Sinumerik 840D NCU 573.2 Booting Error: PLC Watchdog Recovery

David Krause15 min read
Other TopicSiemensTroubleshooting
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Sinumerik 840D NCU 573.2 Booting Error: PLC Watchdog Recovery Procedure

The Sinumerik 840D system with NCU 573.2 occasionally refuses to complete the boot sequence, leaving the operator faceplate (OP) showing a frozen NCK identification and the seven-segment display on the NCU locked. The dominant root causes are loss of PLC communication (alarm 120202 "Waiting for connection to NCK"), PLC watchdog trips that force the PLC into STOP, and bus faults on the MPI/Profibus segment that disconnect the PLC from the NCK. This document consolidates the field-proven recovery procedure, bus diagnostics, and PLC diagnostic-buffer interpretation required to bring the NCU back online without losing the machine's PLC project.

1. Problem Profile and Failure Mode

An NCU 573.2 is the compact numerical control unit used in the Sinumerik 840D sl product line. It contains the NCK (numerical control kernel), the integrated PLC (CPU 317-2DP equivalent on later firmware), the CF card holding the PLC project and NC data, and the MPI/Profibus interfaces used to talk to the OP, the I/O slaves, and the drive bus (PROFIBUS-DP). When the NCK cannot establish the handshake with the PLC, the entire boot sequence stalls. Typical symptoms reported in the field are:

  • NCU seven-segment display stuck on 6 or 2 rather than progressing through the normal 1 → 2 → 3 → 5 → 6 handshake states.
  • PS LED permanently ON, PF LED permanently ON (PLC fault), or PS LED slow-flashing (PLC in STOP with pending error).
  • OP displays Alarm 120202 "Wait for connection to NCK" or "No communication to PLC".
  • PLC diagnostic buffer entry: "PLC watchdog error detected, PLC is in STOP mode".
  • Spontaneous reset of I/O stations, intermittent Profibus slave dropouts, or field wiring short circuits on 24 V sensor/actuator rails returning through the PLC inputs.
Pre-condition before any reset: confirm that an up-to-date PLC backup (S7 project archive, *.s7p or *.zip with the 840D toolchain) exists on a PG/PC. If the PLC project is lost, a recovery attempt that wipes the PLC memory will turn a recoverable fault into a total machine rebuild. The PLC project lives on the CF card in /siemens/sinumerik/ and is mirrored in the PLC's load memory; either source must be intact before continuing.

2. NCU 573.2 Hardware Reference and LED Map

The NCU 573.2 front panel exposes a fixed set of indicators that communicate boot progress and PLC state. The first step in any recovery is to read these correctly.

LED State Meaning
PS (Power/Status) OFF No 24 V supply or internal power failure
Steady ON NCU has completed boot, NCK and PLC are running
Slow flash (~0.5 Hz) NCU powered, PLC in STOP mode with diagnostic entry pending
PF (PLC Fault) OFF No PLC fault active
Steady ON PLC watchdog tripped, OB1 not being called, or PLC project invalid
SF / BF (Bus Fault) OFF Profibus link OK
Flashing Profibus physical layer error, slave dropouts, or termination missing
7-segment 1, 2, 3, 5, 6, 7 Boot stage counter — see Section 3

The rotary switch S4 on the NCU front face is the master mode selector. It is read by the NCK firmware at boot and overrides the project setting in mmc.ini for the current power cycle only.

S4 Position NCK Behavior PLC Behavior
0 Normal run from CF card PLC runs project from load memory, retains cold-restart data
1 Normal run, debug mode (PG visible on MPI) Same as 0
2 NCK startup with default data (clears NC machine data) PLC starts with cold restart, OB100 fires
3 NCK startup with default data + PLC general reset (MRES) PLC work memory, retentive flags, DBs all wiped; forces re-load from CF
4-7 Reserved / factory test modes — do not select on a production machine —
Critical: S4 is sampled only at power-up. Turning the switch while the NCU is live has no effect on the running firmware. Always power down, change S4, then power up.

3. NCU Boot Stages (Seven-Segment Decoder)

The 7-segment display is the most reliable indicator of where the boot has stalled. Capture the exact digit before cycling power, because it points directly to the failing sub-system.

Display Boot Stage Typical Cause of Stall
0 Bootloader active, hardware self-test Failed POST — replace NCU
1 BIOS/loader loading firmware from CF CF card missing, corrupt, or read error
2 Firmware loaded, NCK starting NC machine data invalid; clear with S4=2
3 NCK initializing communication layer PLC handshake failure — alarm 120202
4 Drive link init (Profibus-DP to SIMODRIVE/SINAMICS) Drive bus slave(s) missing or wrong address
5 HMI/OP link init (MPI/Profibus to operator panel) OP not powered, wrong MPI address, or bus termination
6 NC ready, waiting for PLC ready PLC still loading or stuck in STOP — see Section 4
7 PLC ready, NC ready, system handing off to cyclic operation Final handshake

A stall at display 6 with the PS LED slow-flashing and PF LED ON is the canonical signature of the NCU 573.2 PLC watchdog condition described in the field report.

4. Recovery Procedure: S4 General Reset to Recover from PLC Watchdog

The following procedure is the minimum-impact path to clear a PLC watchdog condition on an NCU 573.2. It wipes the PLC work memory and forces a clean reload of the PLC project from the CF card. NC machine data and tool/zero-point data are not erased. Always perform Steps 1-2 from Section 5 (preflight) before executing this sequence.

4.1 Confirm the PLC project is intact on the CF card

  1. Power down the NCU. Remove the CF card (slot on the front, label-up). Read it with a Siemens card reader or any industrial CF-to-SATA adapter in a PG running SIMATIC Manager / TIA Portal.
  2. Verify the following files are present and non-zero: /siemens/sinumerik/nck/dsfb.dir/, /siemens/sinumerik/plc/, and on later builds /card/user/sinumerik/.
  3. If the PLC folder is missing or unreadable, the recovery will fail and the NCU will return to display 3 indefinitely. In that case, restore the PLC project from a SIMATIC Manager backup (.s7p archive) via PG with MPI before continuing.

4.2 Power down, isolate, baseline

  1. Bring the machine to a safe state — axes stopped, drives inhibited, hydraulic/pneumatic dump valves closed per the machine builder's lockout procedure.
  2. Open the main disconnect and verify zero potential on the 24 V DC NCU supply with a calibrated DMM.
  3. Note S4 position. Standard production state is 0.

4.3 Bussed-cable isolation test (eliminate the field as the cause)

  1. With the NCU still powered down, disconnect every plug-in connector from the NCU front face: X1 (24 V), X2 (MPI/Profibus OP), X3 (Profibus-DP to drives), X4 (I/O bus), plus any encoder and Ethernet ports.
  2. Power the NCU from a clean 24 V supply only. Observe the 7-segment and LEDs.
  3. If the NCU completes boot to display 7 or runs normally with all external cables removed, the fault is on the field side (Profibus slave, I/O short, OP cable, or 24 V rail). Reconnect one segment at a time to isolate the offender.
  4. If the NCU still fails to boot in isolation, proceed with the S4 procedure — the PLC project itself is the suspect.

4.4 S4 General Reset Sequence

  1. NCU powered down. Set S4 to position 3.
  2. Apply 24 V power. The NCU will perform a general PLC reset. Expected LED pattern: PF LED ON briefly, then PS LED slow-flashing. The 7-segment will cycle through 1, 2, 3, 5, 6 and may pause at 6 while the PLC reloads.
  3. Wait until only the PS LED is ON (steady) — this confirms the PLC has finished loading its project from the CF card and entered RUN. Typical reload time: 30-90 seconds for a medium-sized project.
  4. Power the NCU down again. Set S4 back to 0 (or 1 if you want PG-visible debug).
  5. Apply 24 V power. Confirm normal boot: 7-segment reaches 7 and clears, OP shows the channel-ready screen with no active alarms.
If the S4=3 cycle does not clear PF: the CF card is not delivering a valid PLC project. Power down, remove the CF, restore the PLC project from a SIMATIC Manager backup using a PG connected to the NCU's MPI port (baud rate 187.5 kbit/s, default MPI address 2 for the NCU, address 0 for the PG). Then repeat the S4 sequence.

5. Preflight Checklist and Prerequisites

Before touching S4, complete the preflight below. Skipping it is the single most common cause of a "recovery" turning into a total PLC loss.

  1. PLC backup verified. A SIMATIC Manager project archive exists on a network share or USB, dated after the last commissioning change.
  2. NC archive available. A series-commissioning archive (.arc) created with Commissioning → Series commissioning → Create archive is on the OP or a USB stick. This preserves options, NC machine data, and tool data if a full NCK reset is later required.
  3. PG/PC with SIMATIC Manager or TIA Portal ready, with the MPI cable (6ES7901-0BF00-0AA0 or equivalent) and the correct PLC authorization/license.
  4. Machine safe state. All axes referenced or known to be unreferenced; hydraulic pressure relieved; tool changer in a safe index; spindle stopped.
  5. Bus topology map in hand. Profibus slave addresses, expected bus termination points, and cable routing. Without this map, a reconnection in Section 4.3 is guesswork.

6. Network and Bus Diagnostics (MPI / Profibus)

A PLC watchdog on the NCU 573.2 is often a symptom, not the root cause. The PLC goes into STOP because OB1 stopped being called, and OB1 stops being called because the Profibus-DP I/O scan failed or because a 24 V short on an input module pulled the PLC into a diagnostic interrupt loop. The two bus segments that must be validated are:

6.1 MPI bus (NCU ↔ OP ↔ PG)

The MPI port on the NCU is X2 (9-pin D-sub, female). Default addresses: NCU = 2, OP = 1, PG = 0. The bus must be terminated at both physical ends with 220 Ω, and the cable shield must be bonded to the connector shell at every node.

Symptom Likely Cause Action
OP shows "No connection to NCU" Open X2, broken cable, or NCU in early boot stage Verify 24 V at NCU, check X2 pin 1+2, swap cable
PG cannot "Accessible nodes" the NCU PG baud rate mismatch, address conflict, or terminator missing at one end Set PG to 187.5 kbit/s, address 0, set unique MPI address on NCU
Intermittent OP dropouts during machine motion Loose D-sub, missing strain relief, or VFD-induced EMI on the cable Re-tape shield, route cable clear of drive power cables, add ferrite

6.2 Profibus-DP bus (NCU ↔ I/O slaves ↔ drives)

NCU 573.2 has two Profibus ports on X3 and X4. The drive bus (typically X3) and the I/O bus (typically X4) must each be terminated exactly once at each physical end, with the terminator powered (9-pin D-sub with the switch in the ON position and the 5 V supply available — the NCU supplies this on its own connector). Slave addresses must be unique; a duplicate address forces the entire bus down.

Symptom Likely Cause Action
BF LED flashing on NCU One or more Profibus slaves missing Compare online slaves to HW Config; check slave power 24 V
BF LED steady ON Bus short or no termination Disconnect segments, measure A-B resistance: 220 Ω across A-B with both ends ON, infinite with both OFF except for terminator pairs
Single slave drops after warm-up Loose connector, oxidation, or insufficient tightening torque on the D-sub Re-tension screws to 0.4 Nm, replace connector if shielding ring is broken
All slaves drop simultaneously on a specific axis motion Inductive kick from a contactor or unfiltered VFD output coupled into the bus cable Re-route the bus cable, separate from motor power by at least 200 mm, add RC snubbers on the contactor coil
Shield bonding is critical. Profibus connectors must use the metallic shell, not the plastic shell. Shield continuity is measured end-to-end at the bonding bar; a floating shield is the same as no shield at 12 Mbit/s. For shielded Profibus cable, target shield resistance end-to-end under 1 Ω.

7. PLC Diagnostic Buffer Interpretation

Once the NCU is back online enough to accept a PG connection (or the PLC can be reached via MPI at 187.5 kbit/s), open the PLC online view in SIMATIC Manager and read the diagnostic buffer. This is the definitive record of why the watchdog fired.

Buffer Entry Meaning Next Action
"OB1 not called / time overflow" Cyclic time exceeded configured OB1 watchdog (default 100 ms for S7-300 in NCU 573.2) Increase OB1 time in HW Config → CPU properties → Cycle/Clock Memory, or profile the slow OB in the project
"I/O access error OB122" PLC read/wrote to a Profibus slave that was offline Validate slave addresses and bus health (Section 6.2)
"Programming error OB121" Indirect addressing, DB out of range, or BCD conversion error Inspect the cross-reference for the failing block; check the project against the archived backup for stray edits
"Short circuit on sensor supply" 24 V rail fault on an input module Identify the affected module via HW Config diagnostic interrupt, isolate the field wiring, replace the sensor
"Battery failure" / "Backup fault" PLC retentive data lost, time/date reset Replace the NCU buffer battery (typically a ½ AA lithium cell) and re-set the time on the OP

Save the diagnostic buffer to a plain-text file using the SIMATIC Manager "Save as text" button. That file is the single most valuable artifact for Siemens support escalation if the recovery does not hold on subsequent boot.

8. Verification Checklist After Recovery

Run the following before returning the machine to production. Any failure here indicates the underlying cause has not been resolved and the watchdog will return on the next shift.

  1. NCU 7-segment reaches 7 and clears. PS LED steady, PF LED off, BF LED off.
  2. OP shows channel-ready state with all axes "Available". No alarm 120202, 120201, 2001, or 380001 in the active alarm list.
  3. From the OP, navigate to Diagnostics → Bus diagnostics and confirm all expected Profibus slaves are present with green status, no red "station failure" entries, and error counters at 0.
  4. Reference all axes and run a controlled axis move of at least 10 mm in each direction from the OP handwheel, confirming actual position feedback tracks the commanded position within the loop tolerance.
  5. Toggle a representative sample of digital inputs (limit switches, door interlocks, lube OK) and confirm the corresponding PLC input indicator in SIMATIC Manager reflects the change within one OB1 cycle.
  6. Verify PLC time-of-day is correct; if not, the NCU buffer battery is exhausted and the next power-down will lose retentive flags.
  7. Trigger a controlled NCK reset (via OP Reset button) and confirm clean re-initialization, no PLC re-entering STOP.

9. Prevention and Hardening Recommendations

  • Schedule a periodic PLC backup. Use the HMI's Commissioning → Series commissioning function to create a dated archive on a network share after every PLC or NCK change. The archive should include the SIMATIC project, the NC archives, and the drive configuration files.
  • Replace the NCU buffer battery on a calendar basis. 5-year maximum service life, replace at 4 years in high-availability cells.
  • Audit Profibus terminations annually. Thermal cycling loosens D-sub screws; 0.4 Nm torque check takes ten minutes per segment.
  • Install RC snubbers on every 24 V DC contactor coil driving machine safety circuits. A single un-snubbed coil is sufficient to take down the Profibus segment when it de-energizes.
  • Keep the CF card write-protected in production. A failing CF card with random bit flips in the PLC project is the most insidious cause of intermittent watchdog faults that look like network issues.

10. Escalation Path

If the S4 general-reset procedure has been performed twice on a freshly restored PLC project from a known-good backup and the watchdog condition returns within one shift, the fault is environmental: a defective I/O module, a damaged Profibus cable, or a 24 V rail instability. The next steps are:

  1. Capture the PLC diagnostic buffer in text form at the moment of the next watchdog event.
  2. Capture the OP alarm log as a CSV via the Commissioning → Logs menu.
  3. Capture the NCU LED state, 7-segment display, and the Profibus slave status from Diagnostics → Bus diagnostics.
  4. Open a Siemens support request (Siemens Industry Online Support, support.industry.siemens.com) with all three artifacts attached and the NCU serial number, firmware version (read from Commissioning → NC → NCK version), and the CF card part number.

What does alarm 120202 "Wait for connection to NCK" mean on the Sinumerik 840D NCU 573.2?

Alarm 120202 indicates the NCK has finished booting but the PLC handshake has not completed within the timeout. It is almost always paired with a PLC watchdog entry and a stalled 7-segment at display 6. The fix is a PLC general reset via S4=3 followed by a clean reload of the PLC project from the CF card.

How do I clear a PLC watchdog on the NCU 573.2 without losing the PLC project?

Set S4 to position 3 with the NCU powered down, power up, wait until only the PS LED is ON, then power down and set S4 back to 0. The CF card must contain a valid PLC project at /siemens/sinumerik/plc/, or this procedure will wipe an empty PLC and the NCU will not boot past display 3.

Can I recover an NCU 573.2 PLC project over MPI from a PG with SIMATIC Manager?

Yes. Connect the PG to the NCU X2 port with an MPI cable at 187.5 kbit/s, set the PG MPI address to 0 and the NCU to 2, then use Accessible nodes to upload the PLC project. This is the only path if the CF card is unreadable, and it is the only path to restore the project if the S4=3 cycle has already cleared it.

Why does the PLC keep entering STOP after a successful S4 reset?

The PLC is being forced into STOP by an unhandled OB1 watchdog, a Profibus I/O access error (OB122), or a sensor-supply short circuit. Read the PLC diagnostic buffer in SIMATIC Manager to identify the specific OB that is firing, then resolve the underlying bus or field wiring fault; the S4 reset only clears the symptom.

What is the difference between S4 position 2 and S4 position 3 on the NCU 573.2?

Position 2 clears the NC machine data to factory defaults and cold-restarts the PLC (OB100 fires), but the PLC project remains in load memory. Position 3 adds a general reset (MRES) of the PLC work memory, forcing a full re-download of the project from the CF card. Use position 2 first if NCK data is suspect; use position 3 only when the PLC project itself is corrupt.

Back to blog