STO vs OFF2 on SINAMICS G120: Safety Integrated Explained

David Krause15 min read
SiemensTechnical ReferenceVFD / Drives
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

STO vs OFF2 on SINAMICS G120: Safety Integrated Explained

Overview

The SINAMICS G120 modular drive family includes the CU240E-2 F Control Unit, a fail-safe variant that supports the Safety Integrated Extended Functions defined in IEC 61800-5-2:2016. Two of the most frequently confused stop behaviors on this platform are the standard OFF2 command and the Safe Torque Off (STO) function. Both ultimately remove torque from the motor, both can be wired to a digital input, and both can be triggered by a normally-closed emergency-stop contact. They are not equivalent.

OFF2 is a functional stop command inherited from the legacy drive command set; it cancels the IGBT gate pulses and lets the motor coast. STO is a certified, two-channel, fault-tolerant safety function that performs the same physical action through two independent shutdown paths and a self-diagnostic mechanism that detects when one path has failed. In the happy path the motor behavior is identical. The difference becomes visible the moment a single fault occurs: a wire shorts to 24 V, a contact welds closed, a transistor fails short, or an external source backfeeds into a broken cable. With OFF2 the drive may continue to produce torque in that faulted state. With STO the diagnostic coverage forces a safe state and the operator is notified.

This distinction is not paperwork. It is the reason a stop command wired to DI0 with a single wire from an E-stop button cannot meet Category 3 / PL d per ISO 13849-1:2015 or SIL 2 per IEC 61508:2010, while the same E-stop button wired with two channels to F-DI0 and F-DI1 of a CU240E-2 F, configured as STO, can reach SIL 3 / PL e / Category 4.

Stop Function Taxonomy on SINAMICS G120

SINAMICS G120 separates its stop and safety behaviors into three classes. The first three rows are functional commands defined in the generic drive standard IEC 61800-2. They are part of the PROFIdrive command set and are not subject to functional-safety certification. The remaining rows are Safety Integrated functions defined in IEC 61800-5-2:2016 and are subject to the full functional-safety lifecycle.

Class Function Standard SIL / PL Implementation Drive Reaction
Standard stop OFF1 IEC 61800-2 None Single-channel Ramp-down on ramp, then pulse inhibit
Standard stop OFF2 IEC 61800-2 None Single-channel Immediate pulse inhibit, coast to stop
Standard stop OFF3 IEC 61800-2 None Single-channel Fast ramp on OFF3 ramp, then pulse inhibit
Safety function STO IEC 61800-5-2 Up to SIL 3 / PL e / Cat 4 Two-channel via F-DI Pulse inhibit via two independent paths
Safety function SS1 IEC 61800-5-2 Up to SIL 3 / PL e / Cat 4 Two-channel + timer Monitored ramp, then STO
Safety function SS2 IEC 61800-5-2 Up to SIL 3 / PL e / Cat 4 Two-channel + ramp Monitored ramp, then SOS
Safety function SLS IEC 61800-5-2 Up to SIL 3 / PL e / Cat 4 Two-channel Safe speed limit
Safety function SDI IEC 61800-5-2 Up to SIL 3 / PL e / Cat 4 Two-channel Safe direction
Safety function SOS IEC 61800-5-2 Up to SIL 3 / PL e / Cat 4 Two-channel Safe standstill (position window)
Safety function SSM IEC 61800-5-2 Up to SIL 3 / PL e / Cat 4 Two-channel Safe speed feedback to logic

STO Architecture: How Two-Channel Safety Works

STO on the CU240E-2 F is implemented through two independent shutdown paths. The two F-DI signals are sampled by separate fail-safe input processors, debounced, and compared for discrepancy. The two gate-driver enable lines are ANDed with the diagnostic result before reaching the IGBT module.

F-DI0 Channel 1 F-DI1 Channel 2 Failsafe Processor 1 p9650/p9651 Failsafe Processor 2 discrepancy + filter IGBT Gate Driver AND (dual path) STO two-channel shutdown architecture on CU240E-2 F

Both processors must agree that the safety request is active before the pulses are inhibited. The agreement check is the discrepancy time, and the diagnostic check that one channel has not stuck is performed by cross-circuit detection and by the dynamic forced checking procedure.

Parameter Meaning Typical Default
p9601 SI enable, functions (basic / extended) 1 (extended)
p9650 SI STO/SS1 discrepancy time 100 ms
p9651 SI STO/SS1 filter (debounce) 1 ms
p9652 SI STO enable (basic / extended) 1 (extended)
p9660 SI forced checking procedure timer 8 h
p10002 SI F-DI switch assignment Per wiring
r9771 SI common diagnostics (read-only, bit field)
Note: Parameter numbers in this table are valid for the CU240E-2 F in the firmware versions documented in the SINAMICS G120 Safety Integrated Function Manual. Always cross-check against the parameter list for your specific firmware version on the Siemens Industry Online Support portal at support.industry.siemens.com.

OFF2 Architecture: Standard Single-Channel Stop

OFF2 is the legacy drive-level stop. It is invoked by either a control word bit (STW1.1 in PROFIdrive) from the PLC or a standard digital input configured via p0701..p0705 on the CU240E-2. The reaction is immediate pulse inhibit on the single signal path. There is no second channel, no discrepancy monitoring, no cross-circuit detection, and no test requirement.

p0701 value Function on DI0
0 No function
1 ON / OFF1
2 OFF2 (coast)
3 OFF3 (fast stop)
... ...

If the wiring from the E-stop button to DI0 breaks, or the contact welds closed, OFF2 may not be invoked. The drive will not detect the fault. In a single-fault scenario, OFF2 cannot meet any functional-safety requirement.

Two-Channel vs One-Channel Wiring

The core architectural difference is redundancy. STO requires two independent signal paths from the safety sensor (E-stop, light curtain, guard-door interlock) to the two fail-safe digital inputs of the drive. The two wires are run separately; they are not shorted together at the sensor. Each is monitored, and the drive expects to see the same state on both at all times.

If one wire shorts to 24 V (active signal level), the second wire must still carry the de-energize state for the drive to enter STO. If one wire breaks, the second wire must still drive the safety state. The drive periodically executes a dynamic test where it briefly toggles one channel to verify the other responds. This is the forced checking procedure described in IEC 61800-5-2:2016 Section 4.2.2.2.

This is fundamentally different from a single-wire design where the drive has no way of knowing whether the wire is broken, shorted, or whether the contact in the E-stop has welded. The single-wire design provides a single point of failure; the two-wire design provides fault tolerance with diagnostic coverage.

Cross-Circuit and Discrepancy Detection

Two specific failure modes are targeted by the two-channel architecture:

  1. Cross-circuit. A short between the two signal wires. If a wire breaks and shorts to the other wire, both signals show the same level permanently. The drive detects the cross-circuit during the test stop when one channel is forced and the other is expected to follow.
  2. Discrepancy. One channel changes state, the other does not follow within p9650. This is caused by a welded contact, a broken wire, a failed input stage, or a backfeed from an external source. The drive declares fault F01611 or F01612, latches the safety state, and forces torque removal.

In both cases, the safety function remains active (torque remains removed) and the drive refuses to restart without an explicit safety acknowledgment. The operator is forced to investigate the cause.

Standards Mapping: SIL, PL, Category

The functional-safety properties of STO on the CU240E-2 F are documented in the Siemens Safety Integrated Function Manual, which is part of the SINAMICS G120 documentation set. The relevant standards are:

  • IEC 61800-5-2:2016 — defines the STO function, its behavior, and required test intervals.
  • IEC 61508:2010 — functional safety of E/E/PE safety-related systems. The PFHd (probability of dangerous failure per hour) for the CU240E-2 F STO function is published in the safety manual.
  • ISO 13849-1:2015 — Performance Level (PL a–e) and Category (1–4) framework. The CU240E-2 F with STO can achieve PL e / Category 4 when wired with two channels and a properly qualified safety sensor.
Drive Function Standard Achievable Level Mission Time
STO basic IEC 61800-5-2 PL d / Cat 3 / SIL 2 20 years
STO extended IEC 61800-5-2 PL e / Cat 4 / SIL 3 20 years

The exact PFHd value must be confirmed from the safety manual shipped with the firmware version in use. The achievable level depends on the connected sensor architecture and the wiring method (single-channel vs two-channel with or without cross-fault detection).

CU240E-2 F Parameter Configuration

  1. Enable Safety Integrated Extended Functions: p9601 = 1.
  2. Confirm the F-DI assignment. F-DI0..F-DI3 on the CU240E-2 F are physically separate terminals from standard DI0..DI5; verify with the terminal diagram in the operating instructions.
  3. Set the discrepancy time p9650. Siemens recommends 100 ms for typical E-stop applications. The value must exceed the worst-case contact bounce plus propagation through any intermediate safety relay.
  4. Set the filter time p9651 (typical 1 ms) to debounce the input.
  5. Set p9660 (forced checking procedure timer) to 8 h default. After 8 h without a dynamic test of the STO path, the drive requests a test stop.
  6. Assign the F-DIs to the safety group: p10002[0] = 0 (F-DI0 to group 1), p10002[1] = 1 (F-DI1 to group 1).
  7. Power-cycle the drive to activate the safety parameters. The drive will report a safety-parameters-changed warning until the cycle is complete.
; Commissioning example: STO extended, two-channel, 8 h test interval
p9601 = 1          ; SI enable extended functions
p9650 = 100        ; SI STO/SS1 discrepancy time, ms
p9651 = 1          ; SI STO/SS1 filter, ms
p9652 = 1          ; SI STO enable (extended)
p9660 = 8          ; SI forced checking procedure timer, h
p10002[0] = 0      ; F-DI0 assigned to STO group 1
p10002[1] = 1      ; F-DI1 assigned to STO group 1
; After write: power cycle required, then run acceptance test

Periodic Test / Forced Checking Procedure

IEC 61800-5-2:2016 Section 6.2 requires that STO be exercised periodically so that dangerous, undetected faults are exposed. The CU240E-2 F implements this as the forced checking procedure (in IEC terminology) or test stop. The drive expects the operator to:

  1. Trigger the safety function (operate the E-stop or open the safety loop).
  2. Verify the drive removes torque.
  3. Release the safety function.
  4. Verify the drive re-enables the pulses only after a deliberate restart acknowledgment.

If the operator does not trigger the safety function within p9660, the drive requests the test stop via alarm A01695. If the test is still not performed, the drive escalates to fault F01695 and latches the safe state. The latched state can only be cleared after a successful test stop and a safety acknowledgment.

The interval is application-dependent. The default 8 h is suitable for typical industrial machinery. For low-demand applications the interval can be extended up to 8760 h (one year) per IEC 61800-5-2:2016 Table D.1, but only if a manual test is performed and documented at least once per year.

Fault Reactions and Acknowledgment

A safety fault is not the same as a standard drive fault. Standard drive faults (F-class faults in the 0xxx range) are cleared with a normal fault acknowledgment. Safety faults (F016xx range) require:

  1. The cause to be removed.
  2. A safety acknowledgment via one of: p3981 = 0 at the drive; a digital input mapped via p10006 (SI STO acknowledgment); the PROFIsafe control word bit S_STW1.7 on a PROFINET-connected F-CPU; or the Startdrive / STARTER commissioning tool during initial acceptance.

A standard drive fault clear (p3981 = 1 or a PLC fault reset) will not clear a safety fault. The drive remains in the safe state and the safety stack remains latched.

Commissioning Checklist

Step Action Verified
1 Confirm CU240E-2 F variant (printed on the control unit label)
2 Read the Safety Integrated Function Manual for the firmware version installed
3 Wire the E-stop with two NO contacts routed separately to F-DI0 and F-DI1
4 Verify the sensor is rated for the required PL / SIL per ISO 13849-1 or IEC 61508
5 Set p9601, p9650, p9651, p9660 per application
6 Activate safety parameters (requires power cycle on G120)
7 Run Startdrive / STARTER acceptance test wizard and document results
8 Mark the safety function in the schematic with the achieved PL / SIL / Cat
9 Sign the acceptance protocol and file in the machine technical file
10 Schedule the periodic test in the maintenance plan

Verification and Acceptance Test

The acceptance test is mandatory. Per IEC 61800-5-2:2016 and ISO 13849-1:2015, a safety function cannot be put into service without a documented acceptance test. The test must verify, at minimum:

  1. The safety sensor triggers the safety function on demand.
  2. The drive removes torque within the required reaction time (typ. < 5 ms for STO on the CU240E-2 F).
  3. The drive remains in the safe state while the safety request is active.
  4. The drive does not auto-restart; a deliberate restart acknowledgment is required.
  5. A single fault in the wiring (open circuit, short circuit, cross-circuit) is detected and forces the safe state.
  6. The discrepancy fault is generated when one channel is forced to a different state than the other.

The acceptance protocol must include the achieved PFHd, PL, SIL, Category, mission time, and the date of the next scheduled periodic test.

Diagnostic Output

The drive exposes a number of read-only parameters useful for diagnostics:

  • r9771 — SI common diagnostics (bit field; bit 0 = STO active).
  • r9780 — SI status word.
  • r9794 — SI cross-check status.
  • r10051 — SI F-DI diagnostics (bit per F-DI).

A supervisory PLC should read r9771.0 over cyclic PROFIdrive and verify it matches the commanded state. Mismatch indicates either a sensor fault, a wiring fault, or a safety stack fault.

Interaction with PROFIsafe

When the SINAMICS G120 is connected to a SIMATIC F-CPU over PROFINET with PROFIsafe, the F-DI configuration may be replaced by PROFIsafe control bits. STO is then commanded via S_STW1.0 in the PROFIsafe telegram. The two-channel property is maintained by the PROFIsafe protocol itself, which uses a 24-bit CRC for each telegram. The acceptance test must cover the PROFIsafe bus and the upstream sensor wiring separately.

Common Misconceptions

Misconception Reality
OFF2 is identical to STO, both remove torque. OFF2 is single-channel with no diagnostic coverage. STO is two-channel with cross-fault and discrepancy detection.
A single-wire connection from an E-stop to a digital input is safe. A single wire has no fault tolerance. A break or short cannot be detected by the drive.
STO can be implemented on a standard CU240E-2 (non-F) by setting a parameter. No. The F variant has the additional fail-safe input processors, gate-driver interlocks, and safety parameter stack.
STO is enough to make the motor safe. STO removes torque but does not provide electrical isolation. A separate disconnect means (contactor, breaker) is required for maintenance per IEC 60204-1.
Once enabled, STO never needs attention. The forced checking procedure must be executed at least once per p9660 hours, or the drive will alarm and then fault.
PROFIsafe replaces the F-DI wiring entirely. PROFIsafe replaces the wiring only between the F-CPU and the drive. The two-channel sensor wiring is still required upstream of the F-CPU to achieve Cat 4 / PL e.

Quick-Reference Decision Tree

If the application needs ... Then use ... Drive parameter
Functional E-stop, no safety rating OFF3 (fast ramp) or OFF2 (coast) p0701 = 2 or 3
Safety stop, PL d / Cat 3 / SIL 2 STO basic with two-channel wiring p9601 = 1, p9652 = 0
Safety stop, PL e / Cat 4 / SIL 3 STO extended with two-channel wiring and qualified sensor p9601 = 1, p9652 = 1
Safety stop with controlled ramp SS1 with two-channel wiring p9601 = 1, SS1 time p9653
Safe speed limit SLS p9601 = 1, SLS config p9501 / p9503
Safe direction SDI p9601 = 1, SDI config p9501 / p9505

Field Notes and Practical Cautions

Sensor qualification. A SIL 3 / PL e STO function on the drive does not automatically make the complete safety function SIL 3. The sensor, the wiring, and any intermediate safety relay must each be qualified for the target level. The PFHd of the complete loop is the sum of the individual PFHds.
Discrepancy time tuning. Setting p9650 too low causes nuisance faults on slow contactors. Setting p9650 too high delays the safety reaction. Validate with the actual contactor bounce time measured at the installation.
Restart acknowledgment. STO alone does not restart the drive when the safety request is removed. A separate restart command (PLC start bit, digital input mapped to ON/OFF1, or a PROFIsafe control bit) is required. This is intentional and prevents automatic re-energization after an E-stop release.

Is OFF2 a safety function on the SINAMICS G120?

No. OFF2 is a functional stop command defined in IEC 61800-2. It removes the IGBT gate pulses on a single signal path and has no diagnostic coverage, no cross-fault detection, and no test requirement. OFF2 cannot meet any SIL or PL rating on its own.

Why does STO require two wires when the visible action is the same as OFF2?

The two wires provide fault tolerance. If one wire breaks, shorts, or carries a welded contact, the second wire still commands the safety state. The drive's discrepancy monitor (p9650) and the forced checking procedure (p9660) detect when one channel has failed and force the safe state. A single wire has no such redundancy.

Can a non-F CU240E-2 perform STO by changing a parameter?

No. The non-F variant does not contain the fail-safe input processors, the safety gate-driver interlocks, or the safety parameter stack required for STO. Only a CU240E-2 F (or other F-variant) control unit can execute STO. Setting p9601 on a non-F unit will not produce a safety function.

How often must the forced checking procedure be performed?

The default on the CU240E-2 F is 8 hours (p9660 = 8). The drive alarms A01695 when the interval is about to expire and faults F01695 if the test is not performed. The interval can be extended up to 8760 h (one year) per IEC 61800-5-2:2016, but only if a manual test is documented at least once per year.

Does STO provide electrical isolation for maintenance work?

No. STO removes gate pulses from the IGBTs; the DC bus and the line side of the drive remain energized. A separate means of isolation (main contactor, disconnect switch, or withdrawable circuit breaker) is required for maintenance work, per IEC 60204-1 Section 5.4.

What is the difference between STO basic and STO extended on the CU240E-2 F?

STO basic is the default single-function de-energize with limited diagnostics. STO extended adds additional diagnostic coverage, including a tighter acceptance threshold and forced test tracking, and is required to reach PL e / Cat 4 / SIL 3. The selection is made with p9652 (0 = basic, 1 = extended on the F variant). Wiring, sensor, and acceptance test requirements are stricter for extended STO.

Can PROFIsafe replace the two-channel F-DI wiring?

No. PROFIsafe replaces the two-channel wiring only between the F-CPU and the drive. The two-channel property upstream of the F-CPU (sensor, contactors, interlock switches) must still be implemented to achieve Cat 4 / PL e. The PROFIsafe telegram itself is a two-channel protocol by design, using a 24-bit CRC per frame.

Back to blog