SINAMICS S110 CU305 CAN: RS232 X22 Connection to STARTER

David Krause21 min read
SiemensTutorial / How-toVFD / Drives
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Overview

The SINAMICS S110 Control Unit CU305 CAN (MLFB 6SL3040-0JA02-0AA0) is the CAN-bus variant of the modular single-axis servo drive controller in the SINAMICS S110 family. The unit is identified by the Machine-Readable Product Code on the front-panel nameplate, by the firmware version reported in parameter r0018, and by the three status LEDs (RDY, COM, OPT) on the front cover. The CU305 CAN is typically paired with a SINAMICS PM340 (Blocksize format) power module in the 1AC 230 V, 3AC 400 V, or 3AC 480 V class.

Three practical paths exist for connecting a PG/PC to the CU305 CAN for commissioning:

  1. X22 service interface (RS232 / point-to-point / USS) — universal across all CU305 variants, requires only a null-modem cable.
  2. X126 (CAN bus, CANopen protocol) — requires a USB-to-CAN adapter such as PEAK PCAN-USB or Vector VN1610.
  3. PROFIBUS / PROFINET — not native to the CAN variant. Use a CU305 DP (6SL3040-0JA01-0AA0) or CU305 PN (6SL3040-0JA00-0AA0) variant instead.

This article covers the X22 RS232 service interface path in depth, including cable wiring, USB-to-serial adapter selection, STARTER configuration, and the commissioning workflow. The X126 CANopen path and the safety / STO wiring are covered as secondary topics because they are commonly requested in the same commissioning session.

The authoritative reference for the S110 platform is the SINAMICS S110 Equipment Manual and the product support page at Siemens Industry Online Support for 6SL3040-0JA02-0AA0. Always verify the chapter for your specific firmware version — the pinout and parameter set are stable, but parameter ranges and default values evolve across firmware versions.

Hardware Identification

Field Value
MLFB (Order Number) 6SL3040-0JA02-0AA0
Product Designation SINAMICS S110 Control Unit CU305 CAN
Fieldbus CAN bus / CANopen
Service Interface RS232 (X22), 9-pin D-sub male (DTE)
Encoder Interface DRIVE-CLiQ + SMx encoder modules (resolver, EnDat, sin/cos, TTL via SMC/SME)
Status LEDs RDY (Ready), COM (Communication), OPT (Optional module)
Memory Card Slot X1, accepts Siemens 6SL3054-0AA01-1AA0 (8 MB) and 6SL3054-0AG01-1AA0 (512 MB)
PE Stud (Control Unit) M6, ring cable lug 10–50 mm²
PE Stud (Power Module) M8, ring cable lug max 120 mm²

Confirm the MLFB on the nameplate before connecting. The DP and PN variants look identical from the front but have different firmware images and fieldbus connectors.

Prerequisites

  • PG/PC with Windows 7 SP1 / Windows 10 (32-bit or 64-bit), at least one free USB port, or a built-in RS232 COM port.
  • STARTER commissioning tool, version V4.5 SP1 or later (V5.5 HF1 is the last version to officially support the S110 device family for legacy reasons). The S110 device description is bundled in STARTER from V4.4 onwards.
  • Alternative: Startdrive in TIA Portal V13 SP1 / V14 / V15.1 / V16 / V17. Startdrive replaces STARTER for new installations.
  • Null-modem (crossover) RS232 cable, 9-pin D-sub female to 9-pin D-sub female, with TxD and RxD crossed.
  • If the PC has no DB9 COM port, a USB-to-RS232 adapter based on a proven chipset (FTDI FT232R or Silicon Labs CP2102N).
  • 24 V DC supply at the CU305 X124 terminal (the CU305 is not powered from the PM340 DC link alone — the control electronics require an external 24 V).
  • STARTER license. A 14-day trial license can be activated through License Manager → Trial License → Activate Online.
Note on STARTER support: Siemens has announced End of Active Marketing for STARTER as a standalone product. For S110 firmware versions above V5.1, Siemens recommends Startdrive in TIA Portal V17 or later. Verify the device description for your specific drive firmware version under Options → Device description in STARTER or Options → Manage device descriptions in TIA Portal. The product support page linked above provides firmware-accurate GSD / GSDML files.

X22 RS232 Service Interface — Pinout

The X22 connector is a 9-pin D-sub male (with pins) on the CU305 front cover. It is wired as a DTE (Data Terminal Equipment) port — the same orientation as a PC COM port. The pin assignment per the SINAMICS S110 Equipment Manual is:

Pin Signal Direction (Drive-side) Description
1 — — Not connected
2 RxD Input Receive Data (drive receives from PG)
3 TxD Output Transmit Data (drive transmits to PG)
4 — — Not connected
5 GND — Signal ground / reference
6 — — Not connected
7 — — Not connected (no RTS)
8 — — Not connected (no CTS)
9 — — Not connected

Standard RS232 levels (±3 to ±15 V) are used. Hardware flow-control lines (RTS / CTS) are not implemented on the CU305; a 3-wire null-modem cable is therefore sufficient and is the recommended wiring.

Null Modem Cable Specification

Two DTE devices (the PG/PC and the CU305) cannot be connected with a straight-through cable. A null-modem crossover is required. The minimum wiring is:

PG/PC End (DB9 Female) CU305 X22 End (DB9 Female) Function
Pin 2 (PC RxD, input) Pin 3 (drive TxD, output) PC ← Drive
Pin 3 (PC TxD, output) Pin 2 (drive RxD, input) PC → Drive
Pin 5 (GND) Pin 5 (GND) Signal reference

Standard commercial null-modem cables (DB9 F/F) are available from any industrial supplier. Recommended part numbers:

  • StarTech SCNM9FM (3 m, DB9 F/F, foil-shielded)
  • L-com CSF9MF-3 (3 m)
  • Siemens 6XV1 840-2AH10 (5 m, factory-prefabricated, recommended for cabinet applications)

Maximum cable length: 15 m at 19 200 bps; 3 m at 115 200 bps. For S110 commissioning at the default baud rate (19 200), 3–5 m is the practical working distance and gives the best noise margin.

Caution: Do not use a 1:1 straight-through serial cable. The PG/PC and the CU305 will both drive the TxD line simultaneously, the bus will be shorted, and the link will not establish. Symptoms include a permanently red RDY LED, no response on the COM port, and a STARTER timeout within a few seconds of "Connect to target system".

USB-to-RS232 Adapter Selection

Modern PCs and laptops no longer ship with a DB9 COM port. A USB-to-RS232 adapter is required. The adapter chipset directly affects RS232 link stability with Siemens drives; cheap Prolific PL2303 clones (HXA, HXD, TA, RA re-marked chips) are known to corrupt frames at higher baud rates and to lose sync during long parameter downloads.

Adapter Chipset Notes
FTDI US232R-10 FT232R Industry reference; assigned COM port stable across reboots.
StarTech ICUSB232PRO FT232R Industrial grade, ±15 kV ESD, 2 kV optical isolation.
TRENDnet TU-S9 FT232R Cost-effective option.
IOGEAR GUC232A FT232R Slim form factor.
Silicon Labs CP2102N reference designs CP2102N Common on evaluation boards.

Adapters to avoid:

  • Prolific PL2303 HXA / TA re-marked clone chipsets (Windows 10 may refuse to install drivers).
  • WCH CH340 — works at 19 200 bps but is sensitive to ESD and to USB hub transient noise.

Set the assigned COM port to a fixed low number (COM1–COM4) via Windows Device Manager → Port Properties → Advanced → COM Port Number. COM port numbers above 10 occasionally require a registry edit (HKEY_LOCAL_MACHINE\SOFTWARE\WOW6432Node\Siemens\Automation\S7WSI\ComUserPort) in older STARTER builds.

Default RS232 Communication Parameters

After a factory reset of the CU305 (p0970 = 1 or p0972 = 1), the X22 service interface operates with the following default values:

Parameter Value
Baud rate 19 200 bps (selectable: 9 600, 19 200, 38 400, 57 600, 115 200)
Data bits 8
Parity None
Stop bits 1
Flow control None (RTS/CTS not wired)
Protocol USS / point-to-point (binary or ASCII)
PG/PC address 0 (parameter p2011 / p2010 family)

Match the COM port settings exactly in STARTER: 19 200 / 8 / N / 1 / no flow control. The drive does not autobaud on X22. If the baud rate is changed in STARTER (parameter p2010 / p2011 in the drive), the new value is only active after a CU305 restart (power off / on, or p0972 = 1 with the standard wait time of 30–60 s).

STARTER vs Startdrive — Tool Selection

Criterion STARTER V4.5 SP1 – V5.5 HF1 Startdrive in TIA Portal V13 SP1 – V17
Tool type Standalone Integrated in TIA Portal
Supported firmware S110 up to firmware V5.1 SP1 (last officially tested) S110 firmware V4.4 onwards; V17 required for V5.x firmware
Trace / measuring functions Full trace, function generator Trace; function generator limited
Project file format *.ssp project archive *.ap17 (TIA Portal)
PLC integration Requires STEP 7 + GSD import Native in TIA Portal
License STARTER license (free download, 14-day trial) TIA Portal STEP 7 Professional + Startdrive option

Use STARTER when you have an existing S110 project archive, when you need full trace / function generator functionality, or when the drive firmware is below V5.1. Use Startdrive for new TIA Portal installations, for S7-1200 / S7-1500 PLC integration, and for firmware V5.x and above.

Step-by-Step: Connect CU305 to STARTER via X22

  1. Bond PE. Connect the cabinet PE to the M6 PE stud on the CU305 front cover using a 10–50 mm² ring cable lug. The M8 PE stud on the PM340 power module takes a max 120 mm² ring cable lug. Reference: SINAMICS S110 Equipment Manual, "PE connection" section.
  2. Power the drive. Apply 24 V DC to the X124 terminal on the CU305. Switch on the line voltage (or precharge the PM340 DC link if a Line Module is upstream). The RDY LED will go red, then flash green, then steady green when the unit is ready (typically 5–10 s after power-up). A steady red RDY indicates a fault — read r0947 / r0948 before continuing.
  3. Plug the null-modem cable into X22 on the CU305 and the COM port (or USB-to-RS232 adapter) on the PG/PC. Hand-tighten the thumbscrews on both DB9 connectors.
  4. Verify the COM port number in Windows Device Manager → Ports (COM & LPT). Note the assigned COM number (e.g., COM3). If the COM number is above 10, change it to COM1–COM4 in the adapter advanced properties.
  5. Launch STARTER. Project → New → assign a project name and storage path. In the project navigator, right-click Drive unit → Insert new object → SINAMICS S110. In the device selection dialog, choose CU305 CAN (type designation shown as "SINAMICS S110 CU305 CAN").
  6. Configure the PG/PC interface. In STARTER, select Options → Set PG/PC interface. The access point is S7ONLINE (STEP7) → PC serial (RS232, PPI) for the X22 path. Choose the assigned COM port and click OK.
  7. Go online. Right-click the S110 drive object → Connect to target system. STARTER will compare the offline project to the drive firmware. On the first connection, choose Upload from target (load to PG) to read the actual drive parameters into the project. After subsequent firmware or topology changes, choose Download to target to write the offline configuration to the drive.
  8. Verify the connection. The COM LED on the CU305 should pulse green every time STARTER polls. The status bar at the bottom of STARTER turns green and the active faults / alarms list refreshes. The online version of r0018 (firmware version) should match the version in the offline project.
  9. Commission the drive. Run the STARTER commissioning wizard. Set p0010 = 1 (quick commissioning) and step through:
    • Motor type: 1FK7 / 1FT7 / 1PH8 (Siemens motor) or third-party induction / synchronous motor.
    • Encoder type: resolver, EnDat 2.1, sin/cos, TTL, HTL — wired via SMC / SME Sensor Module on the DRIVE-CLiQ chain.
    • Control mode: servo (for 1FK / 1FT / 1PH synchronous), vector (for 1PH / 1LA induction), or V/f (for simple induction motors).
    • Current, speed, and torque limits per the motor nameplate.
  10. Save and back up. Set p0010 = 0. Set p0971 = 1 to save parameters to non-volatile memory (RAM → ROM). Right-click the drive → Load to file system to save the project archive. Optionally insert a Siemens memory card in slot X1 and set p0977 = 1 to copy the parameter set to the card for field-replacement backup.

Verification After Online Connection

Before enabling any motion, perform these checks:

  • STARTER status bar is green and the drive shows as Online.
  • r0018 (firmware version) matches the project version. Mismatch = STARTER may not display all parameters correctly.
  • r0020 / r0021 (control / status word 1) — the drive should report Ready to switch on (status word bit pattern 0x...31 in binary) once the enable chain is closed.
  • r0947 (fault code) = 0 and r2122 (alarm code) = 0. Any non-zero value must be cleared before motion commissioning.
  • p0010 = 0 (drive returns to "Ready" state) before any motion enable.
  • r3996 (LED status word) — bit 0 = RDY state, bit 1 = COM state. Used for cross-checking the front-panel LEDs.

Memory Card Backup Procedure

After commissioning, back the parameters up to the CU305 MMC / SD card slot (X1, behind the front cover):

  1. Insert a Siemens-approved memory card: 6SL3054-0AA01-1AA0 (8 MB) for S110 firmware V4.x, or 6SL3054-0AG01-1AA0 (512 MB) for V5.x. Third-party SD cards work but are not guaranteed to be compatible with the CU305 bootloader.
  2. Set p0977 = 1 (RAM → ROM → memory card). Wait for the CU305 to perform the copy cycle (5–30 s, depending on card size).
  3. Verify the copy by reading parameter p9400 / p9401 (card parameter set version) or by removing the card, mounting it in a card reader, and confirming the presence of the SAVE directory and userdata.bin file.

A card with a valid parameter set can be hot-swapped to a replacement CU305 to bring the new Control Unit to the same state as the old one, without needing a PG/PC connection.

Note: Do not remove the memory card while the CU305 is performing the copy (LEDs are flashing in the "OPT" pattern). Wait at least 30 s after p0977 = 1 to allow the file system to close. Removing the card mid-write corrupts the file system and the next boot will fail with F01357 (file system error).

Alternative: CANopen via X126

For installations where the CU305 is already wired to a CANopen bus, the X126 port can be used for STARTER commissioning without disturbing the field wiring. Required hardware and settings:

  • USB-to-CAN adapter: PEAK-System PCAN-USB (IPEH-002021), Vector VN1610, or HMS Ixxat USB-to-CAN V2.
  • STARTER V4.5 SP1 or later (Startdrive in TIA Portal V14 or later) with the CAN device description installed.
  • CAN baud rate (default 1 Mbit/s, settable to 10, 20, 50, 100, 125, 250, 500, 800, 1000 kbit/s via p8620).
  • CAN node ID (default 1, settable 1–127 via p8621 or the CU305 front-panel DIP switch).
  • 120 Ω bus termination at both physical ends of the CAN bus (the CU305 CAN variant does not include an internal termination resistor — install it at the connector if the CU305 is at the end of the segment).

Set the STARTER PG/PC interface to PC internal/PC local → PCAN-USB (or your specific adapter). The connection procedure after this point is identical to the X22 path.

PROFIBUS / PROFINET — Variant Note

The CAN variant of the CU305 (6SL3040-0JA02-0AA0) does not include a PROFIBUS or PROFINET interface. If PROFIBUS-based STARTER commissioning is required, use the CU305 DP variant (6SL3040-0JA01-0AA0). For PROFINET, use the CU305 PN variant (6SL3040-0JA00-0AA0). Do not attempt to connect PROFIBUS or PROFINET cables to X126 — X126 is the CAN bus and the physical-layer voltage levels are incompatible (CAN uses differential 2.7 V / 1.3 V on CAN_H / CAN_L, PROFIBUS uses RS485 ±1 V differential).

LED Status Reference

RDY (green) RDY (red) COM (green) OPT (yellow) Meaning
Off Off Off Off No 24 V supply or unit is powering up
Slow flash Off Off Off Booting / firmware load in progress
Steady Off Off Off Ready, no active communication
Steady Off Flash Off Ready, active RS232 / CAN communication
Steady Off Off Steady Optional module / memory card present
Off Slow flash — — Warning active (r2122)
Off Steady — — Fault active (r0947)
Fast flash Fast flash — — Firmware update in progress, do not power off

Fault and Alarm Code Reference

Code Meaning Action
F01000 Internal software error Power cycle; if persistent, replace CU305
F01018 Power-down interrupted write to memory card Insert known-good card, perform p0972 = 1, reload parameters
F01357 File system error on memory card Reformat card in CU305 or replace; reload parameter set
F08501 COMM board hardware fault Power cycle; if persistent, replace CU305
F08502 COMM board lost connection (CAN/PROFIBUS) Check X126 wiring, 120 Ω termination, baud rate / node ID
A08502 COMM board warning (CAN/PROFIBUS) Same as F08502; warning only, drive continues running
F1910 Encoder error (resolver / EnDat / sin/cos) Check encoder cable, SMC / SME module, set p0010 = 3 to re-init encoder
F30001 Power unit overcurrent Check motor wiring, encoder direction, motor parameters; check for short
F30002 DC link overvoltage Check line voltage, braking resistor sizing, ramp-down rate
F30003 DC link undervoltage Check line supply, precharge circuit, 24 V at X124

Always read r0947 for the most recent fault, r0948 for the fault time stamp (in 24-hour format from the CU305 real-time clock, which is buffered by the 24 V supply), and r0949 for the fault value.

Troubleshooting Matrix

Symptom Likely Cause Action
STARTER reports "Connection to target system failed" Wrong COM port, wrong access point, baud-rate mismatch Recheck PG/PC interface assignment; confirm 19 200 / 8 / N / 1; try a different USB port
COM port visible in Device Manager but no online response Null-modem cable is straight-through Verify continuity: PC pin 2 ↔ drive pin 3, PC pin 3 ↔ drive pin 2, PC pin 5 ↔ drive pin 5
RDY LED steady red, COM LED off Drive in fault state or no 24 V supply Read r0947; verify 24 V at X124; perform p0972 = 1 factory reset if safe
COM LED pulses briefly then timeout USB-to-RS232 adapter chipset issue or driver conflict Switch to FTDI-based adapter; reinstall driver; set COM port number < 10
Communication OK at 19 200 bps but fails at higher rates Cable capacitance or adapter quality Replace cable with shielded < 3 m; reduce baud rate; check shield grounding at drive end only
Drive goes offline intermittently during long parameter downloads Windows power management on USB port Disable USB selective suspend in Windows Power Options
STARTER freezes on "Load to PG" with large projects Insufficient RAM, project > 32 MB Close other applications, increase virtual memory; archive project to *.ssp before re-opening
Drive shows online but parameter set is empty Offline project does not match drive topology Right-click → "Load to PG" with "With actual topology" option enabled
Encoder not recognized after power-up Wrong SMC / SME module or DRIVE-CLiQ chain order Check DRIVE-CLiQ port assignments; perform p0010 = 3, p0010 = 0 cycle

EMC and Shielding Best Practice

For a reliable RS232 commissioning link in an industrial cabinet:

  • Use a shielded cable and connect the shield to cabinet ground only at the drive end to avoid ground loops. If the drive is more than 5 m from the PG/PC, use a separate PE run between the PG chassis and the cabinet PE.
  • Keep the RS232 cable at least 200 mm from any 400 V power wiring, and never run it in the same cable tray as motor power leads.
  • Do not route the cable parallel to motor power leads for more than 1 m; cross at 90° if crossing is required.
  • The CU305 PE stud (M6) must be bonded to cabinet PE with a ring lug sized for the installation (10–50 mm² per the SINAMICS S110 Equipment Manual). The PM340 PE stud (M8) accepts a max 120 mm² ring lug.
  • If the drive is fed by an ungrounded IT line supply, install a residual-current monitoring device (RCM) upstream, and use a 4-pole contactor so that all phases are isolated on stop.

Watch Tables and Trace — First Diagnostics

Once online, two STARTER tools are used for 90% of first-day diagnostics:

  • Watch table (right-click the drive → Watch table): a tabular view of any parameter (read-only or read/write) that updates in real time. Add r0020, r0021, r0026, r0027, r0031, r0032, r0080, r0082 for a real-time motion / current view. Save the watch table to the project so it loads automatically on next connection.
  • Trace (Drive → Trace): time-sampled recording of up to 8 parameters at sample times from 1 ms to 60 s. The trace is downloaded to the drive, runs on the drive firmware (not on the PG/PC, so it is robust against PC timing jitter), and the result is uploaded back to STARTER for graph display. Use the trace to capture step responses, current spikes, and encoder noise.

For S110 firmware V4.x and V5.x, the trace buffer is limited to 2 048 samples per channel. For longer captures, reduce the sample time or use the function generator in STARTER to drive a periodic test signal.

Firmware Update Procedure (Reference)

Firmware updates for the CU305 are performed via STARTER ("Drive → Load firmware to drive") or via a memory card containing the new firmware. Always read the release notes for the new firmware version on the Siemens product support page linked above before updating — some firmware versions require a specific upgrade path (e.g., V4.4 SP3 → V4.5 SP1 → V5.1 SP1) and may not be downgradeable without a service request.

  1. Back up the current parameter set to a memory card (p0977 = 1) and to a project archive (right-click → Load to file system).
  2. Set p0010 = 0 to ensure the drive is in "Ready" state, not commissioning.
  3. In STARTER, right-click the drive → Load firmware to drive. Select the firmware file (*.upd) matching the MLFB and current firmware version.
  4. Confirm the version change. The CU305 will restart automatically after the load. Do not power off during the update — the RDY LED will fast-flash green and red for 30 s to 5 min, depending on the firmware size.
  5. After the restart, go online, verify r0018 matches the new firmware, and reload the project (Upload from target).
Note: Firmware updates reset the drive to factory defaults. Always re-load the project parameter set after a firmware update, or restore from a memory-card backup if the previous parameters are still valid for the new firmware.

Integration with S7 PLCs (Quick Reference)

For PLC → drive integration, the CU305 CAN is connected to the PLC via CANopen. The S7-300 / S7-400 require a CP 340 or CP 341 module, and the S7-1200 / S7-1500 require a CM CAN module. Drive-side, the following parameter ranges are used for the CANopen profile (DSP 402 / CiA 402):

Parameter Function Typical Value
p8620[0] CAN baud rate 6 (1 Mbit/s) or 5 (500 kbit/s)
p8621 CAN node ID 1 (default; 1–127 settable)
p8622 CAN heartbeat time 0 (off) or 1000 ms
p8700 COB ID receive (control word 1) 0x200 + node ID
p8701 COB ID transmit (status word 1) 0x180 + node ID

Refer to the SINAMICS S110 Equipment Manual, "CANopen communication" chapter, for the full parameter list and EDS file integration.

Field Replacement of a Failed CU305

  1. Power down the drive (24 V removed, line contactor off, DC link discharged — wait at least 5 min after power-off before touching terminals).
  2. Remove all connectors from the failed CU305: X22, X126, X100/X101 encoder, X124 24 V, DRIVE-CLiQ, motor cable, memory card (if present).
  3. Insert the memory card from the failed unit into the new CU305 of the same MLFB.
  4. Apply 24 V DC. The new CU305 will detect the memory card and load the parameter set from userdata.bin within 30 s. The RDY LED will go steady green when loaded successfully.
  5. Reconnect all cabling in the original order.
  6. Go online with STARTER. Verify r0018 firmware version matches the memory card version. Verify r0947 = 0 (no faults) and r0021 = 0x...31 (Ready to switch on).

If the memory card is corrupted or missing, the new CU305 will boot with factory defaults. Re-commission via the STARTER wizard as described in the step-by-step section above.

Frequently Asked Questions

Which X connector on the CU305 CAN should I use to connect to STARTER?

Use X22 (9-pin D-sub male, RS232 / USS) for a direct PG/PC link with a null-modem cable. X126 is the CAN bus interface and requires a USB-to-CAN adapter plus CANopen configuration. There is no PROFIBUS interface on the 6SL3040-0JA02-0AA0 variant.

What is the X22 pinout of the SINAMICS S110 CU305?

X22 is a DTE port: pin 2 = RxD, pin 3 = TxD, pin 5 = GND. All other pins are not connected. Hardware flow control (RTS/CTS) is not implemented, so a 3-wire null-modem cable is sufficient.

Do I need a null-modem cable or a straight-through cable?

A null-modem (crossover) cable is required, with PC TxD (pin 3) wired to drive RxD (pin 2) and PC RxD (pin 2) wired to drive TxD (pin 3). A 1:1 straight-through cable shorts both TxD lines together and the link will not establish.

Which STARTER version supports the SINAMICS S110 CU305 CAN?

STARTER V4.5 SP1 through V5.5 HF1 include S110 support. Startdrive in TIA Portal V13 SP1 and later can also be used. Verify that the device description for your specific drive firmware version is installed under Options → Device description in STARTER, or via the Siemens product support page for the 6SL3040-0JA02-0AA0.

Can I use a USB-to-RS232 adapter to connect my laptop?

Yes — but use a quality FTDI FT232R or Silicon Labs CP2102N-based adapter. Avoid unbranded Prolific PL2303 clones; they cause CRC errors and dropped connections at higher baud rates. Set the assigned COM port to a number below 10 for best compatibility with older STARTER builds.

What is the default baud rate of the X22 service interface?

19 200 bps, 8 data bits, no parity, 1 stop bit, no flow control. The drive does not autobaud on X22. Match these values exactly in the PG/PC interface assignment in STARTER.

How do I restore the CU305 to factory defaults?

Set p0010 = 30 (factory reset filter), p0970 = 1, and wait for the unit to restart. After the restart, all parameters are at factory defaults. Note that the password in p9761 is reset only by a full memory-card load or by a Siemens service request, not by p0970.

Back to blog