SITRANS F M MAG 5000: Editing Sensor Characteristics After Reset

David Krause10 min read
Process ControlSiemensTroubleshooting
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Overview

The SITRANS F M MAG 5000 is the standard 115/230 V AC or 24 V DC electromagnetic flow transmitter paired with Siemens MAG 1100, MAG 3100, MAG 5100 W, and MAG 6000 I Ex sensors. The transmitter stores the sensor's identity and calibration data in non-volatile memory so that replacement transmitters inherit the sensor curve without re-calibration. Executing the Set to Default command inside the Sensor Characteristics submenu restores the factory-shipped sensor fingerprint and wipes any field-entered Correction Factor and Excitation Frequency override.

This article explains which parameters may legally be edited, which are factory-locked, the access level (Operator / Supervisor / Service) required for each edit, and the exact menu navigation to recover from an unintended default reset. A separate troubleshooting matrix covers the common error states (read-only fields, "Sensor data invalid", HART write errors) that operators encounter after a default command.

Sensor Characteristics Menu Structure

The Sensor Characteristics menu (menu index 2.x in the standard MAG 5000/6000 firmware) contains the following parameters:

Parameter Default Source Editable Range / List Required Access Level
Sensor size (DN) Factory Fixed by connected sensor Read-only
Calibration factor Factory calibration certificate 0.0000 – 9.9999 (typically 0.8 – 1.2) Service only
Correction factor User field adjustment 0.850 – 2.000 Supervisor (Setup)
Excitation frequency Sensor-specific default 1.5625 Hz, 3.125 Hz, 6.25 Hz, 12.5 Hz, 25 Hz Supervisor (Setup)
Sensor excitation Factory ON / OFF (mains-powered only) Service only
Qmax (flow full scale) Sensor size dependent Editable in Setup Supervisor
Important: The Correction Factor and Excitation Frequency are the only Sensor Characteristics parameters that can be edited by the end user under the Supervisor (Setup) password. The Calibration Factor and Sensor Excitation toggle are gated to Service mode and should never be modified outside of a documented calibration procedure. The factory calibration certificate that ships with every MAG 1100/3100/5100W sensor lists the calibration factor — never overwrite this value without a wet calibration against a reference meter.

Access Levels and Default Passwords

The MAG 5000/6000 firmware implements three hierarchical access levels:

  1. Read-only — no password required; view measured values, totalizers, and current parameter set.
  2. Operator — password 1000 (default) or 2000 on some firmware branches; allows totalizer reset and zero-point adjust.
  3. Supervisor / Setup — password 2000 (default) or 3000; required for Qmax, Correction Factor, Excitation Frequency, output scaling, and most HART/Modbus configuration.
  4. Service — password 3142 (default Siemens service code); unlocks Calibration Factor, Sensor Excitation, and firmware-level diagnostics. This password is logged in the audit trail and should be reserved for factory-trained personnel.

To enter a password on the local keypad, hold the ▲ key for 2 seconds to enter the menu tree, navigate to Access, select the desired level, and enter the numeric code. If the wrong code is entered five times consecutively the keypad locks for 10 minutes. If the customer has changed the passwords, retrieve them from HART DD menu path Device / Security / Passwords via a Siemens PDM or SITRANS DTM host.

Why "Set to Default" Resets Sensor Characteristics

The Set to Default command (menu index 2.9 on most firmware revisions) executes three actions in sequence:

  1. Restores the factory calibration factor stored in the sensor's EEPROM (the value that was burned in at the Siemens flow lab with the actual wet calibration).
  2. Resets the Correction Factor to 1.000.
  3. Resets the Excitation Frequency to the sensor-size default (typically 6.25 Hz for DN ≤ 300, 3.125 Hz for DN ≥ 350).

This is expected behavior — the reset is by design so that a transmitter swapped onto a different sensor body starts from a known state. The factory calibration factor is recovered from the sensor EEPROM automatically on the next power cycle, so the meter's accuracy returns to the original calibration curve. What is lost is any field-applied correction factor (e.g., a 1.018 multiplier used to match a prover) and any custom excitation frequency selection made to suppress noise on a low-conductivity or slurry application.

Best practice: Before executing Set to Default, document the current values from menu path 2.1 (Calibration factor), 2.3 (Correction factor), and 2.4 (Excitation frequency). Export the parameter set via HART command 162 (Save Configuration) so a one-touch restore is possible.

Procedure: Restoring the Correction Factor

  1. Power the transmitter for at least 5 minutes so the sensor EEPROM has stabilized.
  2. Hold the ▲ key for 2 s → enter the menu.
  3. Navigate to Sensor Characteristics → Correction Factor (menu index 2.3).
  4. If the value is displayed but not editable, the transmitter is in Read-only mode. Press the ● (select) key and enter the Supervisor password when prompted.
  5. Use ▲ / ▼ to adjust the value. Acceptable range is 0.850 to 2.000 in steps of 0.001.
  6. Press ● to confirm. The display flashes briefly to indicate the value was written to EEPROM.
  7. Verify by navigating out and back into the menu — the new value must persist across a power cycle.

If the value still refuses to change after the Supervisor password is entered, the transmitter firmware has flagged the sensor as incompatible (wrong sensor size programmed for the connected body, or sensor EEPROM read error). See the troubleshooting matrix below.

Procedure: Restoring the Excitation Frequency

Unlike the correction factor, the excitation frequency is a discrete menu selection, not a numeric entry. Available values are fixed by the sensor size and the supply voltage:

Frequency Typical Application Sensor Size Constraint
25 Hz Low flow, maximum resolution DN ≤ 25
12.5 Hz Default for small process lines DN 40 – 150
6.25 Hz Factory default for most sizes DN 200 – 300
3.125 Hz High flow / large pipe / slurry DN 350 – 600
1.5625 Hz Maximum immunity to partially filled pipe DN ≥ 700
  1. From the Sensor Characteristics menu, select Excitation Frequency (menu index 2.4).
  2. Press ●; the currently active frequency is shown with a tick mark.
  3. Use ▲ / ▼ to step through the allowed list. Frequencies not valid for the connected sensor size are hidden automatically.
  4. Press ● to accept. The new excitation frequency takes effect within 2–4 excitation cycles (a few seconds at 25 Hz, up to 30 seconds at 1.5625 Hz).
  5. Verify on the HART host: variable Primary Variable (PV) should remain stable through the transition; a brief step in the analog output is normal while the coil drive reconfigures.

Why the Calibration Factor Is Editable Only in Service Mode

The Calibration Factor is a four-decimal multiplier (typically between 0.8 and 1.2) printed on the calibration certificate that ships with every MAG 1100, MAG 3100, and MAG 5100 W sensor. Siemens performs a wet calibration of each sensor at the factory against a reference gravimetric or master Coriolis rig. The calibration factor linearises the inherent offset of the sensor coils and electrode geometry; it is not a tuning parameter.

Changing the calibration factor manually causes the following:

  • The meter's stated accuracy of ±0.4 % of flow rate (or ±0.2 % with the MAG 6000 in higher-tier variants) is invalidated.
  • The traceable calibration record is broken — the device no longer matches the calibration certificate.
  • Custody transfer applications under OIML R49, MI-001, or NTEP lose their pattern approval if the calibration factor is edited after the seal is applied.
Service procedure only: If the calibration factor truly must be changed (sensor body replacement, custody transfer re-verification, or wet calibration against a new reference), perform the procedure under Service access with a documented wet calibration. The reference is the Siemens SITRANS F M MAG 5000/6000 Service Manual, available on the Siemens Industry Online Support portal.

Verification Checklist After Recovery

  1. Power-cycle the transmitter and confirm the entered Correction Factor and Excitation Frequency persist.
  2. Compare the live PV (L/m or m³/h as configured) against an independent reference at one flow point between 25 % and 75 % of Qmax. Acceptable deviation: within the published accuracy class for the sensor.
  3. Verify zero point: with the line full and flow at absolute zero, perform Auto Zero under Operator access (menu 3.1) and confirm the offset stores at < 1 mm/s velocity.
  4. Read back parameters via HART command 3 (Read Dynamic Variables) and HART command 13 (Read Tagged Dynamic Variables) to confirm the host DCS sees the corrected values.
  5. Export the final configuration via HART command 162 to the asset database for change-control records.

Troubleshooting Matrix

Symptom Likely Cause Corrective Action
Correction Factor field is greyed-out / read-only Logged in at Operator level only Re-enter with Supervisor password (default 2000)
Excitation Frequency list is empty Sensor EEPROM read error or wrong sensor size programmed Navigate to Sensor Size and re-confirm; if EEPROM CRC fails, swap sensor or reflash transmitter firmware
"Sensor data invalid" banner on display Set to Default wiped sensor size or the EEPROM checksum is corrupt Re-enter sensor size from the sensor nameplate; perform Set to Default once more to recover calibration factor from sensor EEPROM
HART write returns error 8 (device busy) Burst mode enabled or output in fixed current mode Disable burst mode, set loop to multi-drop or live current, retry
Calibration Factor shows but cannot be edited even with Service password Custody-transfer seal is intact and parameter is hardware-locked Break the seal only after gaining authority from the local Weights & Measures body; document the action
PV reads 0 after excitation frequency change Coil driver reconfiguring; signal settling Wait up to 30 s for stabilization; verify coil current with service diagnostic menu
Correction Factor accepts value but reverts on next power-up EEPROM write failure due to low backup capacitor Leave power applied for 60 s after write, then cycle; if it still reverts, the internal lithium backup cell is depleted — replace transmitter main board

Field-Commissioning Notes

When commissioning a replacement MAG 5000 transmitter against an existing sensor body:

  • Always perform a Set to Default on first install. The transmitter then auto-reads the sensor EEPROM and uploads the calibration factor.
  • Document the four key sensor parameters (size, calibration factor, correction factor, excitation frequency) in the commissioning sheet before powering down.
  • Apply the Correction Factor only if the customer's master meter reference disagrees with the SITRANS reading by a consistent ratio across multiple flow points. If the offset is non-linear, the sensor has a real issue (electrode coating, liner damage, partially filled pipe) and the Correction Factor will mask it.
  • When pairing with a MAG 6000 I Ex (Ex-de) sensor in hazardous areas, the excitation frequency is locked at 6.25 Hz by firmware and is not user-editable.

Related Documentation

Reference the official Siemens documentation set for the MAG 5000/6000 platform:

  • SITRANS F M MAG 5000/6000 Operating Instructions (Siemens manual A5E02387356)
  • SITRANS F M MAG 5000/6000 Service Manual (factory-only distribution)
  • Siemens Industry Online Support knowledge base: support.industry.siemens.com
  • SIMATIC PDM device description library for SITRANS F M (DD version 1.2.x and later)
  • SITRANS F M product catalogue FI 01 (printed matter E86060-K6201-A101-A4)

Why did my Correction Factor and Excitation Frequency reset after I ran Set to Default?

Set to Default is a deliberate factory-reset operation that wipes all field-entered overrides and returns the transmitter to its shipped state. The factory Calibration Factor is recovered automatically from the sensor's internal EEPROM, but the user-applied Correction Factor and any custom Excitation Frequency must be re-entered under Supervisor access (default password 2000) once the reset completes.

I am in Setup mode and the Correction Factor still won't change. What is wrong?

Setup mode covers most parameters but the Correction Factor is gated to Supervisor or higher. Hold the ▲ key, navigate to Access, enter the Supervisor password (factory default 2000), return to Sensor Characteristics → Correction Factor, and the field will accept writes. If the value still will not change, the sensor EEPROM read has failed and the transmitter has flagged the sensor as invalid.

Can I edit the Calibration Factor manually to correct a systematic error?

Not in normal operation. The Calibration Factor is a traceable factory value bound to the calibration certificate. Editing it requires Service access (default code 3142), a wet calibration against a reference master, and full change-control documentation. For field adjustments use the Correction Factor (range 0.850 to 2.000) which is intended for this purpose and does not invalidate the calibration certificate.

Why is the Excitation Frequency menu showing fewer options than the manual lists?

The MAG 5000 firmware hides excitation frequencies that are not valid for the connected sensor size. DN 15 sensors expose 25 Hz and 12.5 Hz only; DN 500 sensors expose 6.25, 3.125, and 1.5625 Hz. Confirm the Sensor Size parameter matches the nameplate on the sensor body. If the size is correct but the list is still short, the sensor EEPROM is unreadable.

Does changing the Excitation Frequency affect measurement accuracy?

Yes — lowering the excitation frequency increases the zero-point stability and reduces the influence of slurry noise, but it also slows the response time (T63 at 1.5625 Hz is approximately 4 seconds versus 0.25 seconds at 25 Hz). Select the lowest frequency that still meets the loop's response requirement for your process.

Back to blog