to retrieve the 4-word response.
iRet := DPWR_DAT(LADDR := wDB, RECORD := wPKE_AND_IND_AND_PWE);

Axis Capability and Cycle Times

The CU320-2 in the documented S120 line-up supports up to 6 servo drives (12 V/f) in one control unit. The D4x5-2 SIMOTION variants do not change the underlying SINAMICS S120 limit; the S120 cabinet can be reused identically, the difference is the controller sitting on top.

Axis and cycle comparison
Parameter CU320-2 + S7-300 D455-2 DP/PN + S120
Max. drive axes (per control unit) 6 servo / 12 V/f 6 servo (in S120), up to 64 in SIMOTION
Current controller cycle 125 µs 125 µs (in S120)
Speed controller cycle 250 µs 250 µs (in S120)
Position controller cycle 1-4 ms 1-4 ms (in S120) / 0.5-2 ms (SIMOTION)
IPO cycle (SIMOTION) N/A 0.5-4 ms configurable
Servo cycle (SIMOTION) N/A 0.5-2 ms configurable
PROFINET IRT Optional (CBE20 in CU320-2 PN) Standard on D455-2 PN

The drive-side current and speed loops always live in the SINAMICS firmware; they are unchanged by the choice of controller. The position loop sits at the SIMOTION D level (or inside the CU320-2 in the legacy split). For high-bandwidth, multi-axis coordination, SIMOTION D owns the position loop and achieves tighter cross-axis coupling than the PLC + drive split.

System Topology

The two architectures map onto different physical topologies. In the S7-300 + CU320-2 reference, the PROFIBUS cable runs from the CPU to the CU320-2, and DRIVE-CLiQ fans out from the CU320-2 to the Smart Line Module and the five Single Motor Modules.

Reference Architecture: S7-300 + CU320-2 with SINAMICS S120 CPU 315-2DP SIMATIC S7-300 PROFIBUS Master CU320-2 Drive Control Unit S120 Firmware 6SL3130 SLM Smart Line Module 16 kW PROFIBUS DP 12 Mbaud DRIVE-CLiQ Single Motor Modules 4 x 6SL3120-1TE15-0AA3 (5 A) 1 x 6SL3120-1TE21-0AA3 (9 A) DRIVE-CLiQ from CU320-2 1FK7 Servo Motors (5x) 4 x 1FK7060 + 1 x 1FK7083 DRIVE-CLiQ bus topology SIMOTION D4x5-2 alternative Combines PLC + drive control in one module Replaces CPU 315-2DP and CU320-2 Connects to same S120 line-up via DRIVE-CLiQ PROFINET PN variant for IRT drives Native _gear, _cam, _add commands Up to 64 axes, 0.5 ms IPO

With SIMOTION D4x5-2, the CPU 315-2DP and the CU320-2 are replaced by a single SIMOTION D module in the same rack. The DRIVE-CLiQ, SLM, and 1FK7 motors remain physically unchanged. On PROFINET, the SLM and the Motor Modules connect to the SIMOTION D -PN port as PROFINET IO devices.

When to Choose SIMOTION D

Use the following decision matrix for projects that start as a simple S7-300 + S120 architecture but are heading toward synchronized motion:

  1. Electronic gearing or camming required — Choose SIMOTION D. The _gear, _cam, and _add (additive setpoint) commands in MCC are a fraction of the equivalent STEP 7 + S120 logic.
  2. Cross-axis register, mark correction, or print-mark synchronization — Choose SIMOTION D. The _measInput and _cam commands handle this natively.
  3. Line-shaft or virtual master — Choose SIMOTION D. The virtual master is a built-in Technology Object.
  4. Path interpolation (X-Y-Z coordinated motion) — Choose SIMOTION D with the path object. Not possible on CU320-2 alone.
  5. More than 6 axes, deterministic cycle below 1 ms — Choose SIMOTION D. The D455-2 supports 64 axes and 0.5 ms IPO.
  6. Simple sequential single-axis point-to-point — Stay with S7-300 + CU320-2. Lower hardware cost, lower training cost, faster commissioning.
  7. Mix of motion and large non-motion PLC program — Either architecture works, but S7-300 + CU320-2 keeps the motion and PLC code in familiar editors.

Migration Path and Commissioning

Migrating from S7-300 + CU320-2 to SIMOTION D is incremental, not a rip-and-replace. The cabinet layout, the S120 line-up, the line filter, the line reactor, the Smart Line Module, and the 1FK7 motors all stay. Only the controllers change.

  1. Hardware exchange — Remove the CPU 315-2DP and the CU320-2. Install the SIMOTION D4x5-2 in the same rack footprint. The D425-2 and D435-2 use the S7-300 200 mm rail mount; the D445-2 and D455-2 use 300 mm.
  2. Wiring review — PROFIBUS DP master moves into the SIMOTION D -DP variant. PROFINET IRT can replace DP if the CU320-2 is replaced with a CU320-2 PN (CBE20 plugged in). DRIVE-CLiQ from the S120 modules to the SIMOTION D -DP/PN remains unchanged.
  3. Project conversion — Import the S120 commissioning archive (created in STARTER or SCOUT) into the new SCOUT project. The S120 drive parameters carry over.
  4. PLC logic port — STEP 7 LAD and FBD translate cleanly to SIMOTION D LAD and FBD. ST and SCL are virtually identical. GRAPH sequences are typically re-implemented in MCC for motion segments.
  5. Commissioning checklist:
    • DRIVE-CLiQ topology correctly auto-detected (all Motor Modules green)
    • Encoder values match the mechanical position
    • Limit switches tested in software (SW-limit) and hardware (HW-limit)
    • Safe Torque Off (STO) wired through the SIMOTION D -PN/DP safety channel or a separate SIRIUS safety relay
    • EMC grounding per SINAMICS S120 booksize manual
  6. Acceptance test — Run each axis individually under jog, then under MDI, then under the full MCC sequence with reduced velocity. Confirm MELDW.3 (acknowledgment) and POS_ZSW.0 / .1 / .2 bits.

For the exact steps in TIA Portal V20 — drag a SINAMICS S120 CU320-2 PN from the catalog folder Controller > SIMOTION > SIMOTION drives > SINAMICS S120, drop it into the network view, and connect it to the SIMOTION D -PN port — see the official TIA Portal SCOUT device configuration guide.

Configuring a SIMOTION D455-2 DP/PN with SINAMICS S120 CU320-2 PN over PROFINET IO (TIA Portal V20)
Safety note: The SINAMICS S120 STO input is a hardwired safe input. Wiring it through the SIMOTION D -F variant (PROFIsafe) keeps the safety loop inside the controller; wiring it through a 3SK safety relay keeps the loop outside and avoids the PROFIsafe engineering overhead. Either approach is field-accepted; the choice depends on the safety architecture in the wider machine.

Diagnostic and Fault Handling

Both architectures expose the S120 diagnostic buffer, but the access path differs.

Diagnostic entry points
Fault Source S7-300 + CU320-2 SIMOTION D4x5-2
Drive fault (F-code) Read via S7 DPV1 read record (PKE, IND, PWE) on the CU320-2 PROFIBUS slot Direct in SCOUT > Diagnostics > SINAMICS
Alarm (A-code) Same DPV1 read or STARTER online Alarm buffer inside the TO and in SCOUT
Encoder fault STARTER or SINAMICS Startdrive SCOUT > Axis > Actual values
Following error Read r2560 in STARTER Axis._Status.FollowingError in program
SIMOTION kernel fault N/A Diagnostic buffer in SCOUT > Project > Diagnostics

Common SINAMICS S120 faults to expect during commissioning of a 1FK7 / 6SL3120 line-up:

  • F30002 (DC bus overvoltage) — check Smart Line Module 6SL3130 firmware version, verify line filter 6SL3000-0BE21-6DA0 grounding.
  • F31117 (encoder error) — confirm DRIVE-CLiQ cable pinout, replace if damaged.
  • F07900 (drive: motor blocked) — tune p2175 (motor blocked speed threshold) and p2177 (motor blocked delay).
  • A30016 (load supply switched off) — verify 24 V to the Motor Module from the SLM.

Common SIMOTION D4x5-2 faults:

  • 20002 (axis not homed) — execute _homing command before _MOVE.
  • 20005 (axis not enabled) — set Axis._Enable := TRUE and confirm drive enable (STW1.0).
  • 20130 (cam not interpolated) — verify IPO cycle is shorter than the interpolation step size.

Troubleshooting Matrix

Common commissioning faults and first-line checks
Symptom First Check (S7-300 + CU320-2) First Check (SIMOTION D4x5-2)
Axis will not move STW1.0 (ON/OFF1), STW1.3 (Enable), STW1.13 (Enable traversing block) Axis._Enable, Axis._CommandEnable, axis state machine
Position overshoots Check telegram 105, MD position controller gain (p2532) Axis._KvFactor, _PosCtrl._Gain, _FollowingErrorLimit
Following error alarm r2560 exceeds p2546 (max following error) Axis._Status.FollowingError, increase _FollowingErrorLimit
Encoder counts not updating STARTER online > actual values, check DRIVE-CLiQ SCOUT > Axis > Actual values, check encoder wiring
PROFIBUS station failure SF LED on CPU, diagnostic buffer DP slave diagnostic, SCOUT > Connect to target system

Lifecycle and Spare-Part Considerations

The S7-300 platform entered the phase-out announcement window in 2023, with delivery subject to availability through 2028 in many regions. SIMOTION D4x5-2 DP/PN is currently in active sale and is positioned as the strategic migration path. New greenfield projects that anticipate synchronized motion should design in the D4x5-2 from the start. Existing S7-300 + CU320-2 installations are still serviceable and supported with spares through the announced phase-out window. The SINAMICS S120 booksize platform itself (the line-up used in the reference project) remains a current product and is reused unchanged in SIMOTION D applications.

When buying spare Motor Modules for a SIMOTION D migration, confirm the DRIVE-CLiQ firmware version is compatible with the SIMOTION SCOUT version. A Motor Module running older firmware than the SCOUT expects will fail to commission and emit a topology error at download. The minimum recommended SINAMICS S120 firmware for SIMOTION D4x5-2 DP/PN is V5.2 SP3, with V5.3 or later preferred for new projects.

Frequently Asked Questions

Does SIMOTION D replace both the CPU 315-2DP and the CU320-2?

Yes. A SIMOTION D4x5-2 DP/PN combines the PLC runtime, motion controller, and the drive control unit functions in one module. The SINAMICS S120 power section (Smart Line Module, Single Motor Modules) and the 1FK7 motors stay in place; only the control unit and the SIMATIC PLC are removed.

Can the existing 6SL3120 Single Motor Modules and 1FK7 motors be reused with SIMOTION D?

Yes. The DRIVE-CLiQ wiring, the line filter 6SL3000-0BE21-6DA0, the line reactor 6SL3000-0CE21-6AA0, and the 1FK7 motor cables are all retained. Only the controller above the Smart Line Module changes. Commissioning the SINAMICS S120 in SCOUT carries over the existing STARTER project.

What is the maximum number of axes on a SIMOTION D455-2?

The D455-2 DP/PN supports up to 64 axes, with a minimum IPO (interpolator) cycle of 0.5 ms and a minimum servo cycle of 0.5 ms. The D425-2 supports 16 axes, the D435-2 supports 24 axes, and the D445-2 supports 32 axes.

Which PROFIBUS telegram should be selected for a 1FK7 servo on CU320-2?

For positioning with an S7-300, select telegram 105 (servo with 32-bit position) or telegram 3 (positioning with 32-bit position). Telegram 105 is the default for SIMOTION D integration and provides 16-bit control / 16-bit status plus 32-bit position actual and setpoint, which is the most efficient choice for sequenced point-to-point motion.

When is PROFINET IRT required over PROFIBUS DP?

PROFINET IRT is required when the position loop must run at sub-1 ms deterministic cycle across multiple drives, or when the topology needs cut-through switching and fiber-optic cabling. For the 5-axis, 4-ms-position-loop configuration in the reference project, PROFIBUS DP at 12 Mbit/s is sufficient and remains the lower-cost path.

Back to blog