SINAMICS S120 Motor Module RDY LED Red: Diagnostic and Recovery

David Krause11 min read
SiemensTroubleshootingVFD / Drives
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

SINAMICS S120 Booksize Single Motor Module: RDY LED Red Continuously, DC LED Off

Two SINAMICS S120 Booksize Single Motor Modules — catalog numbers 6SL3120-1TE21-8AA3 (18 A) and 6SL3120-1TE13-0AA3 (3 A) — enter a permanent fault state immediately on power-up. Both modules display the RDY LED steady red with the DC LED off, and neither powers its drive output stage. The original machine builder has password-locked the Starter / Startdrive project, which prevents online access to the fault buffer from the maintenance workstation. This reference documents the offline diagnostic procedure, the LED-state decoding, the firmware/configuration recovery path, and the hardware-verification steps that resolve the fault without requiring project online access.

Safety: The DC link of an S120 motor module can retain hazardous voltage for up to 5 minutes after the line voltage is removed. Verify DC-link voltage with a Class II CAT III 600 V meter at the DC link test points before touching any conductor. Wait at least 5 minutes after Power Off before removing or inserting a module.

1. Affected Components and System Topology

The Booksize Single Motor Modules are part of the SINAMICS S120 Function Manual drive family. Each module is a self-commutated inverter for one servomotor or induction motor and is connected to a higher-level Control Unit (typically CU320-2 or SIMOTION D4xx) over DRIVE-CLiQ.

Catalog number Type Rated output current DC-link voltage Cooling
6SL3120-1TE13-0AA3 Single Motor Module 3 A 510 – 720 V DC Internal air
6SL3120-1TE21-8AA3 Single Motor Module 18 A 510 – 720 V DC Internal air

Both modules share the same LED cluster on the front face:

  • RDY – ready / fault indicator
  • DC – DC-link status
  • OPT – option (DRIVE-CLiQ link state)

A correctly commissioned module lights green on RDY with DC green once the line module has charged the DC bus to the working voltage.

2. RDY LED State Decode for Booksize Motor Modules

The RDY LED is the primary diagnostic indicator. Each colour and cadence maps to a distinct phase of the module's internal state machine.

RDY LED State meaning Recommended action
Off 24 V control electronics missing or module not fully inserted Verify 24 V at X124; re-seat module
Green continuous Ready for operation No action
Green flashing 0.5 Hz Commissioning / ramp-up in progress Wait for completion
Green flashing 2 Hz Firmware download in progress Wait, do not power off
Yellow continuous Warning present, drive still operational Read warning buffer
Yellow flashing 2 Hz Topologies differ (commissioning mode) Accept topology in Startdrive
Red continuous At least one fault present Read fault buffer; module inhibited
Red flashing 0.5 Hz Control Unit boot error Check DRIVE-CLiQ cabling
Red flashing 2 Hz Firmware could not be started (CRC error, version mismatch, missing firmware) Reload firmware / check CF card
Red flashing with rapid blink Hardware defect / EEPROM error Replace module

The cited condition — RDY steady red, DC off — indicates that the module has cleared its boot phase, loaded firmware, and detected a fault that inhibits the DC-link pre-charge and inverter output. The DC LED remains off because the inverter has not been enabled and the gate-drive supply is suppressed by the fault handler.

2.1 SINAMICS Integrated reference

The status-display concept is shared with the SINAMICS Integrated variant inside the SIMATIC Drive Controller. The relevant rule — "RDY LED flashes red at 2 Hz: firmware could not be started (for example, update error, drive firmware not compatible with CPU or missing, CRC check failed)" — applies to every SINAMICS variant that hosts the same firmware stack and applies to the standalone Booksize modules in this article.

3. Root Cause Matrix

For an installation that has run ten years, the fault is almost always one of the following:

# Root cause Symptom clues Likelihood on legacy system
1 CompactFlash card corrupted or unreadable RDY red, 2 Hz flash after long pause High
2 CRC / checksum mismatch on stored firmware RDY red flashing 2 Hz High
3 Firmware version on module newer than Control Unit knows DRIVE-CLiQ topology mismatch Medium
4 EEPROM failure (rare on module, more common on CU) RDY red rapid blink Low
5 24 V supply under-voltage at X124 RDY red after chatter Medium
6 DRIVE-CLiQ cable defect or wrong port OPT LED red or off Medium
7 Hardware defect (IGBT gate-driver, current sensor) RDY steady red, no boot progression Medium on 10-year-old equipment
8 DC link short / motor insulation breakdown RDY red after line module charges Medium

4. Diagnostic Procedure Without Online Project Access

Because the machine builder locked the Starter / Startdrive project, the user cannot retrieve the diagnostic buffer over PROFIBUS / PROFINET. The following procedure extracts the fault information using the panel, the operator controls, and direct hardware inspection.

4.1 Prerequisites

  • One CU320-2 Control Unit (or SIMOTION D4xx) with a temporary service project that does not require the OEM password
  • An empty SD card / CF card formatted FAT32
  • SINAMICS Startdrive or Starter commissioning tool installed on a laptop
  • DRIVE-CLiQ cable (RJ45, Siemens 6SL3060-4Axx-0AA0 or compatible)
  • USB or Ethernet connection between laptop and CU320-2
  • Class II CAT III 600 V meter for DC-link voltage checks

4.2 Step-by-step Offline Diagnosis

  1. De-energise the cabinet. Open the line contactor, isolate the supply, wait 5 minutes, verify zero volts on the DC link at the test points of every module.
  2. Swap modules to an identical spare slot (if available). If the second slot clears the fault, the issue is the upstream connector or DRIVE-CLiQ port, not the module.
  3. Create an empty Startdrive project on the laptop. Insert the project into a CU320-2 with factory reset. Do not transfer the OEM project.
  4. Connect the CU320-2 to the affected modules with a fresh DRIVE-CLiQ cable, observing the standard star topology rules.
  5. Power up the CU320-2 only. Do not yet energise the line module. Read the LED state of the SINAMICS module.
  6. Click "Accessible nodes" in Startdrive. The CU320-2 will detect the motor modules even with no project loaded.
  7. Read the diagnostic buffer of each module: Drive unit > Diagnostics > Diagnostic buffer. Record every F-code (fault) and A-code (warning).
  8. Read the firmware version from the device trace: Drive unit > Properties > Firmware version. Cross-check with the firmware matrix in the S120 Function Manual.
  9. Save the trace files (file extension .trc) and export the fault buffer as XML for archival.
  10. Compare topology. Open Topology > Graphic view. A red exclamation mark on a module indicates either a missing or wrong-addressed DRIVE-CLiQ node.
Even if the OEM project is password-locked, the CU320-2 retains a live diagnostic buffer in non-volatile memory. A factory-reset CU plus an empty Startdrive project is sufficient to read those values without unlocking the OEM configuration.

4.3 Reading the Fault Code Without Startdrive

If a CU320-2 is not available, the module exposes the fault code in two alternate ways:

  1. 7-segment display on the front of the Control Unit (where one exists in the line-up) — the fault number scrolls through the digit positions. For example, "F08501" appears as F then 08501.
  2. Flashing pattern on the RDY LED of the module itself when the CU is replaced by a STARTER diagnostic CU with an empty project.

5. Firmware and Memory Card Recovery

On a 10-year-old installation, the most common cause of the red RDY with CRC mismatch is corruption of the firmware stored on the module's internal memory or on the CompactFlash card of the Control Unit.

5.1 Required firmware

Component Required firmware family Source
CU320-2 SINAMICS S120, V5.x or V4.x (matches existing line) Siemens Support entry 109738572
6SL3120-1TE13-0AA3 SINAMICS S120 V5.x motor module firmware Siemens Support entry 109738572
6SL3120-1TE21-8AA3 SINAMICS S120 V5.x motor module firmware Siemens Support entry 109738572

5.2 Firmware reload procedure

  1. Insert the empty FAT32 SD card into the laptop.
  2. Copy the matching firmware file (.bin) into the root of the card.
  3. Power off the CU320-2.
  4. Insert the card into the CU320-2 card slot.
  5. Hold the DIAG button while powering on the CU320-2 to force a firmware download into the motor module. The RDY LED flashes green at 2 Hz during the write.
  6. Wait until the RDY LED is steady green or red (not flashing). A steady red indicates the firmware loaded successfully but a fault still exists in the system — proceed to read the buffer again.
Compatibility: Mismatching the firmware family (for example loading V5.x onto a V4.x line) is itself a fault source. Always confirm the firmware family on the original machine documentation or read it from a working sister module before reloading.

6. Hardware Verification

After the firmware state is verified, eliminate the hardware causes listed in the root-cause matrix.

6.1 24 V Control Supply Check

Test point Acceptable value Action if out of range
X124 pin 1 (+) – pin 2 (−) 20.4 V – 28.8 V DC Replace SITOP / power supply
X124 pin 3 (+) – pin 4 (−) 20.4 V – 28.8 V DC Check second supply

6.2 DC-Link Pre-Charge

  1. Energise the line module only.
  2. Measure DC link at the test points: target = 1.35 × Vline × √2 / √3 (for 400 V line ≈ 540 V DC).
  3. If DC link voltage stays at zero, the line module pre-charge circuit is suspect; check the pre-charge resistor and contactor K1.

6.3 DRIVE-CLiQ Cable and Port Test

  1. Unplug and re-plug every DRIVE-CLiQ connector on the affected module.
  2. Inspect the RJ45 latch for cracks.
  3. Replace any DRIVE-CLiQ cable longer than 70 m with the Siemens MC500 / MC800 media converter configuration.

6.4 Motor Insulation

  1. Disconnect the motor leads at the module terminal.
  2. Measure phase-to-phase and phase-to-ground insulation with a 500 V megohmmeter.
  3. Reject if R < 1 MΩ. A low reading forces a motor-side overcurrent fault that the module reports as a hardware defect on its own diagnostics.

6.5 Power-Cycle and Watch the RDY Cadence

Reapply 24 V with the line contactor open. Observe the RDY LED for 30 seconds:

Observed cadence Diagnosis Action
Rapid red blink, never settles EEPROM / hardware defect Replace module
Steady red after boot Firmware loaded, fault remains Read fault buffer
Red 2 Hz forever Firmware boot failure Reload firmware via SD card
Steady green Recovered Proceed to commissioning

7. Replacement Considerations

If the module is electrically defective, a like-for-like replacement requires the same catalog number. With the OEM project locked, the replacement module must contain firmware matching the existing system, and the CU320-2 will write its topology automatically on next power-up if the same slot is used.

  • 6SL3120-1TE13-0AA3 – 3 A booksize, 50 mm width, internal air cooling
  • 6SL3120-1TE21-8AA3 – 18 A booksize, 100 mm width, internal air cooling

Use only Siemens-original spare parts. Counterfeit modules exist on the open market; verify the serial number against the Siemens product traceability database before installation.

8. Verification Procedure After Recovery

  1. Power up. Confirm RDY = steady green, DC = green.
  2. Open Startdrive and read the diagnostic buffer: zero faults, zero warnings.
  3. Issue a speed setpoint of zero and enable the drive via the PLC. Confirm output current < rated idle current.
  4. Run the motor at 10 % rated speed for 5 minutes. Monitor temperature; module baseplate temperature should stabilise < 60 °C in a properly ventilated cabinet.
  5. Run the motor at rated speed and load. Capture the diagnostic trace during the run; expect zero faults after one full duty cycle.

9. Extended Troubleshooting Matrix

Observed LED Last fault code Cause Fix without OEM access
RDY red steady, DC off F08501 CRC / firmware mismatch Reload firmware via SD
RDY red steady, DC off F30001 Overcurrent Check motor insulation; check encoder
RDY red steady, DC off F30002 DC link overvoltage Check line module / braking chopper
RDY red steady, DC off F30802 Power-unit EPROM error Replace module
RDY red steady, DC off F31812 DRIVE-CLiQ hardware fault Replace cable / port
RDY red 2 Hz F01000 / F01001 Software / firmware error Reload firmware
RDY red rapid blink n/a Hardware defect Replace module

10. Preventive Recommendations for Legacy Systems

  • Schedule a firmware / parameter backup every 12 months.
  • Replace cabinet fans every 5 years; clogged fans raise module temperature and trigger faults.
  • Inspect DRIVE-CLiQ connectors for oxidation at every major shutdown.
  • Document the OEM password in a secure password vault before the OEM becomes unreachable.
  • Keep a service SD card pre-loaded with the matching firmware family in the cabinet.

What does RDY LED steady red on a SINAMICS S120 Single Motor Module mean?

RDY steady red means at least one fault is present in the module. The module inhibits its gate drivers and the DC LED remains off because the inverter output stage is disabled. Read the diagnostic buffer on the Control Unit to identify the specific fault number.

How can I read the fault code without the OEM Starter project?

Disconnect the OEM Control Unit, replace it with a temporary CU320-2 holding an empty Startdrive project, and select "Accessible nodes" over Ethernet. The diagnostic buffer and firmware version of every motor module remain readable without unlocking the OEM configuration.

Why does the RDY LED flash red at 2 Hz after a long-running system?

A 2 Hz red flash indicates a firmware boot failure — typically a CRC error, missing firmware, or firmware version incompatible with the Control Unit. This is common on systems older than 8–10 years where the CompactFlash card or internal flash memory has degraded. Reload the matching firmware via SD card.

Can a SINAMICS S120 Single Motor Module 6SL3120-1TE13-0AA3 and 6SL3120-1TE21-8AA3 be replaced without the OEM password?

Yes. A like-for-like replacement module with matching catalog number and matching firmware family will be accepted by the CU320-2 on next power-up. The Control Unit writes the topology and parameters automatically when the same DRIVE-CLiQ port is reused.

Is the DC LED off caused by the same fault as RDY red?

Yes. When the module enters a fault state it suppresses the gate-drive supply and blocks DC-link pre-charge, so the DC LED stays off. Clearing the fault restores the DC LED; you do not need to diagnose DC LED off as a separate issue.

Back to blog