SINAMICS S120 CDS Backup Control via TB30: Configuration Guide

David Krause13 min read
SiemensTutorial / How-toVFD / Drives
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Architecture Overview: SINAMICS S120 with S7-1500 and TB30 Backup Path

The SINAMICS S120 is a modular drive system commonly paired with a SIMATIC S7-1500 controller over PROFINET using the PROFIdrive profile. In a redundant-standby architecture the drive accepts its primary commands (control word 1, speed setpoint, torque limits, ramp-function generator controls) from the PLC, and a TB30 Terminal Board is installed on the Control Unit (CU320-2 PN or CU310-2 PN) to provide hard-wired digital inputs, digital outputs, and analog I/O that take over if the PLC fails or PROFINET goes down.

Switching between the two control paths is implemented with Command Data Sets (CDS). The drive supports up to four CDS (index 0–3), and the active CDS is selected at runtime by a two-bit binary code written into binector inputs p0810 (bit 0) and p0811 (bit 1). Each CDS carries its own interconnection of the command sources, so CDS0 can be wired to the PROFIdrive receive words coming from the S7-1500 (via p2050, p2051), while CDS1 can be wired entirely to TB30 digital inputs and the TB30 analog input. The PLC toggles p0810/p0811 when a fault condition is detected.

Important — Infeed limitation: The Smart Line Module (SLM) and Active Line Module (ALM) infeeds do not support Command Data Sets. Backup switching for the infeed must be handled either with DCC (Drive Control Chart) logic in the drive or with hard-wired contactors/24 V signals at the line module terminals. See the section "Smart Line Module Backup" below.

System Topology Diagram

S7-1500 PLC PROFINET STW1 + NSOLL_A PN cable SINAMICS S120 CU320-2 PN Motor Module + SLM CDS0 / CDS1 TB30 Terminal Board 8 DI / 4 DO 2 AI / 2 AO Backup commands Motor 3-phase, encoder-equipped 24 V wiring from cabinet

Prerequisites: Hardware, Firmware, and Software

Item Requirement Notes
Control Unit CU320-2 PN or CU310-2 PN Must have a free option slot for TB30
Terminal Board TB30 (6SL3055-0AA00-2TA0) Plugs into the option slot of the CU
CU firmware V5.x or higher CDDS support unchanged; STARTER version must match
STARTER / Startdrive Matching firmware toolbox Use Startdrive in TIA Portal for S7-1500 projects, or classic STARTER for standalone commissioning
PLC SIMATIC S7-1500 with PROFINET PROFIdrive V4 telegram (telegram 1, 3, or 102) configured
Wiring 24 V DC source, shielded analog cable, DI/DO conductors Analog reference from a stable potentiometer or 0–10 V source
Always commission and download the S120 project before plugging in the TB30. Hot-swapping the TB30 with the drive powered is supported but the drive briefly reports a parameter fault if the topology is changed without re-initialization.

Command Data Set (CDS) Fundamentals

A CDS is a set of binector and connector interconnections stored under a single index. The drive keeps a separate CDS for every control source so that switching between them at runtime does not require parameter re-download. The selection logic is a 2-bit binary word:

p0811 (MSB) p0810 (LSB) Active CDS
0 0 CDS0
0 1 CDS1
1 0 CDS2
1 1 CDS3

For a two-source architecture the PLC only needs to toggle p0810 between 0 and 1, leaving p0811 at 0 permanently. The change is bumpless because the drive reads all CDS values on every scan of the command processing cycle; the active set simply becomes whichever index matches the bit pattern at the time the control word is evaluated.

The number of available CDS depends on the drive object (DO): the Control Unit (DO1) and each Motor Module / Servo drive DO support up to 4 CDS. Drive Data Sets (DDS) are a separate concept and are used to switch encoder configurations, motor data, and closed-loop parameters — not command sources. For this application only CDS is required.

TB30 Terminal Module I/O Specification

The TB30 expands the CU by a fixed I/O set that is independent of PROFINET and therefore available even if the bus is down. Reference: SINAMICS S120 Commissioning Manual.

Signal Channel Electrical Typical Use in CDS1
Digital inputs DI0 – DI7 24 V DC, opto-isolated, 5 mA typ. ON/OFF1, enable setpoint, jog, fault reset
Digital outputs DO0 – DO3 24 V DC, 0.5 A short-circuit-proof Drive ready, fault, running, speed reached
Analog inputs AI0, AI1 ±10 V or 0–10 V, 12-bit, differential Speed setpoint (AI0), torque limit trim (AI1)
Analog outputs AO0, AO1 ±10 V, 12-bit Actual speed, motor current

The TB30 connector pinout on the CU is unique; consult the hardware installation manual for your CU variant before landing conductors. Use shielded twisted pair for the analog channels, with the shield bonded at one end only, typically at the cabinet entry.

CDS Configuration Procedure in STARTER / Startdrive

Perform these steps in order. They assume the project is online with the drive and the CU recognizes the TB30.

  1. Insert TB30 in the topology. In STARTER, open the drive navigator, navigate to the CU320-2 PN, right-click the option slot, and select "Insert option board → TB30". Confirm with "OK". Startdrive uses the same path under "Device configuration → option modules".
  2. Verify TB30 in the topology tree. Expand the CU and confirm TB30 appears below the option slot. If it does not, click "Update firmware / topology" and re-check the drive's LEDs — a flashing yellow COM LED indicates topology mismatch.
  3. Open the expert list. From the drive object, choose "Expert list". Filter the parameter tree by searching for "CDS". You will see parameters with [0], [1], [2], [3] indices, e.g., p0840[0..3].
  4. Configure CDS0 (PLC control). In CDS0 — index [0] of every command-source parameter — wire:
    • p0840[0] (ON/OFF1) = r2090.0 (PROFIdrive STW1 bit 0)
    • p0844[0] (OFF2) = r2090.1
    • p0848[0] (OFF3) = r2090.2
    • p0852[0] (enable setpoint) = r2090.6
    • p1070[0] (speed setpoint main) = r2050[1] (NSOLL_A)
    • p1503[0] (torque limit upper) = r2050[2]
    • p1504[0] (torque limit lower) = r2050[3]
  5. Configure CDS1 (TB30 backup). Switch the parameter index to [1] using the drop-down next to the parameter name and rewire:
    • p0840[1] = r4022.0 (TB30 DI0 as ON/OFF1)
    • p0844[1] = r4022.1 (TB30 DI1 as OFF2)
    • p0852[1] = r4022.2 (TB30 DI2 as enable setpoint)
    • p1070[1] = r4055[0] (TB30 AI0 as speed setpoint)
    • p1503[1] = fixed value, e.g., p1523 = 80 % (upper torque limit)
    • p1504[1] = p1523 = -80 % (lower torque limit)
  6. Set the CDS selector source. On the Control Unit DO, configure:
    • p0810 = r2090.10 (PROFIdrive STW1 bit 10, freely usable per PROFIdrive convention), OR
    • p0810 = a digital input on TB30, e.g., r4022.7 (DI7), if the operator must be able to force CDS1 manually.
    • p0811 = 0 (no need for higher CDS indices)
  7. Save and copy RAM to ROM. From the drive toolbar, click "Copy RAM to ROM". Then right-click the drive and choose "Download → to target device".
Copying parameters between CDS: STARTER offers "Copy parameter values" in the expert list right-click menu. You can copy CDS0 to CDS1, then edit only the lines that differ, to avoid manual errors.

Parameter Mapping Reference Table

Parameter CDS0 (PLC via PROFINET) CDS1 (TB30 backup)
p0840 (ON/OFF1) r2090.0 r4022.0 (TB30 DI0)
p0844 (OFF2 / coast stop) r2090.1 r4022.1 (TB30 DI1)
p0848 (OFF3 / quick stop) r2090.2 1 (constantly inactive)
p0852 (Enable setpoint) r2090.6 r4022.2 (TB30 DI2)
p0860 (Acknowledge) r2090.7 r4022.3 (TB30 DI3)
p1070 (Main setpoint) r2050[1] (NSOLL_A) r4055[0] (TB30 AI0)
p1503 (Torque limit upper) r2050[2] p1523 (fixed)
p1504 (Torque limit lower) r2050[3] p1523 (negated)
p2253 (PID setpoint) r2050[4] r4055[1] (TB30 AI1)

Note that OFF3 in CDS1 is intentionally left at logic 1 (no quick-stop input). If the application requires it, wire TB30 DI4 to p0848[1] via r4022.4.

PLC-Side Implementation in S7-1500

On the S7-1500 side, the PLC maintains a watchdog that toggles the CDS bit if PROFINET diagnostics or a cyclic time-out are detected. A simple pattern in the cyclic OB1:

// Watchdog counter
#iHeartbeat := #iHeartbeat + 1;
IF #iHeartbeat > 1000 THEN
    #iHeartbeat := 0;
    #bHeartbeat := NOT #bHeartbeat;
END_IF;

// Diagnostics-based fallback
#bPLC_OK := NOT "PN-Diag".IO_DeviceFault[0] 
            AND NOT "PN-Diag".ConnectionLoss[0];

// If PLC drops the link, set CDS bit 1 (PROFIdrive STW bit 10)
IF #bPLC_OK THEN
    "DB_Drive".STW1.%X10 := FALSE;      // CDS0 active
ELSE
    "DB_Drive".STW1.%X10 := TRUE;       // CDS1 active
END_IF;

On the hardware, ensure the PLC writes a periodic keep-alive to a configured PROFINET slot so a cable break is detected within ~3 × the configured watchdog time. Siemens PROFINET default in TIA Portal is 3 missed cycles before the device drops out.

Safety note: If the drive is part of a safety circuit (STO via PROFIsafe, F-DI on the line module), backup control via TB30 does not replace PROFIsafe. The drive will refuse to start if PROFIsafe demands STO, regardless of CDS selection. Add hard-wired STO terminals on the Motor Module for full backup. See the S120 Safety Integrated manual.

Smart Line Module Backup (Infeed Has No CDS)

The Smart Line Module (SLM) and Active Line Module (ALM) do not expose CDS parameters. The infeed's run/enable logic is tied to terminals EP (Enable Pulses) and the 24 V enable rail on the X21 connector. To bring the line module online when the PLC is down:

  • Hardware enable approach (recommended). Wire the SLM EP terminal to a 24 V line that is sourced from a UPS or a hardware relay that is energized whenever the cabinet is powered. The SLM will pre-charge and close its line contactor automatically once the DC link is healthy.
  • DCC logic approach. Load a DCC chart on the infeed DO that monitors the fieldbus status (r2043.0 = life-sign bit) and drives the infeed enable via the line module's binector input p840[0] on the CU. When the PLC fails, the DCC chart asserts the infeed enable so the DC bus stays powered.
  • Manual contactor bypass. For service-mode operation, install a key-switch that bridges the PLC enable relay and connects EP to 24 V. Label clearly and lock out during PLC-controlled operation.
Operating the infeed without coordination from the line-side protective devices is a code-compliance question. Verify with the local electrical inspector before commissioning a permanent PLC-bypass wiring path.

Commissioning Procedure and Verification

  1. Power up the cabinet. Confirm the CU's READY LED is green and the TB30 OPT LED is green.
  2. Online in STARTER, open the trace and record r0050 (active CDS) and r4022 (TB30 DI status) over 5 s. Force p0810 = 0 and verify r0050 = 0; force p0810 = 1 and verify r0050 = 1.
  3. Issue ON/OFF1 from the PLC via the HMI button. Confirm the drive accelerates to the PLC-issued setpoint. Check r0021 (actual speed) matches the setpoint within the ramp.
  4. Disconnect the PROFINET cable at the S120 side. Within 3 × watchdog time the drive should report F08501 (PROFINET communication fault) and the PLC's diagnostic block should set bPLC_OK := FALSE. Verify r0050 transitions from 0 to 1 (CDS1 active).
  5. Press the backup ON button wired to TB30 DI0. Verify the drive accelerates to the AI0 reference voltage scaled to p2000. With p2000 = 1500 rpm, 5 V at AI0 should give 750 rpm.
  6. Toggle p0844 (OFF2) via TB30 DI1 to confirm coast-down.
  7. Reconnect PROFINET. The PLC should restore bPLC_OK = TRUE and clear p0810. Acknowledge F08501 from the PLC (or from TB30 DI3 if wired) and confirm CDS0 takes control without a re-start being required.
  8. Record the trace during step 7 and confirm r0050 returns to 0 only after the PLC has re-established the cyclic data exchange and acknowledged any faults.

Verification Checklist

  • [ ] r0050.0 reads 0 when PROFINET is healthy
  • [ ] r0050.0 reads 1 within 1 s of PROFINET failure
  • [ ] TB30 AI0 reference at 10 V drives motor to p2000 rpm
  • [ ] TB30 DI0 = 1 starts motor with ramp p1120[1]
  • [ ] TB30 DI1 = 0 triggers OFF2 within 50 ms
  • [ ] Fixed torque limit p1523 is not exceeded at full load (verify with r0080)
  • [ ] PLC reconnection automatically restores CDS0 without operator action
  • [ ] Infeed DC link r0070 remains within ±5 % of nominal during CDS switchover

Troubleshooting Matrix

Symptom Likely Cause Diagnostic Step Fix
Drive ignores TB30 inputs after PLC disconnect CDS bit not set Check r0050.0 online in STARTER Verify p0810 source wiring or PLC-side fallback logic
Motor stalls at low speed in CDS1 AI0 scaled incorrectly Read r4055[0] and r0021 Adjust p2000 or add scaling at p1070
F08501 (PROFINET fault) not clearing Acknowledge wired only in CDS0 Read p2103 and p2104 Add TB30 DI3 → p2103[1] so backup path can acknowledge
SLM contactor does not close EP terminal floating Measure voltage at X21.1 (EP) vs X21.2 (M) Wire EP to 24 V via UPS-backed supply
Drive ramps but no torque in CDS1 Torque limit p1503[1] = 0 Read r0108 and p1503 Set p1523 = 80 (or application limit) and ensure p1503[1] = p1523
Bumpless switchover fails — drive trips STW1 bit 0 changes state during CDS toggle Trace r2090.0 around the switch Use a 1-shot on the PLC side to mask ON/OFF1 during the CDS bit change
TB30 not visible in topology Firmware mismatch or slot empty Inspect OPT LED and run topology update Insert TB30 firmly and re-power CU
F08502 / F01910 after re-connect PROFINET slot reconfiguration by PLC Read r2050[0..15] and r2090 Confirm telegram assignment matches in TIA Portal device configuration

Documentation and Reference Manuals

How many Command Data Sets does the SINAMICS S120 support, and what parameters select them?

Up to 4 CDS per drive object. The active CDS is selected by the binary pattern at binector inputs p0810 (bit 0, LSB) and p0811 (bit 1, MSB). The currently active CDS is reported in r0050.0.

Does the Smart Line Module support CDS for PLC-failover control?

No. Infeeds (SLM and ALM) do not expose CDS parameters. Use a hardware enable at the EP terminal of X21, or load a DCC chart that monitors the bus life-sign (r2043.0) and drives the infeed enable via p840 on the Control Unit.

Can I use a fixed torque limit in CDS1 even though the PLC sends torque limits in CDS0?

Yes. Set p1523 to the desired fixed torque (e.g., 80 % of rated) and wire p1503[1] = p1523 for the upper limit and p1504[1] = -p1523 for the lower limit. CDS0 retains the dynamic torque limits from r2050[2] and r2050[3].

What TB30 analog input scaling should I configure for CDS1?

Use p2000 as the reference speed (default 1500 rpm). The TB30 AI0 accepts ±10 V. At 10 V the speed setpoint becomes p2000. If you need finer resolution at low setpoints, apply the scaling block by setting p1071[1] to a scaling factor or insert a DCC chart that linearises the potentiometer.

Will the drive switch from CDS0 to CDS1 automatically when PROFINET fails?

Not by itself. The drive only follows the bit pattern on p0810/p0811. The PLC must write 1 to p0810 when it detects a fault on the PROFINET interface (e.g., a dropped cyclic connection or a missed heartbeat). The drive then executes the switchover on its next command processing cycle, typically within 4–8 ms.

How do I acknowledge faults while the PLC is down?

Wire a TB30 digital input (e.g., DI3 via r4022.3) to the second index of p2103[1]. Then drive that input high briefly to clear faults in CDS1. Make sure p2104[1] is set to a pulse source if you want a one-shot acknowledge, not a level-sensitive reset.

Is the TB30 backup path safe-rated for SIL applications?

No. The TB30 provides only standard I/O. Safety functions (STO, SS1, SLS) require PROFIsafe or hard-wired F-DI on the Motor Module. If the application is safety-rated, the backup control path must also satisfy the required Performance Level (PL) or Safety Integrity Level (SIL) — typically by adding a safety relay that mirrors the PROFIsafe signals onto the line module's X41/STO terminals.

Back to blog