Sizing Power and DRIVE-CLiQ Cables for the Siemens 1PH4168

David Krause14 min read
SiemensTechnical ReferenceWiring & Electrical
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Overview

The Siemens 1PH4168-4QF26 is a member of the 1PH4 series of AC induction motors designed for machine-tool main-spindle and high-dynamic servo applications. When paired with a SINAMICS S120 Booksize Motor Module (for example, 6SL3121-1TE31-3AA3 at 132 A line current or 6SL3121-1TE24-5AA3 at 45 A) and a SINUMERIK 840D sl controller, the motor becomes a fully-digitised drive train with DRIVE-CLiQ as the encoder and data-bus backbone.

This reference describes how to select the two completely different cable categories required:

  1. Power cable (U2/V2/W2/PE, motor feeder); sizing depends on the actual phase current required by the application, not the motor's catalogue-rated current.
  2. Signal cable (DRIVE-CLiQ, dual-shielded twisted pair with green/orange conductors in the Siemens MOTION-CONNECT cable family). A Signal Module Interface (SMI) is only needed when retrofitting an existing non-DRIVE-CLiQ encoder; an IN22DQ-style encoder is already DRIVE-CLiQ native.

Because the original application is a low-load test bench that runs to maximum speed only momentarily, the cables are dimensioned against a derated current rating rather than the motor's full-load current. The drive itself can be undersized in current relative to the motor only when the operating point stays inside the S6/S2 envelope and the configuration in the SINUMERIK commissioning tools is set accordingly.

Motor and Drive Identification

1PH4168-4QF26 Article Code

The Siemens 1PH4 article-number convention follows a fixed pattern. The base type 1PH4168 identifies shaft height 160 and stack length 80. The suffixes describe the electrical and mechanical variant:

Article-digit position Code value Meaning
-4 4th mechanical revision / winding class Stator winding group for the listed current and speed combination
Q Shaft and bearing variant Plain shaft, locating/fixed-bearing arrangement suitable for high-speed test duty
F Cooling type Force-ventilated (separate fan unit)
2 Encoder code Indicates native DRIVE-CLiQ multi-turn absolute encoder family on the motor (IN22DQ class)
6 Connection / terminal box code Power connection via terminal box; signal connector M17 DRIVE-CLiQ type
Always cross-check the suffix decoding with the nameplate attached to the motor itself. The exact current, voltage and encoder article numbers printed on the rating plate override any order code extrapolation, especially for refurbished or warehouse stock units.

DRIVE-CLiQ Encoder IN22DQ D25

The encoder indicated on the operator's motor label is an IN22DQ equivalent (sometimes printed 1XP8001-1/A2C173846J family). It is:

  • A multi-turn absolute encoder (counts position across power-off transitions).
  • Wired through a 24-bit singleturn + 12-bit multiturn resolution over DRIVE-CLiQ.
  • Powered only through the DRIVE-CLiQ interface (24 V supplied by the Module); no separate encoder supply cable is needed.

Because the encoder is DRIVE-CLiQ-native and absolute, no Signal Module Interface (SMI) sits between the motor and the SINAMICS Motor Module. The SMI is only required when the original motor has an incremental encoder (such as 1XP8001 with sin/cos) or a third-party resolver, and an SMI20/SMI24 module is inserted for translation.

SINAMICS Booksize Motor Module Options

Article number Module type Rated output current I_r Peak current I_max Typical power at 400 V Suitable for
6SL3121-1TE24-5AA3 Single-axis Motor Module, booksize, internal air-cooled 45 A 90 A (typical) ~28 kW Drives that run at reduced load (for example the test bench in this case)
6SL3121-1TE31-3AA3 3-axis Motor Module, booksize, internal air-cooled 132 A (per axis, axis M3/M4/M5) 210 A ~75 kW per axis Motors operated close to catalogue ratings

Both can be controlled by SINUMERIK 840D sl over DRIVE-CLiQ when configured as the appropriate CompactFlash topology. In STARTER or the SINUMERIK commissioning tool (SVC), the active components are identified by the part of the article number printed on the label:

  1. Active Line Module (for example 6SL3130-6AE21-0AB1) supplies the DC link.
  2. The selected Motor Module is inserted on the DC link and exposes its DRIVE-CLiQ port(s) to the controller.
  3. The motor's IN22DQ encoder occupies the next DRIVE-CLiQ node.
  4. Any additional axis (LA / LB / LIC / ONC) ports required by I/O are populated with Terminal Modules (TMx) or Sensor Modules.

Why the Power Cable Can be Smaller for Test-Bench Duty

Conductor cross-section in AC motor feeders is governed by continuous current, not by maximum mechanical speed. The relevant sizing formula for a three-phase installation is:

I_n (A) = P_mech (W) / (sqrt(3) · V_LL · cosφ · eta)

Where:

  • P_mech = mechanical shaft power required at the operating point (W)
  • V_LL = line-to-line RMS voltage (V)
  • cosφ = power factor at that operating point (typical 0.7–0.85 for spindle motors at low load)
  • eta = motor efficiency (typical 0.90–0.95 for 1PH4 class)

If the test bench only spins the motor at no-load or low-load (no torque from the spindle), the actual RMS phase current is dramatically lower than the rated value printed on the rating plate. Two practical examples for a 1PH4168 motor on a 400 V three-phase supply:

Operating point Mechanical output P cosφ / η Calculated I_n
No-load, max speed ≈ 1.5 kW (windage + friction) 0.6 / 0.85 ~3.5 A
20% of rated mech. power ~15 kW (depends on variant) 0.78 / 0.92 ~30 A
Full rated load ~70–80 kW (variant dependent) 0.85 / 0.94 ~145 A
If the motor label is absent or unreadable and you can only depend on the 6SL3121-1TE24-5AA3 you have on hand (45 A I_r), confirm that the actual thermal current at your worst-case operating point never exceeds the 45 A line rating of the Module. Operating the module at its rated current continuously is acceptable; brief excursions above may trigger I²t pre-warning (F07800 family) but are recoverable.

Power Cable Selection

Cable Family

Siemens recommends the MOTION-CONNECT 800PLUS shielded feeder cable family (ordered under 6FX5008-1BBxx-Fxxx for fixed installation or 6FX8002-5xx cross-section series). Symmetric 3-core constructions with concentric shield + drain wire are mandatory for compliance with EMC directive and SINAMICS S120 emission specifications:

  • Minimum insulation class: PVC or better (XLPE for higher ambient).
  • Shield: tinned copper braid, optical coverage ≥ 85% (Siemens supplies ≥ 90%).
  • Outer jacket: 9YY-style PVC, oil-resistant 11Y for machine tools.
  • Symmetric, not 4-core; one PE conductor only.

For a fixed test-bench installation a 4-core cable is acceptable as an alternative, but symmetric 3-core is preferred because reduced common-mode current improves bearing-lifetime at high switching frequencies typical of SINAMICS drives. The same Siemens guidance applies: “Twisted or three-core cables with additional ground conductor should be used as motor feeder cables. The insulation should be removed from the ...” Siemens AC Induction Motors 1PH4 PDF.

Cross-Section Sizing

With the calculated operating current from the previous section, the copper cross-section can be downscaled relative to the catalogue-rated sizing. As a quick rules-of-thumb for a 600V-class PVC cable routed on open trays:

Continuous phase current Minimum copper cross-section Example Siemens cable
≤ 10 A 2.5 mm² 6FX5008-1BB21-...
10–24 A 4 mm² 6FX5008-1BB31-...
24–32 A 6 mm² 6FX5008-1BB41-...
32–44 A 10 mm² 6FX5008-1BB51-...
44–55 A 16 mm² 6FX5008-1BB61-...
55–76 A 25 mm² 6FX5008-1BB71-...
76–105 A 35 mm² 6FX5008-1BB81-...
105–132 A 50 mm² 6FX5008-1BB91-...

Per the Siemens 1PH4 manual, apply an additional 20% derating factor when:

  • cable is bundled with other live cores in a raceway
  • ambient > 40°C
  • free length in air > 20 m bundled

Voltage Class

For a 1PH4168 running on a 400 V/480 V three-phase SINAMICS supply, use 600 V-rated cable minimum, 1000 V-rated cable preferred (typical Siemens 1PH4 cable designation: 0.6/1 kV). At higher DC-link voltages (8 kV class on large drives) confirm the cable is rated for the inverter peak dU/dt if they are outside the typical cabinets.

Connector Layout

Each 1PH4 motor variant is delivered with a defined power and signal connector arrangement:

  • Power: terminal box with gland entries; ring lugs for U2/V2/W2/PE on M6/M8 studs. Torque per Siemens motor manual (commonly 4 Nm for power leads, 4–5 Nm for PE stud depending on stud size).
  • Signal: M17 DRIVE-CLiQ circular connector (6-pin) on the motor housing. Pinout is proprietary; do not wire DRIVE-CLiQ as crimp-style Ethernet.

Signal Cable Selection (DRIVE-CLiQ)

Two Cable Generations

Cable type Siemens part number family Connector Use for
DRIVE-CLiQ RJ45 6FX5002-2DC00-... (MOTION-CONNECT 500) RJ45 on both ends Backplane / cabinet interconnection of S120 components, NCU ↔ NX ↔ Line Module, typical lengths 0.5–30 m
DRIVE-CLiQ M17/M12 6FX5002-2CG00-... (MOTION-CONNECT 800PLUS) M17 (IP67) at motor end, RJ45 at cabinet Encoder / motor to Sensor Module or Motor Module, fixed installation, length up to 100 m
DRIVE-CLiQ M17/M17 6FX5002-2EG00-... M17 on both ends Longer runs for harsh environments when the cabinet end must be IP67
A “standard” RJ45 Ethernet patch cable will not reliably operate over DRIVE-CLiQ. The cable spec is electrically similar to Cat 5e but mechanically harder: green outer jacket, double shield (overall foil + braid), and rated for continuous flex/torsion in drag chains. Always use MOTION-CONNECT or a Siemens-approved equivalent.

Absolute Signal Support

  • Absolute-signal DRIVE-CLiQ: The cable carries the multi-turn position data (12-bit revolution counter). After the controller is switched on, the SINUMERIK reads the absolute position over DRIVE-CLiQ within < 1 second and can home the axes without a referencing run. Required when the motor uses an absolute encoder such as IN22DQ.
  • Non-absolute DRIVE-CLiQ: Sometimes referred to on machines where an incremental encoder (sin/cos or TTL) is fitted with a separate SMI20 / SMI24. In this case the SMI module is the DRIVE-CLiQ node and reports position to the controller but does not carry absolute revolution data unless the encoder itself is absolute.

The IN22DQ encoder used here is absolute, so the following conditions apply:

  1. Use a Siemens DRIVE-CLiQ cable with M17 plug at the motor end and RJ45 at the cabinet end. Standard 6FX5002-2CG00 series is correct.
  2. Connect the other end to the matching Sensor Module port on the SINAMICS Motor Module or directly to the X200-class DRIVE-CLiQ input of the Motor Module (no SMI needed).
  3. Configure the axis in STARTER / SVC so that the encoder appears as the EXTERNAL ENCODER for the position controller, not just as a speed feedback channel.

Pinout Reminder (Motor M17 Connector)

Pin Signal
1 +24 V (DRIVE-CLiQ supply)
2 GND (signal ground)
3 DATA +
4 DATA −
5 n.c.
6 n.c. / shield contact

Twisting and pair assignment are part of the Siemens cable specification — do not splice a longer run with off-the-shelf RJ45 patch cord, because the shield and pair attenuation will exceed the 100 m / 100 MHz budget.

Topology and Cable Run Lengths

The recommended topology for the test bench is a star from the NCU through the Line Module and on to the Motor Module. The DRIVE-CLiQ cable from the motor's M17 plug terminates into the X202 port of the Motor Module reserved for direct encoder without Sensor Module, or routed via an intermediate Sensor Module if the cabinet layout requires separation.

Run From To Suggested cable Max length
Power feeder Motor Module output busbars Motor terminal box U2/V2/W2/PE MOTION-CONNECT 800PLUS 4-conductor shielded Per cross-section: ~50 m at 70 mm²
Encoder Motor M17 encoder Motor Module X202 or SMI 6FX5002-2CG00-... 100 m
DRIVE-CLiQ backplane NCU X120 Line Module X400 6FX5002-2DC00-... 30 m
DRIVE-CLiQ backplane Line Module X401 Motor Module X200 6FX5002-2DC00-... 30 m
When the cabinet is grounded, the shield of the power cable must be applied 360° at both ends with the supplied EMC gland rings, and the DRIVE-CLiQ cable shield must be applied 360° at the M17 connector. Spring-cage clamp is acceptable for low-vibration environments; pull-apart style for service-friendly cabinets.

Optional: Using the Smaller 45 A Motor Module

The 6SL3121-1TE24-5AA3 can drive a 1PH4168 motor provided the actual thermal loading stays within the I²t envelope of the module. Activate the following parameters during commissioning:

  • p340 = i2t integration model enable (default) — leave at the default if available
  • p640 = Current limit (set to 45 A)
  • p1299 = Motor model enabling (configure the correct motor in p2900xx ID list)

The matching motor identification code for 1PH4168 is part of the SINUMERIK standard list (1PH416x-Fxxx entries). If a more recent SINUMERIK kernel releases an updated motor ID, use the updated value to ensure the field-weakening and thermal model match the actual stator winding.

Commissioning Steps

  1. Identify the motor rating plate and verify article code, rated current, rated voltage, encoder code (should be IN22DQ or compatible). Cross-check against the SINUMERIK motor-ID list before powering up.
  2. Configure the SINUMERIK in SVC with the project, insert the Line Module and Motor Module with the correct article numbers.
  3. Perform drive commissioning: connect via STARTER / SVC, identify the actual topology, run “automatic” commissioning with motor identification at standstill and rotating measurement.
  4. Connect power and encoder cables using the appropriate cross-section and DRIVE-CLiQ part numbers from the tables above. Both cable shields must be applied 360° on the EMC glands.
  5. Verify DRIVE-CLiQ network: a green LED on each DRIVE-CLiQ port means the node is recognised and the cable is good. Yellow LED or off indicates wiring error or cable mismatch.
  6. Test the absolute position: power off, move motor a fraction of a turn by hand, power back on. The SINUMERIK should report an absolute position that reflects the movement. If it returns to its previous reference position absolute position was lost — check IN22DQ cable and connector.
  7. Run-up profile: start at a low speed, ramp to maximum speed, monitor thermal model (Motor temperature via KTY/PTC). For test-bench duty with no workpiece a high-speed pass for ~30 s is usually sufficient.

Verification Checklist

Check Expected indication What it tells you
Module status LED on Line Module / Motor Module Green (RUN), off red DRIVE-CLiQ on its specific port
DRIVE-CLiQ LED on the motor connector Solid green 24 V supply present + data link up
STARTER / SVC online view Lists IN22DQ encoder at the right slot Motor model + encoder linked correctly
SinuTrain absolute-position test Position remains across power-cycle Absolute encoder chain is functional
DC link voltage at Motor Module ~600 V DC (Line Module nominal input 400 V AC) Power electronics ready
Phase current via trace Inside calculated value from Section 2 Cross-section sizing adequate
Cable surface temperature after first no-load run < 60°C (PVC) or < 70°C (XLPE) Cooling margin healthy

Fault Behaviour and Common Diagnostics

Alarm / fault Probable cause Action
F08501 — Sensor Module / encoder error DRIVE-CLiQ cable too long, missing shield, or wrong pairing Replace with 6FX5002-2Cxxx cable; verify shield drain contact
F31912 — Encoder initialization failed Absolute position lost, mismatched motor ID Re-run motor commissioning; verify IN22DQ is selected
F07800 — Drive I²t pre-warning Current above module rating during run-up Reduce demand or step to 6SL3121-1TE31-3AA3
F30024/F30027 — Motor thermistor tripped Load point too high, motor blocked, fan failure Verify forced-vent fan FOV presence and rotation
No DRIVE-CLiQ LED at motor connector Open / damaged cable or PS24V missing Check 24 V on Module side connector, replace cable

Notes

The values quoted for the two Motor Modules above are for the standard AA3 internal air-cooled variants. If liquid-cooled (AA4/PA4) variants are available in your cabinet, the same selection principles apply but the cabinet thermal calculation will differ.
The cable cross-section tables above assume 0.6/1 kV PVC-insulated copper conductors routed in accordance with IEC 60364-5-52 installation method B1 (cable on perforated tray). For other methods apply the corresponding derating factor from the IEC tables.

Can I drive a 1PH4168 with the smaller 45 A Motor Module (6SL3121-1TE24-5AA3) on a low-load test bench?

Yes, provided that the calculated RMS current at the worst-case load point stays ≤ 45 A and the SINUMERIK is configured with the correct motor ID plus a current limit of 45 A. Test-bench-only operation (no torque from the spindle, only windage and friction) typically draws < 5 A, well inside the module envelope.

Do I need an SMI (Sensor Module Interface) when the encoder is IN22DQ?

No. The IN22DQ encoder is a native DRIVE-CLiQ component, so it plugs directly into the Motor Module's X202 (or equivalent) DRIVE-CLiQ port using a 6FX5002-2CG00-... cable. SMI20/SMI24 modules are only required when a motor with a non-DRIVE-CLiQ encoder (resolver or sin/cos incremental) is retained.

What is the difference between a “standard” and a “non-standard” DRIVE-CLiQ cable?

In daily terminology this usually means the difference between an absolute-signal DRIVE-CLiQ cable (carries the multiturn position data of an IN22DQ-style encoder) and a cable wiring that simply feeds an incremental encoder through an SMI. Mechanically both look identical; the electrical parameter set is the same but the firmware in the Sensor Module handles the position-data transmission differently.

What minimum copper cross-section is acceptable for a 1PH4168 at no-load on a 400 V three-phase supply?

For a no-load spin-up with phase current under 5 A, a 4 mm² shielded cable of the MOTION-CONNECT 800PLUS family is acceptable. Above ~10 A continuous current step up to 6 mm² or 10 mm² per the table above. Always apply the derating factor for bundling, ambient temperature and routing method.

Do I have to run a separate 24 V supply cable for the IN22DQ encoder?

No. The DRIVE-CLiQ interface delivers the 24 V encoder supply on the same cable, and the encoder itself draws only a small fraction of the port's current budget. A second encoder cable is required only for resolver (8±1 V excitation) or for a separate SSI input.

Where can I download the official 1PH4 motor manual?

The Siemens AC Induction Motors 1PH4 PDF on the Siemens Industry Online Support portal covers cable selection, terminal assignments and connection diagrams for the entire 1PH4 family including the 1PH4168.

Back to blog