SINAMICS PM230 EMC/EMI: P1800 Limits, Filters, Cable Screening

David Krause22 min read
SiemensTroubleshootingVFD / Drives
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

1. Problem Description

A SINAMICS PM230 unfiltered output power module, part number 6SL3210-1NE31-5UL0, rated for 75 kW, has been installed as part of the propulsion or auxiliary-drive system of a vessel. From the moment the inverter is enabled, low-voltage thermocouple signals feeding the ship's automation network drift and produce erroneous temperature readings. The fault is independent of motor load, and the disturbance disappears within a fraction of a second after the inverter is stopped. The motor feeder has already been wired with a screened, low-capacitance cable, but the screening alone has not eliminated the coupling. The three open engineering questions are:

  1. Why does parameter P1800 reject the value 2 kHz even though P1801 appears to indicate a 2 kHz minimum?
  2. What is the practical difference between a filtered and an unfiltered PM230, and what is the most economical output filter for a 75 kW load?
  3. Can the unfiltered unit be returned to Siemens Italy to be retrofitted to a filtered variant?
All ratings in this article are written for a 75 kW PM230 on a 3-phase 400 V ship distribution. Where the source is silent on a specific value, the assumption is stated explicitly so the engineer can verify against the device rating plate and the firmware parameter list.

2. Affected Hardware and Configuration

The unit at the centre of this case is identified from the MLFB as follows:

Item Value
Siemens part number (MLFB) 6SL3210-1NE31-5UL0
Drive family SINAMICS G120 — PM230 power module
Filter status Unfiltered (suffix UL0)
Power class 75 kW (verify Heavy-Duty or Low-Overload rating on rating plate)
Rated line voltage 3 AC 380–480 V
Frame size (typical) FSE; verify against MLFB structure
Default pulse frequency 4 kHz
Typical minimum selectable pulse frequency at this power class 2 kHz; firmware-dependent — confirm against parameter list
Maximum permissible motor cable length, unfiltered, without output reactor 50 m screened (typical, see manual)

The UL0 suffix means no integrated line-side EMC filter is fitted. The unit is intended for cabinet installations where an external filter is mounted on the line side, or for installations where conducted-emission limits do not apply. On a vessel, EMC requirements are dictated by the classification society (DNV, Lloyd's Register, ABS, BV, RINA) and by IACS UR E22. Shifting the EMC compliance burden to the system integrator means the integrator must add filtering, screening, and bonding discipline to bring emissions under control.

For full device ratings, refer to the SINAMICS G120 PM230 operating instructions on Siemens Industry Online Support and to the SINAMICS G120 parameter manual for the firmware build currently loaded on the unit.

3. PWM Ringing and EMI Coupling Physics

The dominant interference mechanism on the load side of any IGBT inverter is not the supply-side harmonics but the high-frequency common-mode (CM) voltage that the inverter's pulse-width modulation creates between the DC bus negative rail and the chassis (PE). The PM230 switches the IGBTs at a programmed pulse frequency that is typically 4 kHz by default. Each switch transition has a rise time in the 50–200 ns range, which produces a voltage step with a slope du/dt easily exceeding 5 kV/μs.

This step is impressed across the stray capacitance of the motor cable (typically 0.2–0.4 nF/m between conductor and screen for a standard 4-core motor cable). The CM current that flows as a result is:

I_CM = C_cm · dV/dt

For a 20 m cable at 0.3 nF/m and 5 kV/μs:

I_CM = (20 · 0.3e-9) · (5e9) = 30 mA peak CM current per conductor

The total CM current summed across all three phases and re-circulated through the screen is of the order of tens of milliamps with sub-microsecond edge rates. The spectral content extends well into the VHF band (30–300 MHz), which is why the disturbance is referred to as "MHz ringing" in the field report. The wavelength of a 100 MHz signal is 3 m in free space, so a 20 m motor cable behaves as a multi-wavelength transmission line for this interference, with the cable screen acting as the return path.

The interference enters thermocouple circuits because:

  1. Thermocouple voltages are in the 0–50 mV range, and even a few millivolts of coupled noise represents a temperature error of several tens of degrees for a type K thermocouple (41 μV/°C).
  2. Thermocouple extension wire typically has no screen, and the input stage of a marine automation analogue card has high input impedance and limited CM rejection at VHF.
  3. The PM230 chassis, the motor frame, and the automation cabinet are coupled through the ship's hull and bonding network, providing a low-impedance return path that the disturbance will exploit if the dedicated return path (the motor cable screen) is broken or high-impedance.

4. Root Cause Analysis

From the discussion thread, four interacting root causes are present in this installation:

4.1 PWM MHz common-mode voltage on the load side

The pulse-frequency default of 4 kHz produces edge rates high enough to drive substantial CM current through the motor cable capacitance. The PWM fundamental itself is not the problem — the resonant overshoot and ringing created by the IGBT commutation loop, the cable inductance, and the motor winding capacitance are the problem. This ringing typically settles within 200–500 ns and produces a damped oscillation in the 20–80 MHz range.

4.2 Screen bonding not adequately low-impedance at VHF

Pigtails, earthing posts, and short jumper wires all look low-impedance at 50 Hz but become inductive at VHF. At 50 MHz the impedance of a 50 mm pigtail is already 16 Ω, and at 100 MHz it exceeds 30 Ω. The screen must be clamped to the chassis with a 360° bond (EMC backshell or saddle clamp) at both the inverter end and the motor end, and that bond must be continuous through any isolator fitted in the cable.

4.3 Multiple parallel return paths through the ship's bonding network

If the dedicated screen return path is not the lowest impedance available, the disturbance will return to the inverter through whatever path is lower — typically the ship's hull, the automation cabinet earth bus, and the thermocouple cable shields. This is why a 10 m thermocouple run behaves as if it is sitting directly on the inverter CM noise source.

4.4 No output filtering to limit du/dt and peak voltage

An unfiltered PM230 has no dv/dt reactor and no sine filter on its output. The IGBT edge rate reaches the motor terminals unchanged. At cable lengths above the manufacturer's shielded-cable limit, peak voltages at the motor terminals can exceed 1.5 kV, accelerating winding insulation ageing and broadening the conducted and radiated emission spectrum.

5. Diagnostic Procedure

Run the following procedure before changing any hardware or parameters. Each step isolates one root cause.

  1. Read the active fault and alarm buffer from the PM230 (r0947 / r2122) and note any F30002 (DC-link overvoltage), F30004 (converter overtemperature), F07900 (motor blocked) or F07801 (motor overtemperature) entries.
  2. Capture P1800, r0027 (actual output current), r0037 (converter temperature), and r0206 (rated power unit power) via STARTER, Startdrive, or the IOP/BOP.
  3. With the drive enabled and the motor unloaded, use a battery-powered oscilloscope (not a mains-powered scope) and a high-voltage differential probe to view the line-to-line voltage at the inverter output terminals. Look for ringing with a peak above 1.4 · V_DC-link and a frequency above 20 MHz.
  4. With the same scope, view the CM voltage between any output phase and the cabinet chassis earth bar. A reading above 30 V peak at the PWM fundamental indicates that the cabinet earth bar is carrying substantial CM current.
  5. Move the scope probe to the screen of the motor cable at the inverter end. Measure the screen-to-chassis voltage. Anything above a few hundred millivolts peak indicates that the screen bond at that point is inadequate.
  6. Disconnect the motor cable screen from the motor junction box and re-measure with a low-resistance bond (≤ 5 mΩ DC, verified with a four-wire milliohm meter) at the screen gland.
  7. Repeat the thermocouple reading test with the drive stopped vs the drive enabled at zero speed reference. If the noise disappears when the drive is stopped, the coupling path is from the inverter, not from the ship's electrical system.

Document each measurement. They form the baseline against which every change is verified.

6. Resolving P1800 Pulse-Frequency Limits

The first question is why P1800 will not accept 2 kHz. Three mechanisms can cause this. Work through them in order.

6.1 Confirm what P1801 actually represents

In the standard SINAMICS G120 parameter list for the PM230 firmware in question, there is no universal parameter named P1801 that exposes a "minimum pulse frequency" setting. P1800[0...n] is the only pulse-frequency write parameter, and it is indexed (one entry per Drive Data Set in most G120 configurations). The figure shown on the BOP/IOP that the operator has read as "P1801" may in fact be:

  • A read-only display parameter such as r0113 (pulse frequency recommendation) or r0024 (output frequency).
  • One index of P1800 shown without its index, in which case only P1800[0] has been edited while another index (e.g. P1800[1]) still holds the higher factory default.
  • A customer-specific parameter introduced by a project-specific parameter set, or a misread parameter number.

Cross-check against the parameter list of the firmware build installed on the CU. The exact list is part of the SINAMICS G120 parameter manual matching the firmware version of the Control Unit.

6.2 Drive operating state and access level

P1800 can only be written when the drive is in commissioning access level and not in Run. The relevant conditions are:

  • Drive in state S1 (Commissioning) or S2 (Ready for operation), not S3 (Run) or S4 (Fault active).
  • BOP access level set to "Expert" (parameter P0003 = 3) or higher; some firmware variants gate P1800 behind "Expert" access.
  • No active safety function preventing pulse-frequency reduction. STO does not lock P1800, but SS1 with a time-to-ramp shorter than 200 ms can override it.
  • No active bypass contactor or motor changeover (if a motor changeover is configured, P1800 is locked at the higher value used for the larger motor).

6.3 Power-module-specific floor

For PM230 power modules, the minimum pulse frequency rises with the rated current of the unit. For 75 kW PM230 units (frame FSE), the firmware typically enforces a minimum pulse frequency of 4 kHz in some firmware builds and 2 kHz in others. If the installed firmware enforces 4 kHz, the rejection of 2 kHz is correct operation, not a configuration error.

To resolve:

  1. Read r0190 (Power unit identification) and confirm the MLFB structure against the part number on the rating plate.
  2. Read r0200 (actual power unit code number) and confirm it matches the firmware-expected code number.
  3. Read the firmware version of the CU (read from r0018 or from the firmware download log) and consult the parameter list for that exact version.
  4. If the floor is firmware-enforced, the 4 kHz default cannot be reduced to 2 kHz by parameter editing alone. The remaining option is to reduce the disturbance at the source by adding an output filter (Section 8) and tightening the screen bonding (Section 9), not by reducing the switching frequency.
Reducing pulse frequency increases thermal stress on the IGBTs and reduces the usable output current. PM230 ratings are derated above and below the default pulse frequency. Always cross-check the derating curves in the operating instructions before editing P1800.

7. Filtered vs Unfiltered PM230 Comparison

Aspect Unfiltered PM230 (UL0) Filtered PM230
Internal line-side EMC filter None Class A1 / A2 EMC filter, sized for the unit
Required external line filter Yes — must be sized for I_n and cable length Typically none; cabinet mounting still requires care
Earth-leakage current contribution Low (no filter capacitance to PE) High (each filter stage adds capacitance to PE)
Ship generator RCD behaviour No interaction Risk of nuisance tripping; ship earth-leakage monitoring can detect the filter discharge current
Compliance path for IACS UR E22 External filter + cabinet layout discipline Internal filter combined with cabinet layout
Cost Lower unit cost Higher unit cost; reduced engineering effort
Typical MLFB suffix pattern UL0 AL0 or similar (verify on rating plate)

The ship installation described in the source already shows the symptom of a class-A filter being unsuitable: nuisance tripping of the generator earth-fault detection caused by filter discharge current. The discussion thread explicitly warns that supply-side filters can encourage such trips. The filtered PM230 has the same problem because the filter capacitance is internal to the unit and cannot be bypassed. This is why the most economic answer is often not to add a line filter at all, but to combine:

  1. Output filter (dv/dt reactor or sine filter) on the load side.
  2. Disciplined screen bonding on the motor cable.
  3. Physical separation and routing of the thermocouple cable away from the motor feeder.

8. Output Filter Selection for 75 kW

Three output filter topologies are viable for a 75 kW PM230. Their effects on the noise mechanism in this case differ.

Filter type Effect on du/dt Effect on CM noise Effect on motor peak voltage Effect on cable-length limit Cost (relative)
dv/dt reactor (load reactor) Reduces to < 500 V/μs Marginal Limits peak to < 1 kV Increases to ~100–150 m screened Low
Sine filter (LC low-pass) Reduces to a near-sinusoidal output Substantial Limits peak to < 1 kV, sinusoidal Increases to 300 m+ screened High
Voltage Clamping Limiter (VPL) Clamps peak to a fixed voltage Substantial Limits peak to < 1 kV Increases to 150 m+ Medium

For thermocouple-noise mitigation on a 75 kW drive, a sine filter is the most effective because it converts the PWM output to a near-sinusoidal waveform and removes the high-frequency harmonics responsible for CM coupling. A dv/dt reactor is cheaper but does not suppress the CM noise enough to fully resolve a thermocouple pickup problem. The Voltage Clamping Limiter (VPL) is the most cost-effective compromise where motor insulation protection is also a concern.

8.1 Filter sizing

Use the following approach to size the filter for a 75 kW PM230 on a 400 V line:

  1. Calculate the base impedance from the rated three-phase apparent power:
Z_base = V_LL² / S_3ph = (V_LL)² / (sqrt(3) · V_LL · I_n) = V_LL / (sqrt(3) · I_n)

For a 75 kW unit at 0.85 power factor:

S_3ph = 75 / 0.85 = 88.2 kVA Z_base = 400² / 88200 = 1.81 Ω
  1. Select filter inductance at 2–3 % of base impedance for a dv/dt reactor, or at 5–8 % for a sine filter:
L_reactor_2% = (0.02 · Z_base) / (2π · 50) ≈ 115 μH L_sine_6% = (0.06 · Z_base) / (2π · 50) ≈ 345 μH
  1. Verify the filter continuous current rating is ≥ the drive rated output current. At 75 kW on 400 V, this is approximately 145 A (verify against the unit's r0207).
  2. Verify the filter switching-frequency compatibility — the filter must be rated for the actual switching frequency that P1800 is set to, with margin for transient excursions.
The exact Siemens MLFB for the matching dv/dt reactor or sine filter for the 6SL3210-1NE31-5UL0 must be cross-referenced against the SINAMICS G120 accessories catalogue and the operating instructions. Do not assume a filter from a different drive family is compatible — the IGBT module, gate drive, and fault handling differ between PM230, PM240, PM250 and PM260.

9. Cable Screening and Bonding Procedure

Before adding any filter, apply the following screening discipline. The field report thread is unambiguous that screen bonding is the single highest-impact intervention.

9.1 Required materials

  • EMC backshells (or saddle clamps) sized for the motor cable outer diameter, at both ends.
  • Bonding braid or short strap (≤ 50 mm length) from the EMC backshell to the cabinet chassis at the inverter end.
  • EMC cable gland at the motor junction box, providing 360° contact with the screen.

9.2 Procedure at the inverter end

  1. Strip the motor cable outer sheath back far enough to expose 25–40 mm of the braided screen, while leaving the screen intact and continuous.
  2. Fit the EMC backshell so the saddle clamps the exposed screen with full circumferential contact. Verify the clamp compresses the screen onto a bare-metal saddle.
  3. Bond the backshell body to the cabinet chassis via a short braid (≤ 50 mm) to a chassis-bonding stud. Do not pigtail the screen to an earth post.

9.3 Procedure at the motor end

  1. Use an EMC cable gland rated for the cable diameter. The gland's contact ring must bear directly on the screen.
  2. Verify the motor junction box body is bonded to the motor frame with a low-impedance bond (≤ 5 mΩ).
  3. Confirm the motor frame is bonded to the ship's hull at the motor mounting feet. On a steel-hulled vessel this is automatic; on aluminium or GRP hulls a dedicated bonding strap is mandatory.

9.4 Procedure through any isolator

If a switch-disconnector or isolator is fitted in the motor feeder:

  1. Do not interrupt the screen inside the isolator. The screen must remain continuous.
  2. Clamp the entering and leaving screens together inside the isolator with a saddle clamp, so the screen is bonded across the isolator body.
  3. Bond the isolator body to the same chassis earth bar as the inverter.

9.5 Screen-to-screen contact verification

After assembly, measure the DC resistance from the screen at the inverter end to the screen at the motor end. The reading should be below 100 mΩ for a 20 m cable. Above 1 Ω indicates a broken screen or a pigtail that needs to be replaced.

10. Isolator and Thermocouple Handling

The thermocouple interference observed in the field report is a direct consequence of the noise currents finding a return path through the ship's bonding network and through the thermocouple wiring. Two interventions are needed.

10.1 Route and shield the thermocouple cable

  1. Replace the existing thermocouple extension wire with a screened, twisted-pair type. Screen must be a foil-plus-braid or a metallised-foil with a drain wire.
  2. Terminate the screen at the automation cabinet end only — do not bond the screen at the thermocouple head end. This prevents ground-loop current from flowing in the screen.
  3. Use a bonding clamp at the cabinet gland plate, with a short bond (≤ 50 mm) to the analogue-earth bar.

10.2 Increase physical separation

  1. Maintain at least 200 mm separation between the motor feeder and any analogue signal cable throughout the cable run. Cross them at 90° if they must cross.
  2. Where the motor feeder runs through a trunk or tray, route the thermocouple cable in a separate tray with a metal divider.
  3. For new installations, use a screened, twisted-pair cable with a separate integral drain wire and bond the screen at one end only.

10.3 Verify against the source warning

The field report explicitly warns that the screen end at the inverter "must be clamped to the chassis, rather than trying to terminate the screen to an earth post." This is because the chassis bond is short and wide (low impedance at VHF), whereas an earth post is typically connected via a pigtail or a short wire that has substantial inductance above 10 MHz. Apply this principle consistently at every screen termination in the system.

11. Retrofitting the PM230 to a Filtered Variant

The third source question — whether the unfiltered PM230 can be sent to Siemens Italy to be upgraded — is not a standard service path. The filter PCB in a PM230 is mounted inside the unit during manufacture and the unit's rating plate carries the filter designation (e.g. UL0 vs AL0). Field retrofits to a different filter designation are not part of the standard service offer, because:

  • The MLFB is printed on the rating plate and the unit's certificate refers to that MLFB.
  • The internal filter is matched to the IGBT module's switching characteristics.
  • EMC compliance testing on a vessel refers to the as-installed configuration.

The correct path is to:

  1. Order a replacement PM230 with the filtered designation (the AL0 or equivalent MLFB matching the unfiltered part's electrical ratings). Confirm the exact MLFB with the Siemens regional office.
  2. Return the unfiltered unit under the standard RMA process via the local Siemens service contact for repair, not retrofit.
  3. If EMC compliance for the vessel still cannot be met with the filtered unit (because of generator earth-leakage interaction), use an external output reactor or sine filter and keep the unfiltered unit.

Contact the regional Siemens service desk through the official Siemens Industrial Automation contact page for the precise RMA and replacement process for the vessel's flag state and classification society.

12. Verification Checklist

Run this checklist after each intervention. A change is successful only if every item below is satisfied.

  1. Drive operates at rated speed and rated load without raising F30002, F30004, F07801 or any new fault.
  2. r0027 (output current) is within the unit's continuous rating.
  3. Drive temperature r0037 stabilises within the rated envelope after 2 hours of full load.
  4. Line-to-line voltage at the motor terminals shows no ringing above 1.4 × V_DC-link on the oscilloscope.
  5. CM voltage at the inverter cabinet earth bar is below 5 V peak with the drive running at rated load.
  6. Screen-to-screen DC resistance is below 100 mΩ for a 20 m cable.
  7. Thermocouple reading at the automation HMI matches a reference instrument (handheld calibrator or a second thermocouple with a separate routing) within the documented accuracy class.
  8. Vessel classification society EMC verification (IACS UR E22 or equivalent) passes.
  9. Generator earth-leakage monitor does not record nuisance trips during drive start, run, or stop.

13. Troubleshooting Matrix

Symptom Likely cause First action
Thermocouple reading drifts only when inverter runs CM noise from PWM ringing coupling into analogue input Apply Section 9 screen bonding; add output filter (Section 8)
P1800 rejects 2 kHz Firmware floor or wrong access level Check Section 6.2; confirm firmware build; consider keeping default 4 kHz
Generator RCD trips when inverter starts Line-side EMC filter discharge current Remove external line filter; use output-side filter instead
Motor winding insulation failure within warranty Peak voltage from PWM exceeding insulation rating Add dv/dt reactor or sine filter; check cable length against Section 8.1
Interference worse at long cable runs (> 50 m) Standing wave on motor cable, transmission line effect Add output reactor; consider sine filter
Interference appears only at specific motor speeds Mechanical resonance modulating CM coupling Change switching frequency via P1800 if firmware permits; verify derating
Interference persists after screen bonding Common-mode current returning through ship's hull Verify single-point bonding of automation cabinet to hull; isolate analogue earth
Interference appears only when isolator is operated Screen continuity broken inside isolator Apply Section 9.4 procedure; clamp entering and leaving screens together

14. Safety and Classification Notes

All work on the PM230 and its associated cabling must be carried out with the drive isolated, locked out, and the DC-link discharged per the SINAMICS G120 operating instructions. Wait at least five minutes after isolation before opening any cabinet door. Verify the DC-link voltage at a test point before touching any conductor.
EMC compliance on a vessel is part of the classification society survey. Any change to the drive configuration, filter topology, or bonding network must be reflected in the vessel's EMC documentation. Notify the classification society surveyor before re-commissioning if the change is material to the EMC technical file.

For the absolute limits on pulse frequency, derating curves, motor cable length, and output filter selection, always defer to the current revision of the SINAMICS G120 PM230 operating instructions and the SINAMICS G120 parameter manual matching the firmware build installed on the Control Unit. The parameter values, fault codes, and MLFB structures referenced in this article are based on the published Siemens documentation available at the time of writing and may have been revised in subsequent firmware releases.

Why does P1800 on a 75 kW PM230 reject 2 kHz even when the display shows a 2 kHz minimum?

On PM230 power modules at the 75 kW rating, several firmware builds enforce a 4 kHz floor on P1800 because of IGBT thermal and current-ripple limits at this power class. The display value the operator read as "P1801" is typically r0113 (recommended pulse frequency) or an indexed entry of P1800 that has not been written. Check the access level (P0003 = 3 for Expert), confirm the drive is in commissioning state, and verify against the firmware-specific parameter list. If the firmware floor is 4 kHz, accept it and reduce EMI through output filtering and screen bonding instead.

What is the most economical output filter for a 75 kW PM230 on a ship?

A dv/dt reactor (load reactor) is the cheapest and addresses peak voltage and motor insulation stress. For thermocouple-noise mitigation specifically, a sine filter is significantly more effective because it removes the high-frequency harmonics responsible for common-mode coupling, but it costs more and adds voltage drop. Select on the basis of the dominant symptom: insulation protection → dv/dt reactor; analogue-signal interference → sine filter. Confirm the filter MLFB against the SINAMICS G120 PM230 accessories catalogue for the installed firmware build.

Can the PM230 UL0 unit be sent to Siemens Italy to be retrofitted to a filtered variant?

No — Siemens does not offer a field retrofit from unfiltered (UL0) to filtered (AL0 or equivalent) PM230. The internal filter is part of the manufacturing build and the MLFB on the rating plate is the certificate of conformity. The correct path is to order a replacement filtered unit with matching electrical ratings and return the unfiltered unit under the standard RMA process for repair. If the filter interacts with the ship's generator earth-leakage detection, retain the unfiltered unit and add an output-side filter instead.

Does adding a line-side EMC filter help with thermocouple noise on the load side?

Not for thermocouple pickup. Line-side filters address conducted emissions on the supply side, not common-mode voltage on the load side. The dominant interference mechanism for thermocouple noise is the PWM common-mode voltage at the motor terminals, which is governed by the output-side switching behaviour, the motor cable capacitance, and the screen bonding. Adding a line-side filter without addressing the output side will not solve the problem and can introduce earth-leakage current that trips the vessel's generator protection.

How do I terminate the motor cable screen to stop the MHz interference?

Use a 360° EMC backshell or saddle clamp at both ends. Bond the backshell body to the cabinet chassis (inverter end) and to the motor junction box (motor end) with a bond length of 50 mm or less. Do not pigtail the screen to an earth post. If an isolator is fitted in the motor feeder, keep the screen continuous through it and clamp the entering and leaving screens together inside the isolator body. Verify the screen-to-screen DC resistance is below 100 mΩ for a 20 m cable.

Back to blog