1. Problem Statement
A SINAMICS G120C Profinet (PN) drive trips with fault F08501 the moment the PROFINET controller drops the connection or the PLC transitions to STOP / CLEAR. The default reaction is OFF1 (controlled ramp stop via the ramp-function generator defined by p1121), which halts the motor. In processes where the application requires the drive to keep running from terminal commands when the fieldbus link is lost, the controller must be reconfigured so that F08501 no longer stops the drive and so that a Command Data Set (CDS) switchover moves control from PROFINET back to digital inputs. The same approach applies to the G120C DP (PROFIBUS) variant using F01910 and F07220.
The behavior matches what is already familiar from the legacy MICROMASTER 4 (MM440), where P2040 could be set to 0 to disable the fieldbus watchdog. The SINAMICS platform does not expose a single P2040-style toggle; instead, the same effect is achieved by remapping the fault reaction through the P2100 / P2101 pair.
F08501 to reaction NONE means the drive will continue to apply the last valid setpoint after the fieldbus drops, including the last frequency command from the PROFINET telegram. The PLC must implement a deterministic safe-state, monitor the status word, and execute a controlled switchover to the terminal CDS. This configuration is not suitable for safety-rated applications that require a hard stop on communication loss; use STO (Safe Torque Off, terminal-based on G120C) or a safety PLC for those.2. Affected Drives and Fault Codes
| Variant | Order Reference (typical) | Communication Profile | Triggering Fault |
|---|---|---|---|
| SINAMICS G120C PN | 6SL3210-1KE1x-xxxx (PN) | PROFINET RT / IRT |
F08501 PROFINET communication failure |
| SINAMICS G120C DP | 6SL3210-1KE1x-xxxx (DP) | PROFIBUS DP-V0/V1 |
F01910 Fieldbus timeout, F07220 Telegram failure |
| SINAMICS G120C USS/Modbus | 6SL3210-1KE1x-xxxx (RS485) | USS / Modbus RTU |
F08501 / F01910 (variant-dependent) |
Note: the user-supplied notation "F8501" in the field is the common short form of F08501 as displayed in older STARTER / Startdrive alarm windows. The fault number is identical. The same applies to F1920 ↔ F01910 and F7220 ↔ F07220.
3. Root Cause Analysis
When the G120C receives a PROFINET frame, the on-board PROFINET interface expects another valid frame within the configured sign-of-life fail-safe time. Three conditions raise F08501:
- The PROFINET controller enters the
CLEARstate (PLC goes to STOP, OB1 is no longer scheduled, or the AR is aborted). - The watchdog timer expires. The timeout is set by the controller in the PROFINET AR and is typically 3 missed cycles (default ~30-50 ms depending on the send clock).
- The physical link is broken (cable removed, switch port disabled, EMC-induced link flap).
By default, the SINAMICS fault handler in P2100 / P2101 reacts to F08501 with the standard reaction defined in the firmware: OFF1. The drive decelerates along the ramp defined by p1121, coasts if the fieldbus also carried the OFF2 command, and the process stops. There is no P2040-style "disable comm monitoring" parameter on G120C; instead, the fault reaction itself must be remapped.
4. Solution: Masking F08501 with P2100 / P2101
The P2100 / P2101 pair is the standard SINAMICS mechanism for overriding the reaction of any internal fault or alarm. It is not vendor-locked; the same mechanism masks F30003 (DC-link undervoltage), F07900 (motor blocked), and any other Fxxxxx in the firmware.
4.1 Parameter Semantics
| Parameter | Name | Range / Allowed Values | Index | Description |
|---|---|---|---|---|
p2100[x] |
Fault code for fault reaction change | 0, 30003, 8501, 1910, 7220, etc. | 0..19 (G120C: 0..3 typical) | The fault number whose reaction you want to override. |
p2101[x] |
Fault reaction change | 0 = NONE, 1 = OFF1, 2 = OFF2, 3 = OFF3 | 0..19 (must match p2100 index) | The new reaction. 0 = alarm only, drive continues. |
p2100[4] = 0 (a free index), you must set p2101[4] on the same index. Mismatched indices silently do nothing.4.2 G120C PN — Mask F08501
Use the BOP-2, IOP, STARTER, or Startdrive commissioning tool to enter the following values. This example assumes index 0 is free:
- Set
p2100[0] = 8501(PROFINET communication failure). - Set
p2101[0] = 0(reaction = NONE, i.e. alarm only, no stop). - Save with
p0971 = 1or use the tool's "Copy RAM to ROM" button.
After this change, when the PROFINET connection drops, the drive will issue A08501 (an alarm, not a fault) and continue running with the last valid setpoint. The bit r2139.0 (fault present) and r2138.7 (alarm present) update accordingly; the drive status word will still show the Operation enabled bit set as long as the contactor close / enable bits remain on.
4.3 G120C DP — Mask F01910 and F07220
On the PROFIBUS variant the failure is reported by two faults, both of which should be masked together:
- Set
p2100[0] = 1910,p2101[0] = 0. - Set
p2100[1] = 7220,p2101[1] = 0. - Save with
p0971 = 1.
With both reactions set to NONE, losing the PROFIBUS connection no longer stops the drive. The process is now identical to the G120C PN configuration described above.
5. Masking F30003 (DC-Link Undervoltage) by the Same Method
The same p2100 / p2101 pair masks F30003. The source confirms:
"Set P2100[x] = 30003 & p2101[x] = 0. You need to set p2100 index [x] value which is already 0 & corresponding p2101 index [x] to 0 e.g. if p2100[4] is 0, modify it to 30003 & p2101[4] to be set 0."
- Set
p2100[4] = 30003. - Set
p2101[4] = 0. - Save with
p0971 = 1.
6. PLC Integration: CDS Switchover Logic
Once the fault reaction is NONE, the drive will keep running with the last PROFINET setpoint forever. That is not what most applications want; the correct topology is:
- Define two Command Data Sets on the drive:
-
CDS0= control from digital inputs (terminals), reference from analog input 1. -
CDS1= control from PROFINET, reference from PROFINET PZD2.
-
- Set
p0170 = 2to enable two CDS. - Wire
p0820andp0821(CDS selection bit 0 and bit 1) to a free digital output or to a control word bit that the PLC can write via PZD1. - In the PLC, monitor
ZSW1(Status Word 1, PZD1 received from the drive). When the connection is lost the fieldbus driver clears the input image, the status word reads zero, and the PLC must switch to CDS0.
6.1 Status Word (ZSW1) Bit Map
| Bit | Name | Meaning |
|---|---|---|
| 0 | Ready to switch-on | Power on, electronics initialized |
| 1 | Ready | DC link charged, no faults, ready for ON |
| 2 | Operation enabled | Drive running, following setpoint |
| 3 | Fault present | Latched fault active (irrespective of reaction) |
| 4 | Coast down active (OFF2) | OFF2 command active |
| 5 | Quick stop active (OFF3) | OFF3 command active |
| 6 | Switching on inhibited | ON command locked, fault or OFF1 active |
| 7 | Alarm present | At least one Axxxxx active |
| 8 | Speed setpoint/actual deviation | Outside tolerance window |
| 9 | Control request | PLC requests control; drops on comm loss |
| 10 | f or n reached | Setpoint reached |
6.2 TIA Portal SCL — PROFINET Link-Down Detection and CDS Switchover
Sample code block for a SIMATIC S7-1200/S7-1500 with PROFINET to the G120C PN. Replace the data block / IO addresses with the actual configuration from the device configuration.
// FB: G120C_CommLossHandler
// Inputs
// i_hwIdDrive : HW_IO Hardware identifier of the drive's input slot
// i_dbDrive : BLOCK_DB Symbolic DB mapped onto the drive PZDs
// i_bProfiOK : BOOL TRUE while the PROFINET AR is established
// Outputs
// q_bUseTerminal : BOOL TRUE -> drive should follow CDS0 (terminals)
// q_bAlarm : BOOL TRUE -> raise operator alarm
// Drive status word is at i_dbDrive.%DBW0 (ZSW1, PZD1)
// Drive control word is at i_dbDrive.%DBW2 (STW1, PZD1 outgoing)
// Detect comm loss:
// 1. PROFINET AR aborted -> i_bProfiOK FALSE
// 2. ZSW1 == 0 -> fieldbus input image is zeroed by the controller
#iZSW1 := WORD_TO_INT(i_dbDrive.%DBW0);
IF (NOT i_bProfiOK) OR (iZSW1 = 0) THEN
// Communication lost -> force CDS0 (terminal control)
// CDS bit 0 = 0 selects CDS0; CDS bit 0 = 1 selects CDS1
i_dbDrive.%DBX4.0 := FALSE; // p0820 = CDS bit 0 = 0
// Issue controlled ramp stop via the control word
// STW1 bit 0 = ON/OFF1, bit 1 = OFF2, bit 2 = OFF3
// Set bit 0 = FALSE to ramp down with p1121
i_dbDrive.%DBX3.0 := FALSE; // OFF1
i_dbDrive.%DBX3.1 := TRUE; // No OFF2 (keep torque available for regen)
i_dbDrive.%DBX3.2 := TRUE; // No OFF3
q_bUseTerminal := TRUE;
q_bAlarm := TRUE;
ELSE
// Link is up: PLC controls the drive via PROFINET (CDS1)
i_dbDrive.%DBX4.0 := TRUE; // p0820 = CDS bit 0 = 1 -> CDS1
q_bUseTerminal := FALSE;
q_bAlarm := FALSE;
END_IF;
When i_bProfiOK drops, the S7-1500 also zeros the entire process input image for the missing AR. The S7-1200 CPU behaves the same way. The PLC must not only remap the CDS — it must also stop the drive gracefully, because the masking means the drive itself will not stop on comm loss.
6.3 Ladder Alternative
// Rung 1: comm-loss detector
| NOT i_bProfiOK |
| OR (i_dbDrive.DBW0 == 0) |
|------( )q_bUseTerminal------|
// Rung 2: pick CDS bit
| q_bUseTerminal |
|-----------------(/)---+---( )i_dbDrive.DBX4.0---|
| NOT q_bUseTerminal |
|---( )i_dbDrive.DBX4.0---|
// Rung 3: ON/OFF1 (STW1 bit 0)
| q_bUseTerminal |
|---(/)i_dbDrive.DBX3.0---|
7. Complete Parameter Reference
| Parameter | Value (this procedure) | Meaning |
|---|---|---|
p0170 |
2 | Number of Command Data Sets (CDS). Default is 1. |
p0820 |
r2090.x or PLC bit | BI: CDS bit 0. 0 = CDS0, 1 = CDS1. |
p0821 |
r2090.x or PLC bit | BI: CDS bit 1. With bit 0 forms a 2-bit selector for CDS0..CDS3. |
r0050 |
(read only) | Currently active CDS number (0..3). |
p2100[0] |
8501 (PN) or 1910 (DP) | Fault whose reaction is being remapped at index 0. |
p2101[0] |
0 | Reaction = NONE (alarm only). |
p2100[1] |
7220 (DP only) | Second fault to remap at index 1. |
p2101[1] |
0 | Reaction = NONE. |
p2100[4] |
30003 (optional) | Mask F30003 only if DC-link ride-through is guaranteed. |
p2101[4] |
0 | Reaction = NONE. |
p0971 |
1 | Save parameters to non-volatile memory. Resets to 0 when done. |
p1121 |
(application) | OFF1 ramp-down time, used for the controlled stop on the terminal side. |
r2138.7 |
(read only) | 1 = at least one alarm present (after masking F08501 -> A08501). |
8. Verification Procedure
Verify the masking on a real test rig before going into production. The order matters: confirm fault reaction override first, then verify the PLC's comm-loss response.
-
Baseline. With default parameterization, unplug the PROFINET cable. Drive should ramp down on
F08501with default reactionOFF1. Recordp1121and the deceleration time. -
Apply the masking. Write
p2100[0] = 8501,p2101[0] = 0, andp0971 = 1. Power cycle the drive so the new parameters load from ROM. -
Repeat the cable pull. Disconnect the PROFINET cable while the drive is running at 50% speed. The drive should continue at 50% speed and the HMI should show
A08501(alarm) instead ofF08501(fault). Status wordr0052.0(drive running) should remain TRUE. -
PLC verification. With the drive still at 50% speed and the cable disconnected, observe the S7 input image. It should zero out,
i_bProfiOKshould go FALSE, and the PLC should driveSTW1.0FALSE to command OFF1 on the drive. Verify the drive ramps down onp1121. -
Restoration. Reconnect the cable. The PLC should detect
i_bProfiOK = TRUE, set CDS1, and resume PROFINET control. Verify the drive accelerates back to the new PROFINET setpoint. -
Reset faults. If you want to clear the alarm history after a test, use
p0952 = 0(no fault case counter) or triggerOFF1thenOFF1on the control word. The CDS switchover in CDS0 should remain in place until the PLC explicitly switches back.
9. Alternative Approaches
Masking the fault reaction is one of several methods to deal with comm loss. Evaluate the alternatives against the safety and process requirements before adopting any of them.
| Method | Effect on F08501 | Safety Posture | Recommended Use |
|---|---|---|---|
p2101[0] = 0 (this article) |
Alarm only, drive continues | Lowest — PLC must catch comm loss | Non-safety processes with redundant comm detection in PLC |
| Increase PROFINET watchdog in PLC project | Fault delayed, still stops | Medium — slow response, still controlled | Networks with transient jitter |
| Use PROFIenergy / standard STOP with setpoint zero | Drive ramps to 0, no trip | High — orderly stop | Energy-saving in conveyor clusters |
Wire STO via terminals (drive-side safety) |
Hard stop on wire break | Highest — SIL 2/3 capable | Safety-rated machinery per EN 60204-1 / EN ISO 13849-1 |
| Use a fail-safe PLC with PROFINET Safety | PROFIsafe-controlled stop | Highest — SIL 3 with F-CPU | Machines requiring safety communication |
10. Field-Commissioning Caveats
-
Firmware version:
p2100indexing on G120C has varied across firmware versions. On older V4.4 SP3 the array length was 4 indices; on V4.7 it is still 4 in the standard dataset, but the list manual may show more for newer G120C variants. Always readp2100from the drive to confirm free indices before writing. -
Indexing reset: Writing
p2100[x] = 0does not free the index for re-use on all firmware. If you change the fault number on a used index, the previous fault's reaction is restored. Always write to a known-free index. -
Cold start vs. warm start: On power-up the masked reaction loads from ROM. If the masking was only done in RAM (
p0971not executed), a power cycle will restore the default reaction. - BOP-2 navigation: On the BOP-2, the index is set with the up/down arrow on the parameter number — easy to overlook. The BOP-2 displays the index as a small superscript; STARTER / Startdrive displays the array index in the inspector window.
-
CDS bit source: If
p0820is wired to a digital input, the PLC cannot switch the CDS from PROFINET. Use a control-word bit mapped throughr2090if you need PLC-driven selection.
11. Troubleshooting Matrix
| Symptom | Likely Cause | Corrective Action |
|---|---|---|
Drive still ramps down after p2101[0] = 0
|
Wrote to wrong index; masking not active | Verify p2100[0] reads back as 8501; check the index on the BOP-2 superscript. |
| Masking applied, alarm clears, but PLC still receives F08501 | PLC latches the slot's diag; needs acknowledgment | Acknowledge with STW1.7 rising edge or p3981; clear the S7 diagnostic buffer. |
| Drive keeps running but at the last setpoint after comm loss | PLC did not write STW1.0 = 0; CDS not switched |
Implement the comm-loss handler in section 6; verify r0050 reads 0 after comm loss. |
p2100[0] = 8501 rejected with F7011 |
Parameter locked by BOP-2 access level or write protection | Set p0003 = 3 (Expert access); confirm p7761 = 0 (no know-how protection). |
| After restart, masking is gone | Forgot p0971 = 1
|
Save parameters to ROM; verify by reading p2100[0] after power cycle. |
12. Frequently Asked Questions
Does the G120C PN have a P2040 parameter like the MM440?
No. The SINAMICS G120C does not expose P2040. Communication monitoring is disabled by remapping the fault reaction of F08501 through p2100[0] = 8501 and p2101[0] = 0. The same approach is used for PROFIBUS variants with F01910 and F07220.
Is it safe to set p2101[0] = 0 for F08501?
Not by default. Setting the reaction to NONE means the drive continues at the last valid setpoint after the PROFINET connection drops. The PLC must detect the loss (via ZSW1 == 0 or the PROFINET AR status) and command a controlled stop or switch to a terminal CDS. Use STO or PROFIsafe for safety-rated applications.
How many fault numbers can I remap on a G120C?
The p2100 / p2101 arrays support up to four entries on standard G120C firmware (index 0..3). The user topic references index 4 for F30003, which is a G120C-specific extension; verify the maximum index of your firmware by reading p2100 in STARTER or Startdrive.
Do I need to mask F07220 if I already mask F01910?
On PROFIBUS, yes. F01910 is the fieldbus timeout and F07220 is the telegram failure; they are raised by different conditions inside the SINAMICS firmware. Mask both with p2100[0] = 1910, p2101[0] = 0 and p2100[1] = 7220, p2101[1] = 0 to ensure no comm-loss condition stops the drive.
How do I confirm the masking is saved?
After writing p0971 = 1, wait for the drive to complete the save cycle (typically 3-10 seconds; the BOP-2 displays busy). Power-cycle the drive, then read p2100[0] and p2101[0] from a fresh STARTER / Startdrive session. The values must read 8501 / 0 (or 1910 / 0 for DP) after the cold start.