Sizing the Siemens CM AS-i Master ST 3RK7137-6SA00-0BC1 for AS-i Networks Above 4 A
The CM AS-i Master ST (Siemens part number 3RK7137-6SA00-0BC1) is the standard AS-i master module for the SIMATIC ET 200SP distributed I/O system. It integrates an AS-Interface v3 master into the backplane bus of an ET 200SP station and exposes the standard and safety slaves to the higher-level S7-1500 CPU through PROFINET. The module is rated for up to 62 AS-i slaves per master and a maximum of 8 masters per ET 200SP station, but the integrated power path that feeds the AS-i cable from the master is constrained to a hard 4 A limit through the busbar. When the cumulative slave current exceeds 4 A, the network must be split into multiple AS-i segments. This reference explains the electrical limits, the load calculation, the topology options, the TIA Portal configuration, and the verification procedure for a representative 42-slave Alfa Laval Think Top network totalling 4.4 A.
1. Problem Definition
The reference design consists of:
- 1 × S7-1500 CPU (e.g. CPU 1511-1 PN or CPU 1511F-1 PN for safety applications).
- 1 × ET 200SP IM 155-6 PN ST interface module (or HF variant for extended diagnostics).
- 1 × CM AS-i Master ST,
3RK7137-6SA00-0BC1. - 42 × Alfa Laval Think Top AS-i valve positioners, mix of:
- 35 units with 90 mA nominal current consumption.
- 7 units with 180 mA nominal current consumption.
- 1 × AS-i power supply, 30 V DC, 8 A (e.g.
3RX9501-0BA00or6EP1334-3BA10).
Total continuous AS-i current from the slaves:
I_total = (35 × 0.090 A) + (7 × 0.180 A) = 3.150 A + 1.260 A = 4.410 A
This is 0.41 A above the 4 A conductor limit on the master's power busbar. A direct connection to a single CM AS-i Master ST is therefore not permissible — the module's integrated current path cannot carry the load, and the derated thermal envelope (see Section 3) will trip long before the cable insulation fails. The slave set has to be re-distributed across two AS-i segments.
2. AS-i Power Architecture Fundamentals
AS-Interface (actuator-sensor interface) is a single-cable bus that combines 30 V DC power and digital I/O signalling on the same yellow profile cable. The relevant electrical and protocol parameters for v3 masters are:
| Parameter | Value | Source / Note |
|---|---|---|
| AS-i supply voltage | 29.5 V – 31.6 V DC (nominal 30 V) | IEC 62026-2 / AS-Interface specification |
| Maximum slaves per master (standard addressing) | 31 | AS-i spec v2.0 / v2.1 |
| Maximum slaves per master (extended addressing) | 62 | AS-i spec v3.0 — supported by 3RK7137-6SA00-0BC1
|
| AS-i cycle time, 31 slaves | 5 ms | AS-i spec |
| AS-i cycle time, 62 slaves | ~10 ms | AS-i spec — doubled with A/B addressing |
| Maximum cable length per segment | 100 m (no repeater) / 200 m (1 repeater) / 300 m (2 repeaters) | AS-i spec |
| Maximum current per AS-i segment (cable spec) | 8 A | AS-i yellow cable ampacity |
| Maximum current through CM AS-i Master ST power busbar | 4 A | Siemens manual, page 27 (3RK7137-6SA00-0BC1) |
3. CM AS-i Master ST 3RK7137-6SA00-0BC1 Electrical Limits
The CM AS-i Master ST is a single-width ET 200SP base unit (BU type A0) that carries the AS-i voltage from the AS-i power supply onto the yellow bus cable through the integrated power busbar. The terminal layout is:
-
1L— AS-i + (connected to power busbar P1) -
1N— AS-i − (connected to power busbar P2)
Conductor limits (per the manual page 27 cited in the project discussion):
| Parameter | Value |
|---|---|
Maximum continuous current through 1L / 1N
|
4 A |
| Maximum ambient, horizontal mounting, 4 A load | 55 °C |
| Maximum ambient, vertical mounting, 4 A load | 50 °C |
| Maximum ambient, ≤ 3 A load, horizontal | 60 °C (full ET 200SP spec) |
| Diagnostic LEDs | SF, BF (AS-i), 24 V, AS-i voltage OK |
| PROFINET interface to ET 200SP backplane | via IM 155-6 PN, no separate port on module |
| Supported AS-i profiles | M0–M4, M0e, M4e, M5, S-0.B, S-7.A, S-7.5, S-7.F (F-CM only) |
For a complete pinout and wiring diagram refer to the TIA Portal Fail-Safe Modules Manual Collection and the Siemens AS-i Master brochure (DFCP-B10157-00).
4. Load Calculation for the Think Top Network
Alfa Laval Think Top valve positioners (Think Top D30, Think Top Basic, Think Top V50, Think Top V70) report nominal current consumptions between 60 mA and 200 mA depending on variant, valve feedback, and output configuration. The project uses two populations:
| Slave group | Quantity | Current each | Subtotal |
|---|---|---|---|
| Think Top 90 mA variant | 35 | 0.090 A | 3.150 A |
| Think Top 180 mA variant | 7 | 0.180 A | 1.260 A |
| Total | 42 | — | 4.410 A |
| Reserve margin (20 %) | — | — | 0.882 A |
| Recommended supply | — | — | ≥ 5.3 A |
The 8 A AS-i power supply selected for this project is correctly sized for the slave current, but it cannot be routed through a single CM AS-i Master ST because the master's 4 A feed-through is the bottleneck.
5. Topology Options for >4 A Networks
Three architectural options exist for AS-i networks whose slave current exceeds the master's 4 A limit:
5.1 Option A — Two CM AS-i Master ST modules in one ET 200SP station (recommended)
Insert a second 3RK7137-6SA00-0BC1 module next to the first in the same ET 200SP station. Up to 8 CM AS-i Master ST modules can be plugged into a single station. Each master becomes the gateway for its own AS-i segment. The two segments are electrically isolated and can be fed from a single 8 A AS-i power supply through two independent feed terminals, or from two parallel 4 A supplies.
Advantages: clean separation, each segment ≤ 4 A, no extra hardware beyond a second base unit and a second master module, both masters are visible in the S7-1500 as a single PROFINET device with two AS-i sub-systems.
5.2 Option B — Two independent ET 200SP stations on the same PROFINET
Use two separate IM 155-6 PN stations, each with one CM AS-i Master ST. Both are PROFINET devices of the same S7-1500 CPU. This is functionally identical to Option A but spreads the wiring across two cabinets. Use it when physical segmentation is required (e.g. one cabinet per process cell).
5.3 Option C — One CM AS-i Master ST + an AS-i repeater
An AS-i repeater (e.g. 3RK1901-1MX01) extends the cable and re-isolates the segments, but it does not increase slave count or split the power source. Both sides of the repeater are powered from the same 30 V supply through the same master, so the 4 A limit on the master still applies to the entire combined segment. A repeater alone does not solve a >4 A load problem. It is the right tool to extend cable length beyond 100 m, not to scale current.
5.4 Recommended topology for the 4.4 A Think Top network
Use Option A: split the 42 slaves into two groups of 21. For an even load distribution, group the seven 180 mA units and 14 of the 90 mA units on Segment 1, and the remaining 21 × 90 mA units on Segment 2:
| Segment | 90 mA slaves | 180 mA slaves | Total current | Headroom vs 4 A |
|---|---|---|---|---|
| Segment 1 (Master #1) | 14 | 7 | 14 × 0.090 + 7 × 0.180 = 2.520 A | 1.480 A (37 %) |
| Segment 2 (Master #2) | 21 | 0 | 21 × 0.090 = 1.890 A | 2.110 A (53 %) |
| Total | 35 | 7 | 4.410 A | — |
Each segment is well below 4 A. Future expansion of up to ~7 additional 90 mA units per segment is possible before the 4 A limit is reached.
6. Topology Diagram (SVG)
7. AS-i Power Supply Sizing and Wiring
The AS-i power supply must be a data-decoupling supply (often called an AS-i power supply or AS-i power extender) — not a generic 30 V DC PSU. The data-decoupling choke integrates an inductor that blocks the AS-i telegram modulation from the supply input while passing the DC component. Suitable Siemens units:
| Siemens part | Output | Use |
|---|---|---|
| 3RX9501-0BA00 | 30 V / 8 A | Standalone AS-i power supply, 230 V AC in |
| 3RX9501-1BA00 | 30 V / 8 A | Standalone AS-i power supply, 400 V AC in |
| 3RX9502-0BA00 | 30 V / 4 A | Power supply with integrated data decoupling, 8 A peak |
| 6EP1334-3BA10 | 24 V / 10 A DC | Use only as DC source for an external AS-i decoupling module |
The 8 A supply can drive both segments from a single source. Wire it as follows:
- Run the 30 V output of the supply to a two-way AS-i power distribution terminal block.
- From the first output, run a yellow AS-i cable to the
1L/1Nterminals of Master #1, then continue the yellow cable out to the segment-1 slaves. - From the second output, run a separate yellow AS-i cable to the
1L/1Nterminals of Master #2 and out to the segment-2 slaves. - Earth the
FEterminal of the supply. Earth any shielded portions of the AS-i cable per IEC 62026-2.
1L outputs of two masters together. The two segments must remain electrically isolated, otherwise the slaves will see conflicting supply rails and the masters will flag ground faults. Each segment is a single AS-i network; the two masters are independent gateways into the S7-1500.8. TIA Portal Configuration
Two masters in one ET 200SP station are configured together. Procedure for TIA Portal V17 or later:
- Open the S7-1500 project. Drag a CPU 1511-1 PN (or 1511F-1 PN if safety slaves will be added later) into the project tree.
- Drag the ET 200SP station from the hardware catalog → "ET 200SP" → "Interface modules" → "PROFINET" → "IM 155-6 PN ST" (6ES7155-6AU00-0BN0) or "IM 155-6 PN HF" (6ES7155-6AU01-0BN0).
- Assign a PROFINET device name and IP to the IM. Connect it to the S7-1500 PROFINET interface.
- Open the ET 200SP device view. In slot 1, leave the IM 155-6. In slot 2, insert "AS-i Master" → "CM AS-i Master ST" →
3RK7137-6SA00-0BC1on a "BaseUnit BU15-P16+A0+2D" (6ES7193-6BP00-0BA0) or equivalent. - In slot 3, insert a second
3RK7137-6SA00-0BC1on its own base unit. TIA Portal automatically indexes them as AS-i master 1 and AS-i master 2 within the station. - In the master properties, set the AS-i mode to "Single master per ET 200SP" (default) and the addressing mode to "Extended (62 slaves)".
- Wire the
1L/1Nterminals of each base unit to the AS-i power supply. Do not parallel the terminals. - Compile and download the hardware configuration. Online, the "AS-i diagnostics" view in TIA Portal will show the slave count and live current per segment.
For projects that include F-CM AS-i Safety ST (e.g. 3RK7136-6SC00-0BC1), refer to the Siemens application note 109480137 for the F-CPU, F-shield, and PROFIsafe addressing. Up to 8 CM AS-i Master ST and F-CM AS-i Safety ST combined can populate a single station — the manual explicitly states "up to 8 CM AS-i Master ST modules" per station.
9. Commissioning and Verification
After wiring and download, verify the network as follows:
- Power up the ET 200SP and the AS-i supply. The "AS-i voltage OK" LED on each master must be solid green.
- In TIA Portal, open "Online & diagnostics" → "AS-i diagnostics". Each master should report "Configuration = Actual" with 21 slaves present.
- Use the AS-i master "Read current" diagnostic (PROFINET record data). Confirm Segment 1 reads ~2.52 A and Segment 2 reads ~1.89 A at idle (valves de-energised). If the readings are higher than the calculated values by more than 10 %, look for a wiring short or a slave drawing excessive current.
- Cycle each Think Top valve. Watch for AS-i ground-fault alarms. The CM AS-i Master ST detects ground faults on the AS-i cable and disconnects the affected segment to protect the slaves.
- Force an AS-i reset on each master and verify the slaves re-address cleanly. This validates that the segment has the right number of free addresses.
10. Fault and Diagnostic Matrix
| Symptom | Probable cause | Action |
|---|---|---|
| "SF" LED on CM AS-i Master ST, segment offline | AS-i ground fault, slave current > 4 A, or short on yellow cable | Measure total current with clamp meter. Disconnect slaves in halves until segment returns. |
| Intermittent slave dropout on one segment | Voltage drop on long cable run | Measure AS-i voltage at the far slave; if < 26.5 V, shorten cable, add a repeater, or add a power supply mid-segment. |
| AS-i voltage OK LED off, all slaves dark | AS-i power supply tripped or 1L/1N reversed | Check supply, polarity at the base unit, and the data-decoupling choke continuity. |
| Both masters report identical slave addresses | Segment cabling accidentally bridged | Disconnect the yellow cable between the two segments. Verify electrical isolation with a multimeter (infinite resistance between segment 1 1L and segment 2 1L). |
| Master reports slave count > 31 but cycle time > 10 ms | Normal with extended (A/B) addressing | No action — expected behaviour. The PROFINET update to the S7-1500 runs at the configured IO cycle, typically 1–4 ms. |
| Cabinet temperature alarm, master resets randomly | Operating at 4 A in a >55 °C ambient | Reduce load to ≤3 A (rebalance segments), improve cabinet cooling, or derate to the 50 °C vertical-mounting limit. |
11. Field-Proven Caveats
- Some Alfa Laval Think Top variants draw an inrush current well above the steady-state 90 mA / 180 mA during valve actuation. If the supply cannot sustain the inrush, the AS-i voltage will dip and slaves will reset. Use a supply with at least 50 % inrush headroom or stage the valve actuations.
- The 4 A limit is a continuous rating. Pulsed loads (solenoid actuation, LED indicators on Think Top) can briefly exceed 4 A without tripping the master's thermal protection, but the average must stay below 4 A.
- Never route both segments through the same AS-i power supply terminal block. The two segments need independent feed points to keep the masters isolated.
- When extending the cable beyond 100 m, use an AS-i repeater (e.g.
3RK1901-1MX01) on the same segment — do not put a repeater between two masters. A repeater passes the same AS-i telegram and same 30 V rail; it does not create a new segment. - For the safety variant, the F-CM AS-i Safety ST (
3RK7136-6SC00-0BC1) replaces the standard master on the slot and shares the same wiring. Safety slaves can coexist with standard slaves on the same segment.
12. Summary
The CM AS-i Master ST 3RK7137-6SA00-0BC1 supports up to 62 AS-i slaves but only 4 A through its integrated power busbar. A 42-slave Think Top network at 4.41 A must be split across two masters. The 8 A AS-i power supply is sufficient for the total load, provided it feeds the two segments through independent output terminals. Use TIA Portal to assign the two masters to a single ET 200SP station, verify the load in the online diagnostic view, and observe the 55 °C / 50 °C derating when each master is at its 4 A continuous limit.
Can a single CM AS-i Master ST 3RK7137-6SA00-0BC1 feed 4.4 A of Think Top slaves?
No. The module's power busbar is rated at 4 A continuous (manual page 27). At 4 A the ambient must also be limited to 55 °C (horizontal) or 50 °C (vertical). To carry 4.4 A the network must be split across two CM AS-i Master ST modules in the same ET 200SP station, each feeding its own segment.
How many CM AS-i Master ST modules can one ET 200SP station hold?
Up to 8 CM AS-i Master ST modules (or F-CM AS-i Safety ST variants) per station, with up to 62 slaves per master. This allows up to 496 slaves in a single PROFINET device.
Will an AS-i repeater solve the >4 A current problem?
No. A repeater re-isolates the cable and extends the bus length, but both sides of the repeater share the same 30 V supply from the same master. The 4 A limit is on the master's feed, not on the cable. Use two masters, not a repeater, to scale current.
What AS-i power supply part should I use for an 8 A total load?
Use a Siemens AS-i data-decoupling supply with at least the sum of the slave currents plus 20 % margin. The 3RX9501-0BA00 (30 V / 8 A) is the standard match. Split its output to two independent feed terminals, one per master, and never parallel the master power inputs.
How do I read the live AS-i current in TIA Portal?
Open the ET 200SP device online, select the CM AS-i Master ST, then "Online & diagnostics" → "AS-i diagnostics". The "AS-i current" field shows the live current on that master's segment. Compare it to the calculated value; deviations above 10 % usually indicate a wiring fault or a slave drawing excess current.