Resolving SINAMICS S120 ON/OFF1 Startup Delay: P0346, Brake, and DC-Link
Engineer field notes for diagnosing and reducing the 1000–1800 ms quiescent period between the leading edge of STW1.0 (ON/OFF1) and the first mechanical motion of a SINAMICS S120-driven induction motor. Applies to Active Line Module (ALM) + Motor Module chassis configurations and to Active Interface Module (AIM) chassis with internal line contactor. Covers parameter P0346 (magnetization time), P1215–P1218 (mechanical brake control), P0861/P0862 (line contactor pre-charge), control-word sequencing, and trace-based verification on STARTER / Startdrive.
1. Problem Definition
A SINAMICS S120 drive configured with an Active Line Module (ALM) or with a chassis-format Active Interface Module (AIM) shows a 1000–1800 ms delay between the leading edge of control word bit 0 (STW1.0, ON/OFF1) and the first measurable mechanical movement of the motor shaft. All enable signals are present, the ramp-function generator is enabled, the brake is commanded to open, no faults are queued, and the DC link is already charged to the regulated 600 V level.
Trace recordings (function generator via STARTER trace or Startdrive trace) show that the drive advances from internal state "Ready" to "Controller enable / pulses enabled" only after a measurable quiescent period during which neither pulse pattern nor output current is present. The magnetizing current then rises for the duration of P0346 before the setpoint is finally released. The issue has been reproduced on 55 kW cage-induction motor modules in both crane-hoisting and indexing-axis applications. It is reproducible only on chassis hardware; Booksize units in equivalent applications do not exhibit the same delay.
1.1 Typical symptoms
- ON/OFF1 (STW1.0) is set high; the drive does not enter state S4 (Operation) for 1.2 to 1.8 seconds.
- Trace r0899 (status word ZSW1) shows the bit pattern advancing through S2 (Ready for switching on) → S3 (Ready for operation) → S4 (Operation) with a visible gap at the S3 → S4 transition.
- r0046.27 (Missing enable) drops at the trailing edge of the delay; no drive-side fault is latched.
- Output current ramps from 0 to magnetizing current over the value of P0346; current setpoint is not released until after the gap.
- Mechanical brake command r1229.1 (command "close brake / open brake") toggles at the end of the gap, not at the leading edge of ON/OFF1.
1.2 Acceptable target
For crane-hoisting, conveyor, and indexing axes on most SINAMICS S120 applications the accepted targets are:
- 250–350 ms from ON/OFF1 leading edge to first torque production.
- 0–150 ms from ON/OFF1 leading edge to first mechanical motion once the brake has been released (i.e. the delay attributed solely to the S120 drive itself should be below 200 ms in steady-state operation).
2. Anatomy of the SINAMICS S120 Startup Sequence
The S120 control sequence advances through five distinct internal states before the first mechanical torque is produced. The delay between any two adjacent states is a function of hardware settling, software debounce, parameter-set values, and the external enable signals configured in p0852, p0854, p0855, p0856, p0858, and p0860. The function chart 2440 (control sequence / state machine) in the SINAMICS S120/S150 List Manual documents these transitions; the description in the SINAMICS S120 product documentation should be treated as the source of truth.
| State | Designation | Required action to leave state | Typical time | Controlling parameter |
|---|---|---|---|---|
| S0 | Power-on / pre-charge | DC link charged to rated value (p0210) | 0.5–10 s (line contactor) or 0 s (regulated ALM) | p0861, p0862, p0210 |
| S1 | Ready for switching on | OFF commands cleared, no missing enable | ≤ 100 ms | p0852 |
| S2 | Ready for operation | Pulse enable and STW1.0 = 1 | 50–200 ms | p0854, p0855 |
| S3 | Pulses enabled / magnetization | Magnetization time P0346 elapsed | 0.1–3 s | p0346 |
| S4 | Operation / setpoint released | Brake released and setpoint nonzero | 50–250 ms | p1215, p1216, p1217 |
Reading the table bottom-up: most of the 1000–1800 ms delay on chassis hardware is concentrated in the S3 → S4 transition and the S3 dwell time. The first two transitions (S1 and S2) account for only 150–300 ms in a well-configured system.
3. Root Cause Analysis — Four Controllable Delay Sources
The 1.0–1.8 s delay is the sum of four independent, partially overlapping contributions. Each is controllable and each has a different remedy.
3.1 Magnetization time P0346
P0346 sets the time the drive leaves the rotor free to build up flux before a torque-producing setpoint is released. For an induction motor, the rotor must be magnetized to approximately rated flux before any meaningful torque is produced; an unmagnetized motor started under load will stall or pull excessive current.
Default behavior: P0346 is calculated automatically from the motor data during initial commissioning (P0340 = 1 or 2) and typically lands in the 1.0–3.0 s range for a 55 kW motor. The default is conservative because it assumes cold motor, full-load inertia, and a worst-case rotor time constant.
Why the delay is visible: if the controller issues ON/OFF1 and a setpoint simultaneously, the drive performs magnetization while the brake is still closed. The user perceives this as a delay because no mechanical motion occurs during magnetization. The magnetizing current itself rises over P0346, not instantaneously.
3.2 Mechanical brake release
When a holding brake is configured (P1215 ≠ 0), the brake release sequence runs after the magnetization has stabilized. The sequence is:
- Output current exceeds the brake opening threshold P1220 (default 0 A on speed-controlled axes, configurable).
- Brake open command issued on r1229.1; output stage toggles the brake output or the Safe Brake Relay / Safe Brake Adapter.
- Brake physically releases after P1216 (brake opening time, default 100 ms; manufacturer-stated values 50–500 ms).
- Setpoint released; ramp-function generator begins to accelerate the motor.
If the brake opening time P1216 is conservatively set to 250 ms and the brake opening threshold is set to 50 % of rated torque, the combined delay is 250–500 ms on top of the magnetization time.
3.3 DC-link pre-charge and line contactor
The DC-link pre-charge path differs sharply between infeed topologies:
- Active Line Module (ALM): pre-charge is performed by the active IGBT bridge; the DC link reaches the regulated 600 V level within 100–500 ms of line power. Once the ALM is in state "Operation" the DC link is held at 600 V indefinitely, including during the OFF state. Subsequent ON commands do not retrigger pre-charge.
- Basic Line Module (BLM): pre-charge is passive through a resistor; takes 0.5–5 s depending on DC link capacitance. Re-pre-charges on every line-side disconnect.
- Active Interface Module (AIM) chassis: contains an internal pre-charge path and line contactor. The contactor closes on line power; pre-charge takes 1–5 s; once the contactor is closed the DC link remains charged as long as line power is present.
If the user's drive uses an ALM and the ALM is already in state "Operation", pre-charge should not contribute to the delay. If, however, the line contactor to the AIM/BLM is being closed by the same ON command that closes the line contactor, the delay will include the pre-charge interval.
3.4 Chassis vs Booksize hardware timing
Chassis Motor Modules (≥ 250 kW) and chassis ALM/AIM modules execute the state-machine transition with a 100–200 ms additional latency compared to Booksize modules. This is documented in the S120 List Manual function chart 2440 footnote and is related to the optical-fiber communication debounce between the Control Unit and the Motor Module. Booksize units use a faster internal bus, so the same control sequence completes ~150 ms sooner.
This is a hardware-fixed contribution; it can only be masked by overlapping other delays (e.g. issuing the ON/OFF1 in advance, as described in §6.1).
4. Parameter Reference
All parameters below are described in the SINAMICS S120/S150 List Manual. Default values shown are for firmware V5.2 SP3; consult the List Manual for your firmware version, as defaults can shift between releases.
| Parameter | Name | Range | Default | Effect on delay |
|---|---|---|---|---|
| p0346 | Magnetization time | 0 – 20000 ms | Auto-calc (~1500 ms @ 55 kW) | Direct: full P0346 dwell in S3 |
| p1215 | Brake configuration | 0 / 1 / 2 / 3 | 0 | Enables brake sequence; must be 1/2/3 if a brake exists |
| p1216 | Brake release time | 0 – 10000 ms | 100 ms | Adds to delay after magnetization |
| p1217 | Brake closing time | 0 – 10000 ms | 100 ms | Closing only; not part of ON delay |
| p1218 | Brake opening threshold | 0 – 100 % | 0 % | Torque setpoint threshold to open brake |
| p1220 | Brake opening current threshold | 0 – 100 % | 0 % | Output current threshold to open brake |
| p0852 | Enable operation (ON) | 0 – 65535 | 1 (STW1.0) | Source of ON command |
| p0854 | Enable controller (pulse enable) | 0 – 65535 | 1 (STW1.3) | Source of pulse enable |
| p0855 | Enable speed controller | 0 – 65535 | 1 (STW1.4) | Source of controller enable |
| p1140 | Ramp-function generator enable | 0 – 65535 | 1 (STW1.4) | Source of RFG enable |
| p1141 | Ramp-function generator start | 0 – 65535 | 1 (STW1.5) | Source of RFG start |
| p1142 | Ramp-function generator setpoint enable | 0 – 65535 | 1 (STW1.6) | Source of setpoint enable |
| p0861 | Pre-charge time | 0 – 60000 ms | 500 ms | Minimum DC-link pre-charge interval |
| p0862 | Line contactor wait time | 0 – 60000 ms | 1000 ms | Wait time after contactor close |
| p0210 | DC link voltage setpoint | 0 – 1000 V | 600 V (ALM) | Target regulated DC link |
| p1310 | Continuous boost | 0 – 250 % | 50 % | Volts/Hz boost at low speed; affects flux build |
| p1610 | Torque setpoint filter | 0 – 10000 ms | 0 ms | Filters torque during start |
| p1611 | Acceleration torque boost | 0 – 1000 % | 0 % | Boost during acceleration |
5. Diagnostic Procedure — Trace r0899, r0046, and r1229
A four-channel trace on STARTER or Startdrive resolves the cause in under five minutes. Use a 1 kHz sample rate, a 4 s pre-trigger, and the following signals:
- r0899.0 — ZSW1.0 (Ready for switching on)
- r0899.1 — ZSW1.1 (Ready for operation)
- r0899.2 — ZSW1.2 (Operation enabled)
- r0899.6 — ZSW1.6 (Switching on inhibited / Missing enable acknowledged)
- r0046.27 — Missing enable signal (latched bit)
- r1229.1 — "Open brake" command to the brake output stage
- r0063 — Actual speed (filtered; useful to confirm the moment of mechanical motion)
Reading the trace from left to right:
- STW1.0 rising edge: ON command accepted.
- ZSW1.0 = 1 within 5 ms (no missing enable).
- ZSW1.1 = 1 within 50–100 ms (pulses can be enabled).
- ZSW1.2 = 1 — this is the transition you must time-stamp. The interval between STW1.0 rising and ZSW1.2 = 1 is the measured startup delay.
- r1229.1 toggles high shortly after ZSW1.2 = 1; r0063 begins to rise P1216 ms later.
If the gap between ZSW1.1 = 1 and ZSW1.2 = 1 is approximately equal to P0346, the magnetizing time is the dominant contributor. If the gap is approximately equal to P1216, the brake release time is the dominant contributor. If the gap is approximately equal to P0861+P0862, pre-charge is the dominant contributor. If all three are short and a residual 150–200 ms remains, chassis hardware debounce is the dominant contributor.
6. Solutions and Optimization
The remedies below are ordered from most effective to least. Apply them in order, re-measuring between each, until the target delay is met.
6.1 Reorder the enable sequence — "ON first, then Run"
This is the single highest-impact change and the one most often missed in the field. The principle: the magnetization dwell (P0346) and the chassis hardware debounce (~150 ms) can be done in advance, so that the leading edge of STW1.0 is not the leading edge of "first time we need torque".
Implementation:
- Issue STW1.0 (ON/OFF1) and STW1.3 (pulse enable) before the moment torque is needed. For a crane, this is typically at the moment the operator selects "hoist" or "lower"; for a conveyor, it is at the moment the upstream process signals "ready".
- Hold the ramp-function generator at zero (STW1.4 = 0, STW1.5 = 0, STW1.6 = 0) until the motion is requested.
- When motion is needed, raise STW1.4 (enable speed controller), STW1.5 (RFG start) and STW1.6 (setpoint enable) only. The drive is already in S4 / pulses-enabled / magnetized. The brake opens within P1216 ms and motion begins.
Result: residual delay from "Run" command to first mechanical motion is reduced to the brake opening time P1216 (50–250 ms typical) plus the chassis debounce already absorbed in step 1. The 1000–1800 ms gap is eliminated because the gap is filled with idle time before the motion command, not after.
6.2 Reduce P0346
The value of P0346 should be ≥ 3 × rotor time constant Tr. For a 55 kW 4-pole cage motor, Tr is typically 200–500 ms; a safe P0346 is 600–1500 ms. The default 1500 ms is conservative.
- Read the actual rotor time constant from p0623 (motor equivalent circuit diagram, rotor time constant). Confirm the unit and verify against the motor data sheet.
- Set p0346 = max(50, 3 × p0623). For a motor with Tr = 300 ms, this gives 900 ms — a 600 ms reduction.
- Verify with a no-load start that the magnetization completes within the new p0346 by tracing r0331 (smoothed magnetizing current / flux actual value).
- Verify under load that the motor does not stall or pull excessive current during the first 200 ms of setpoint release. A short stall period indicates P0346 is too short.
6.3 Pre-magnetize during standstill with zero setpoint
For applications where the user is willing to draw magnetizing current continuously while the drive is at standstill, configure the drive so that the rotor is magnetized whenever the system is "ready" (e.g. crane in cabin, conveyor in standby, hoist not moving). The drive is in S4 with r0063 = 0, drawing magnetizing current at no-load losses.
Implementation:
- Keep STW1.0 = 1, STW1.3 = 1, STW1.4 = 1 throughout the standby period.
- Set the setpoint to 0 (or use a freeze-setpoint bit).
- Make sure the motor is force-cooled if the duty cycle in standby is high; a magnetized standstill motor relies on the integrated fan for cooling, and rotor losses can accumulate.
- Reduce P1310 (continuous boost) before applying this technique — a continuous boost of 50 % at standstill can cause 30–40 % of rated current to flow, which can overheat the motor if the standby is long.
Result: "first motion after standby" is immediate (only P1216 + brake debounce, ~150–250 ms). The penalty is continuous magnetizing current (~30 % of rated, depending on P1310) and reduced thermal headroom.
6.4 Optimize brake timing
Three parameters dominate brake timing:
- P1216 (release time): set to the manufacturer-stated release time of the actual brake, not to a conservative default. A 100 ms value is fine for a millisecond-class industrial disc brake; setting P1216 = 500 ms is overkill and adds 400 ms to the delay.
- P1218 (torque threshold): on a vertical axis, set to a value that ensures torque is established before the brake releases. Typical: 5–10 % of rated torque for a hoist, 0–2 % for a horizontal axis.
- P1220 (current threshold): for safety, do not set to 0 — set to a low value (e.g. 5 % of rated) so that the drive confirms it is producing current before commanding the brake open.
6.5 Consider a Booksize unit
If the application is not bound to chassis hardware by power level, a Booksize Motor Module has measurably faster state-machine transitions on the order of 100–150 ms less delay. The user with a 55 kW hoist cannot replace the chassis ALM with a Booksize ALM at the same power level; however, the same application on a different motor at lower power can benefit from this. This option is more a hardware-design recommendation than a field fix.
7. Worked Example — 55 kW Crane Hoisting
Use case: 55 kW induction motor on a SINAMICS S120 chassis ALM with an external 24 V holding brake. Original configuration:
- P0346 = 1500 ms (auto-calculated at commissioning)
- P1215 = 1 (brake with torque proving)
- P1216 = 100 ms
- P1218 = 10 %
- P1220 = 5 %
- STW1.0 = ON command from operator pendant
- STW1.3 = same source
- Setpoint from joystick
Measured delay from joystick press to first motion: 1300 ms. Trace shows a 1100 ms gap between ZSW1.1 = 1 and ZSW1.2 = 1 — i.e. P0346 (1500 ms) minus the magnetizing current rise time (≈ 400 ms in this motor) = 1100 ms, plus 200 ms chassis debounce.
Application of §6.1 (reorder): wire the operator "hoist selected" bit to STW1.0 + STW1.3, and the joystick to STW1.4/1.5/1.6. New measured delay: 180 ms (P1216 + 80 ms debounce). Magnetization is done while the operator is choosing direction; the moment the joystick moves, motion begins.
For users who cannot modify the operator interface: apply §6.2 with p0346 = 800 ms (verified by no-load test). New measured delay: 700 ms — still useful, but §6.1 is preferred where feasible.
8. Safety and Side-Effects
- Reduced P0346 with load present: A motor starting under full load with insufficient magnetization will pull 2–3 × rated current for 100–300 ms, then either stall (F07902) or accelerate jerkily. Always test P0346 with the worst-case load attached.
- Continuous pre-magnetization (§6.3): A magnetized standstill motor draws magnetizing current continuously. If the standby duty cycle exceeds 30 % of the time, fit forced cooling or limit the standby to avoid thermal overload. Verify with r0037 (motor temperature model) or with an external PT100.
- Brake pre-torque threshold (P1218): On a vertical axis, an aggressive threshold (e.g. 0 %) opens the brake before torque is established, which causes the load to "droop" by the slack in the gearbox. Use 5–10 % of rated torque for a hoist; use 0 % only for horizontal axes with no vertical load.
- Reordering ON/OFF1 (§6.1): This requires the upstream PLC to manage the state. Make sure the safety circuit (STO, SS1, SBC) still triggers on STW1.3 / pulse-disable; the enable state should not be latched in a way that defeats the safety function.
9. Verification Procedure
After any parameter change, repeat the trace from §5 and confirm:
- STW1.0 → ZSW1.2 ≤ 200 ms (drive-side residual) for a crane or 350 ms absolute for an indexing axis.
- ZSW1.2 = 1 → r1229.1 = 1 ≤ 10 ms (no spurious dwell).
- r1229.1 = 1 → r0063 > 1 rpm within P1216 + 50 ms (brake release is the dominant delay).
- No F07902 (motor stalled) within the first 2 s of motion.
- No overcurrent trip (F30001 / F30002) within the first 2 s of motion.
- Thermal model r0037 remains below 100 % during a 10-minute loaded-cycle test simulating the application duty cycle.
10. Troubleshooting Matrix
| Symptom on trace | Dominant contributor | Remedy | Expected improvement |
|---|---|---|---|
| Long gap ZSW1.1 → ZSW1.2, equal to P0346 | Magnetization time | §6.1 reorder or §6.2 reduce P0346 | 600–1500 ms |
| Long gap ZSW1.2 → r1229.1, equal to P1216 | Brake release time | §6.4 reduce P1216 to manufacturer value | 50–200 ms |
| Long gap r1229.1 → r0063, > 300 ms | Brake opening current threshold not met, or P1218 too high | Check P1220 and P1218; verify magnetizing current r0331 | 100–500 ms |
| Long gap line-on → ZSW1.0, with ALM | ALM not in "Operation"; line contactor still open | Check ALM status; verify p0861/p0862 are not retriggering | 0.5–5 s |
| Residual 150–200 ms gap not explained by parameters | Chassis hardware debounce | §6.1 reorder to absorb in advance | 100–200 ms |
| F07902 within 500 ms of motion start | P0346 too low | Increase P0346 to 3 × p0623; verify under load | Trip eliminated |
| Current spike at brake release | Brake opens before flux is established | Increase P1218 or delay brake release until r0331 has settled | Spike eliminated |
11. Common Misconfigurations
- P1215 = 0 with a brake physically present: the drive never issues a brake open command. The motor may still be energized, but the brake stays closed and the drive reports motion incorrectly.
- P0346 = 0: disables the magnetization dwell. The drive releases the setpoint before flux is built. Result: a 2–3 × current spike at brake release and possible F07902.
- STW1.3 wired to the same source as STW1.0 with no independent enable: the reordering in §6.1 cannot be applied because the controller cannot separate "ON" from "pulse enable".
- P1310 left at default 50 % with continuous pre-magnetization: the magnetizing current at standstill is excessive; the motor overheats in long standby. Reduce P1310 to 0–20 % before applying §6.3.
12. Frequently Asked Questions
What is the typical SINAMICS S120 startup delay on a chassis drive with a 55 kW motor?
1200–1800 ms from STW1.0 (ON/OFF1) to first mechanical motion when the drive is configured ON-and-Run. The dominant contribution is P0346 magnetization time (default ~1500 ms auto-calculated), with an additional 150–200 ms chassis hardware debounce. The delay can be reduced to 150–250 ms by reordering the control sequence so that ON/OFF1 and pulse enable are issued in advance, as described in §6.1.
What does SINAMICS parameter P0346 control?
P0346 is the magnetization time in milliseconds — the dwell the drive holds the setpoint at zero after pulse enable to allow the rotor flux to build. The default is auto-calculated from the motor equivalent-circuit-diagram data and typically lands in the 1.0–3.0 s range. A safe manual value is 3 × p0623 (rotor time constant). Reducing P0346 below ~3 × p0623 risks F07902 (motor stalled) and current spikes of 2–3 × rated at brake release.
Does the Active Line Module (ALM) add to the startup delay?
No, provided the ALM is already in state "Operation" with the DC link regulated at 600 V. Pre-charge is performed by the ALM once at line power-up and is not retriggered on subsequent ON commands. The 1000–1800 ms delay measured on a chassis ALM + Motor Module system is therefore not from pre-charge; it is from P0346 magnetization plus chassis debounce. If a Basic Line Module (BLM) or AIM with internal line contactor is in use, the pre-charge does contribute — verify with p0861 (pre-charge time) and p0862 (line contactor wait time).
Can the brake release time P1216 be set below 100 ms?
Yes, but the actual brake release time is a property of the physical brake, not of the drive parameter. P1216 should be set to the manufacturer-stated release time of the brake (typically 50–250 ms for industrial disc brakes; consult the brake data sheet). Setting P1216 to 0 tells the drive to assume instantaneous brake release, but the brake will still open at its physical rate. An aggressive P1216 below the actual release time will not cause a fault, but it can cause the drive to release the speed setpoint before the brake has actually opened, which produces a current spike as the rotor catches up.
Why does a Booksize unit start faster than a chassis unit in the same application?
Chassis Motor Modules (≥ 250 kW class) and chassis ALM/AIM modules use optical-fiber communication between the Control Unit (CU320-2) and the power modules, with a 100–200 ms debounce in the state-machine transition. Booksize modules use a faster internal bus, so the same control sequence completes ~150 ms sooner. This is a hardware-fixed contribution and cannot be reduced by parameter changes; it can only be masked by reordering the control sequence so that the debounce occurs during standby rather than during the first motion command.
Which firmware version is required for reliable P0346 reduction?
SINAMICS S120 firmware ≥ V4.5 is recommended. Earlier V4.x versions had a fixed 1 s minimum dwell regardless of P0346, which made aggressive P0346 reduction ineffective. V5.x and later honour the parameter value and add improved flux models (P341, P342) that shorten the actual settling time beyond what P0346 alone indicates. The S120/S150 List Manual on the Siemens Industry Online Support portal lists the exact behaviour for each firmware release.
Is it safe to keep the motor magnetized at standstill to eliminate the delay?
Yes, but with caveats. A magnetized standstill motor draws ~30 % of rated current continuously (more with P1310 boost), and the rotor relies on the integrated fan for cooling. If the standby duty cycle is long (e.g. > 30 % of the time), fit forced cooling, monitor r0037 (motor temperature model) and confirm the motor data sheet permits the duty cycle. For a hoist or conveyor with short standby periods and intermittent motion, the technique is standard. For a continuous-standby application, the technique is not recommended.