Sinamics S120 Manual Speed Controller Tuning in SLVC Mode

David Krause14 min read
SiemensTechnical ReferenceVFD / Drives
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Sinamics S120 Manual Speed Controller Tuning in SLVC Mode

Manual tuning of the speed controller on a SINAMICS S120 drive operating in Sensorless Vector Control (SLVC) with a third-party squirrel-cage induction motor is a recurring field task on conveyor applications where a closed-loop encoder is either unavailable or impractical. This reference consolidates the parameter sequence, the manual Kp/Tn adjustment procedure, and the F07902 fault root-cause analysis that a commissioning engineer needs to walk through when the drive trips on motor-speed deviation at first start with load.

Safety first. Before enabling any tuning step, verify the motor is decoupled from the conveyor if the mechanical system cannot absorb unexpected reversals or torque transients. Confirm the stop category and STO wiring per SINAMICS S120 Safety Integrated Function Manual. Tuning must be performed with the drive in local control and an active operator E-Stop.

1. Application Overview and Drive Topology

The reference topology for a coal-conveyor duty is a Line Module (Active Line Module or Smart Line Module) feeding a Motor Module (Booksize or Chassis) that supplies a 3rd-party TEFC induction motor through a sinus filter or du/dt filter. SLVC is selected because the motor shaft is not fitted with an incremental encoder or resolver, and the mechanical envelope will not allow retrofit.

Drive Function Selected Mode Implication
Control mode (p1300) 20 = Sensorless vector control with speed controller Speed feedback inferred from observer model; bandwidth limited.
Motor type (p0300) 1 = Induction motor, squirrel-cage Standard 3rd-party motor without encoder.
Motor identification (p1900 / p1960) 2 / 1 = Stationary + rotary ID with full identification Required for SLVC model accuracy.
Speed setpoint filter p1656 (activation), p1657-p1659 (PT2 filter) Suppresses mechanical resonances.

For an overview of the control structure, refer to the SINAMICS S120 Drive Functions Function Manual, section "Vector control / Speed controller."

2. Prerequisites and Required Tools

  1. Starter / Startdrive / Scout commissioning tool online connection via PROFIBUS, PROFINET, or Ethernet service interface (X127 on CU320-2).
  2. Motor data sheet: rated voltage (p0304), rated current (p0305), rated power (p0307), rated power factor (p0308), rated frequency (p0310), rated speed (p0311), motor cooling type (p0335), and rotor time constant (p0623 if known).
  3. Equivalent circuit data (preferred): stator/rotor resistance, leakage reactance, magnetizing reactance. Where unknown, p0620-p0628 can be left on default and identified automatically during the rotary measurement.
  4. Mechanical data: total inertia referred to motor shaft (J_total in kgm²), gearbox ratio, conveyor belt length and load profile.
  5. Trace license / 4-channel SCOUT trace for capturing r0061 (actual speed, encoderless) and r0062 (setpoint) during the step response.
A scalar (V/f) auto-tuning step never substitutes for the SLVC model. If the drive was commissioned in V/f mode (p1300 = 0, 1, or 2), the controller gains and slip model defaults are not valid for SLVC. Re-enter the motor data and rerun the identification in p1300 = 20.

3. Motor Data Entry and Identification Sequence

The first source of F07902 trips on a 3rd-party motor is incorrect motor model parameters. Perform the data entry and identification sequence in this order:

3.1 Enter motor nameplate data

Parameter Description Source
p0304 Rated motor voltage Nameplate, line-to-line RMS
p0305 Rated motor current Nameplate, per-phase RMS
p0307 Rated motor power Nameplate, mechanical kW
p0308 Rated motor power factor cos φ Nameplate
p0309 Rated motor efficiency η Nameplate or default 0.9
p0310 Rated motor frequency Nameplate Hz
p0311 Rated motor speed Nameplate RPM at rated load
p0335 Motor cooling type 0 = natural, 1 = forced, 2 = water
p0601 Motor temperature sensor type 0 = none, 1 = PTC, 2 = KTY84, 10 = PT1000

3.2 Run stationary measurement (p1900 = 2)

Set p1900 = 2 and issue an ON command. The drive injects a controlled stator current to measure stator resistance (p0620), rotor resistance (p0621), and the IGBT dead-time compensation values. The motor is not rotating. The drive returns to "Ready to Run" upon completion.

3.3 Run rotary measurement (p1960 > 0)

Set p1960 = 1 (rotary measurement, full identification including saturation characteristic) or p1960 = 2 (only saturation characteristic). With p1960 = 1 the drive accelerates the motor to the configured speed (typically p1961 = rated speed) and measures the magnetizing reactance, leakage reactance, and the rotor time constant used by the SLVC observer.

On a coal conveyor the rotary measurement must be run with the belt empty. The ID sequence assumes a known inertia set in p1498 / p0341 / p0342. A heavily loaded belt during the rotary ID corrupts the rotor time constant, which in turn destabilises the speed observer and produces the F07902 at first loaded start.

4. F07902 Fault Root Cause Analysis

F07902 ("Drive: Motor speed deviation") is raised when the absolute difference between the speed setpoint and the speed actual value exceeds the threshold configured in p2162 for longer than p2163 ms.

Fault Value Meaning Likely Cause in SLVC with 3rd-Party Motor
F07902 value 1 n_set ≠ n_act, ramp-up Ramp-up too fast, p1959/rotor time constant too small, load inertia too high
F07902 value 2 n_set ≠ n_act, pull-out / loaded Stall, Kp/Tn too aggressive, rotor resistance mismatch, observer loss of synchronism
F07902 value 3 Overspeed during ramp Kp too high, setpoint filter missing
F07902 value 10 Sensorless signal lost Low speed below p1755, observer collapses

The F07902 value 2 reported by the source content is the loaded-pull-out case. The corrective sequence is:

  1. Verify p0620-p0628 (motor equivalent circuit) are populated from the rotary ID, not left at default.
  2. Verify p1498 / p0341 / p0342 / p1496 (load inertia, motor inertia, friction). The total inertia is the dominant parameter for SLVC; the speed observer at low speed depends on the inertia model.
  3. Reduce p1120 (ramp-up) and p1121 (ramp-down) to a conservative value, e.g. 20-30 s for a long conveyor, and re-test.
  4. Increase p2162 (default 6 rpm) and p2163 (default 100 ms) only as a temporary measure to validate root cause. Do not leave relaxed; it masks the real issue.
  5. Perform the manual Kp/Tn procedure in section 6.

5. Speed Controller Structure and Parameter Map

The SLVC speed controller is an IP controller with feed-forward torque. The relevant parameter map for manual tuning is:

Parameter Function Manual Tuning Effect
p1460 Speed controller P gain Kp (with encoder) Rarely used in SLVC
p1462 Speed controller integral time Tn (with encoder) Rarely used in SLVC
p1470 Speed controller P gain Kp, encoderless (SLVC) Primary proportional gain
p1472 Speed controller integral time Tn, encoderless (SLVC) Primary integral time
p1475 Speed controller droop For load sharing on mechanically coupled drives
p1459 P gain adaptation upper transition speed Optional, for variable bandwidth
p1496 Acceleration pre-control scaling 100% enables full feed-forward
p1498 Total inertia (kgm²) for feed-forward Enter measured or estimated value
p1656 Activate speed setpoint filter 1 Enable for noisy speed feedback
p1657-p1659 PT2 filter natural frequency / damping / activation Insert notch or low-pass on setpoint

The default SLVC values are calculated by the drive during identification and stored in p1470/p1472. They are typically conservative. Manual tuning overwrites these.

6. Manual Kp/Tn Tuning Procedure (With Load)

The conventional manual tuning approach for a 3rd-party induction motor in SLVC follows the engineering convention of starting from the slowest stable controller and progressively increasing Kp, then reducing Tn, while observing the actual speed response on a SCOUT trace.

6.1 Initial setup

  1. Set p1470 = 0.005 Nm/rpm (a deliberately low Kp).
  2. Set p1472 = 2000 ms (a deliberately high Tn, effectively disabling the I term).
  3. Set p1496 = 0% to disable acceleration pre-control during the first pass.
  4. Disable the setpoint filter: p1656 = 0.
  5. Set the ramp p1120 = 30 s (long), p1121 = 30 s. Adjust once tuned.

6.2 Open-loop step response (no load)

Apply a small fixed setpoint step from 0 to 20% of rated speed using the control panel in Startdrive. Capture r0061, r0062, r0079 (torque setpoint), and r0080 (torque actual) on a 4-channel trace with a 4 ms sample time.

Observe:

  • Rise time t_r to 90% of final speed.
  • Steady-state error with p1472 = 2000 ms (should be obvious — that is the point of starting with a large Tn).
  • Any oscillation. With Kp = 0.005 the response should be very damped.

6.3 Increase Kp

Raise p1470 in 50% steps (0.005 → 0.0075 → 0.011 → 0.016 → 0.024 …) and repeat the step. The drive becomes faster and stiffer; overshoot will appear. Continue until one of the following limit conditions is reached:

  • Torque ripple on r0079 exceeds ~3% of rated torque (controller is driving mechanical resonances).
  • Sustained oscillation on r0061 (the Kp has exceeded the open-loop gain margin).
  • Acoustic noise increase in the motor.

Set p1470 to approximately 60-70% of the Kp value that produced the first sustained oscillation. This is the "engineering-acceptable" Kp.

6.4 Decrease Tn

With the chosen p1470, lower p1472 in steps: 2000 → 1000 → 500 → 333 → 250 → 200 → 150 → 100 ms. The drive becomes more aggressive in closing the steady-state error but also less damped. Stop at the Tn value where:

  • The steady-state speed error in r0061 - r0062 collapses to within p2162 within 1 s of a step.
  • Overshoot remains under 5% of the step magnitude.

A rule of thumb is p1472 ≈ 2-3 × t_r observed at the chosen Kp. For a 200 ms rise time, start with p1472 ≈ 400-600 ms and adjust from there.

6.5 Enable acceleration pre-control

Set p1498 to the total inertia referred to the motor shaft (motor + gear + belt + load). For a coal conveyor the belt dominates: a 200 m belt at 200 kg/m contributes ~6,400 kg of belt plus a nominal load of ~5 t, all scaled by the gearbox ratio cubed. Use the SIEMENS "Inertia Calculator" worksheet or compute directly:

J_total = J_motor + J_gear/η + (m_belt × r² / η) + (m_load × r² / η)

where r is the head pulley equivalent radius and η is the gearbox efficiency. Set p1496 = 100% to enable full feed-forward.

6.6 Repeat with the belt loaded

Reapply the step with full coal load on the belt. Kp/Tn may need to be re-trimmed by ±20% because the observer has to track a higher inertia. The F07902 value 2 trip should clear if the model and the gain/reset are correct.

7. Reference Tuning Example (90 kW Conveyor Motor)

Parameter Before tuning (default) After manual tuning
p1470 (Kp) 0.030 Nm/rpm 0.012 Nm/rpm
p1472 (Tn) 80 ms 250 ms
p1496 (pre-control) 0% 100%
p1498 (inertia) 0.0 kgm² 4.8 kgm²
p1120 (ramp-up) 10 s 25 s
p1121 (ramp-down) 10 s 25 s
p2162 (n-tol) 6 rpm 15 rpm
p2163 (n-tol time) 100 ms 300 ms
p1656 (setpoint filter) 0 1 (PT2 with f = 80 Hz, D = 0.7)

Note that the tuned Kp is lower than the default. The default is computed from p0350 (motor moment of inertia) only; the manual procedure takes into account the load inertia and the observer stability at low speed.

8. Verification and Acceptance Tests

  1. Step response test (no load): Apply 0% → 50% → 0% step in Startdrive control panel. Record r0061, r0062, r0079, r0080. Verify: rise time < 500 ms, overshoot < 5%, settling time < 1.5 s.
  2. Step response test (loaded): Same test with the belt loaded. Verify the same numerical criteria and no F07902.
  3. Reversal test: Issue 0% → +50% → -50% → 0% setpoint sequence. Verify no observer loss of synchronism (r1407 bit "Sensorless model valid").
  4. No-load current: r0027 (motor current utilization) below 30% at zero load, 60-80% at full load.
  5. F07902 fault memory: Confirm r0945 / r0947 = 0 after the acceptance run. Re-arm p0950 = 0 if required.
  6. Long-term loaded run: 30 minutes at rated load with continuous monitoring of r0061 - r0062. Deviation should be less than p2162 (15 rpm) with p2163 (300 ms).

9. Coal Conveyor Application Specifics

Coal conveyors present four characteristics that complicate SLVC speed control relative to a pump or fan:

  • High and varying inertia. The load can change by 5:1 between empty and fully loaded belt. The inertia parameter p1498 should be set to the average loaded value; the I-term absorbs the residual error.
  • High starting torque. Coal on a start-up is not a static load — the coal mass shifts and settles. Kp must be high enough to track a 100% torque step, but the observer bandwidth at low speed (below p1755, default 5 Hz) is limited.
  • Negative resistance to flow. On inclined conveyors the load pulls the belt downhill when the drive trips. The controller must remain stable at low speed with negative load torque — confirm the reverse direction test in section 8.
  • Long cable runs and du/dt filters. The encoderless observer assumes a clean back-EMF measurement. du/dt filters add ~150 ns of rise time and may require p0230 (filter type) = 2 to be selected so the controller compensates.
For belts longer than 300 m, consider whether SLVC is the correct topology. A belt travel of 30 s and an observer bandwidth of 1-2 Hz will mask load disturbances; a closed-loop encoder (p1300 = 21) may be a more robust engineering choice despite the mechanical retrofit cost.

10. Troubleshooting Matrix

Symptom First Check Most Likely Cause Corrective Action
F07902 v2 at first start with load p0620-p0628 Motor ID never completed or done with loaded belt Empty the belt, repeat p1900 + p1960 = 1
F07902 v2 on every ramp-up p1498 vs. measured inertia Acceleration pre-control either disabled or wrong Re-enter inertia, set p1496 = 100%
Speed oscillation at constant load r0061 / r0062 trace Kp too high for the mechanical coupling Reduce p1470 by 30%, retest
Speed droops under load, never recovers p1472 Tn too large Halve p1472, retest
Acoustic humming from motor at low speed p1755, p1750 Operating below SLVC bandwidth, observer unstable Raise p1755 or set minimum speed p1080 ≥ 5%
F7900 motor overtemperature r0035 I²t, p0610 Motor model has wrong rated current, or Kp too high driving oscillation Verify p0305, reduce p1470
Drive stable empty, trips on load p1498 + p1496 Inertia model mismatch Enable p1496 = 100%, fill p1498
F7902 v3 overshoot on ramp p1656, p1657 Setpoint filter missing, controller too aggressive Enable PT2 filter on setpoint

11. Field-Engineering Notes

  • Always save a backup of the parameters before any manual tuning. Use p0971 = 1 to write to the CF card on the CU320-2.
  • Parameter r1407 bit 8 ("Sensorless model valid") should be 1 continuously when the motor is rotating above p1755. If it toggles, the observer is fighting the load and Kp/Tn are off.
  • Where multiple Motor Modules are mechanically coupled (dual-drive conveyors), enable droop with p1475 ≈ 0.3 × rated speed for even load sharing.
  • If the application demands SLVC below 5 Hz for sustained periods, do not use SLVC. Use V/f with slip compensation (p1300 = 3) for those sub-frequency operating points and switch to SLVC above p1755.
  • For chassis-format S120 modules above 250 kW, the rotary measurement must be run in the "vector control" mode (p1300 = 20) and not in "V/f" (p1300 = 0); verify before issuing the ON command.

FAQ

What does F07902 value 2 mean on a Sinamics S120 in SLVC mode?

It means the actual speed deviated from the setpoint while the drive was under load. The deviation exceeded the threshold in p2162 (default 6 rpm) for longer than p2163 (default 100 ms). For 3rd-party motors, the most common cause is an incorrect motor model after identification or a Kp/Tn combination that is unstable under the loaded mechanical inertia.

Should I run the stationary and rotary measurement with the conveyor loaded?

No. Run p1900 = 2 (stationary) and p1960 = 1 (rotary, full identification) with the belt empty. Loaded belts corrupt the rotor time constant and magnetizing inductance, which destabilises the SLVC observer and reproduces F07902 v2 on the first loaded start.

What are the default SLVC speed controller parameters on a 3rd-party motor?

Defaults are calculated by the drive after identification and stored in p1470 (Kp, encoderless) and p1472 (Tn, encoderless). They are conservative. Typical starting values for manual tuning are p1470 = 0.005 Nm/rpm and p1472 = 2000 ms, before walking Kp up and Tn down following the procedure in section 6.

Can I tune p1460/p1462 in SLVC mode?

No. p1460 and p1462 are the speed-controller gains for encoder-based closed-loop control (p1300 = 21). In SLVC (p1300 = 20) the active gains are p1470 (Kp) and p1472 (Tn). Using the wrong parameter set is a common commissioning error when the drive is online from a closed-loop project.

How do I confirm the SLVC observer is tracking correctly?

Monitor r1407 bit 8 ("Sensorless model valid") and r1407 bit 12 ("Speed observer stable"). Both should read 1 continuously when the motor is rotating above p1755 (default 5 Hz). If either toggles while loaded, the Kp/Tn tuning or the inertia model (p1498, p1496) is incorrect.

Is acceleration pre-control (p1496) required for a conveyor?

Strongly recommended. Set p1498 to the total inertia referred to the motor shaft (motor + gear + belt + load) and p1496 = 100% for full feed-forward. Without it, the I-term alone must absorb the entire inertia-dependent error during ramp-up, which trips F07902 v2 on a heavily loaded belt.

Why is my tuned Kp lower than the default the drive calculated?

The automatic default from identification uses only p0350 (motor moment of inertia). A coal conveyor has a total inertia several times the motor inertia, and the SLVC observer bandwidth at low speed is limited. Reducing Kp by 30-60% of the calculated value, while filling p1498 with the real inertia and enabling p1496 = 100%, is a common correct outcome of manual tuning.

Back to blog