Application Overview: Eight-Motor Yarn Winding Machine
The reference machine is a yarn winding station built around eight (8) single-direction 0.25 kW motors. Originally each spindle was driven by an individual motor started direct-on-line (DOL) from a bank of electromechanical relays. A retrofit is now required: the same eight motors must continue to share a common speed reference (same RPM, same frequency, same acceleration ramp), but the start/stop authority for each spindle must move to a PLC driven by eight independent yarn-break sensors. A single variable-frequency drive (VFD) sitting upstream of eight output contactors is the lowest-cost mechanical topology, but it introduces a switching problem that does not exist with a pure relay panel: opening an output contactor while the VFD is actively producing PWM voltage destroys the drive.
Two facts from the original field experience must be carried into the design:
- The motors were later re-identified as 3-phase 0.25 kW induction machines (not single phase). The VFD therefore runs all eight stator windings from a 3-phase output bus.
- A similar machine has been running for years on a Yaskawa VFD with output contactors that open and close under load, with no recorded drive trips. The drive has been oversized for the application so that it never "notices" the inrush of the largest motor it must pick up next.
Why a Single VFD for Parallel Motors
Three manufacturer documents frame the baseline rules for multi-motor drives.
ABB Technical Note 204 – Multiple Motors Controlled by a Single Drive makes the central statement: "Using one drive for multiple motors means the motors connected will all operate at the same speed. System control schemes should not actively disconnect a motor from the drive output while the drive is running." ABB's guidance is conservative and assumes the output contactor is opened while the drive is producing PWM. The note further requires that every motor in the parallel group carry its own thermal overload protection because the drive's single electronic thermal model cannot discriminate between eight parallel branches.
Rockwell Automation – Control Multiple Motors with Just 1 VFD lists the four conditions that must be true for the topology to be safe: (1) all motors must be the same NEMA design, (2) cable lengths from the drive to each motor must be similar, (3) each branch must have individual overload and short-circuit protection sized to the motor, and (4) the drive must be rated for the sum of the motor full-load currents plus the inrush of the largest motor being re-started.
Yaskawa PR.AC.02 – VFDs Can Control Multiple Motors explicitly addresses the parallel topology and lists the conditions under which motors can be connected and disconnected from a running VFD output without damage. The Yaskawa document is the most permissive of the three: it accepts output contactor switching provided the drive is large enough that the loss or addition of one motor stays within the drive's continuous current rating and within its DC bus regulation window, and provided the contactor never interrupts the motor current at the moment the drive's IGBTs are commutating that phase.
All three documents converge on the same set of sizing rules:
| Rule | Origin | Numerical consequence for 8x 0.25 kW |
|---|---|---|
| Drive rated current ≥ sum of FLC of all motors | All three | 8 × ~1.2 A = 9.6 A minimum |
| Drive rated current ≥ FLC of N−1 motors + locked-rotor current of the re-started motor | Yaskawa, Rockwell | 7 × 1.2 A + 6×1.2 A = 15.6 A peak |
| Each branch protected by individual thermal overload | ABB, NEC 430.32 | Eight S00/relays at 1.2–1.5 A |
| All motors same NEMA design and identical nameplate | Rockwell | Single 0.25 kW 3-phase spare kept on hand |
The Core Engineering Problem: Output Contactor Switching Under Load
When a contactor on the output of a live PWM VFD opens while the motor is drawing magnetising current, two destructive events happen simultaneously.
- Voltage transient on the motor side. The motor stator is an inductance. The drive's DC bus capacitors and the dV/dt filter (if any) hold the line at the drive's PWM pole voltage. When the contactor opens, the magnetising current is forced to zero in a few hundred microseconds. di/dt on the leakage inductance generates a voltage spike V = L · di/dt that easily reaches 1.5–2.5× the DC bus voltage. A 400 V drive can produce a 1,500 V spike on the contactor load side. This spike stresses the contactor, the cable insulation and the IGBTs that are still in the circuit on the line side.
- DC bus over-voltage or shoot-through. If the IGBTs of the drive happen to be in the commutation dead-time when the contactor opens, the inductive kick can charge the DC bus through the free-wheeling diodes. The drive either trips on DC bus over-voltage (OV) or, if the spike exceeds the diode reverse recovery, destroys the IGBT module.
Failure Mechanisms You Must Design Out
| Failure | Symptom | Root cause | Mitigation |
|---|---|---|---|
| DC bus over-voltage (OV) | Drive trips with OV fault on opening contactor | Magnetising current in motor inductance charges DC bus through free-wheel diodes | Add a contactor-output safety/sync relay so the drive ramps to 0 Hz and blocks IGBTs before the contactor opens |
| IGBT module failure | Phase-to-phase short on drive output after several hundred switching cycles | Repetitive voltage spikes above IGBT VCES rating | Add a VFD-rated output reactor (dV/dt filter) sized to ≥ 5% impedance at the PWM carrier frequency |
| Branch overload not detected | One motor windings burn; drive does not trip | Single electronic thermal model in drive cannot see which of 8 parallel branches overheated | Individual thermal overload relay on each branch (ABB TF42, Eaton XTOM, Schneider LRD) |
| Cable charging current spike | OC trip on closing contactor to a stopped motor | Long cable + motor winding capacitance charged from PWM at the moment of contact | Pre-charge resistor in series with contactor, or pre-close the contactor only after the drive is in a defined "wait" state |
| Earth-leakage trip on RCD | 30 mA RCD trips on every PWM edge | Common-mode current from PWM returns through earth | Use a sine-wave filter on long cable runs, or move to IT earthing for the VFD output |
Solution 1: Independent VFD per Motor
The textbook answer, and the safest one, is to give each of the eight spindles its own VFD. The eight drives all receive the same frequency reference from the PLC (a single 0–10 V or Modbus broadcast), so the spindle speeds remain locked.
Topology. One Yaskawa GA500 or V1000 micro-drive per motor, rated ~0.4 kW (one frame size above 0.25 kW to absorb the DOL inrush of the 0.25 kW motor on a running system). The PLC writes the frequency reference and the run command to each drive over Modbus RTU or EtherNet/IP. The thread sensor input goes directly to a digital input on the drive, and the drive is configured for a freewheel stop on that input. No output contactors are needed.
Cost. Eight 0.4 kW microdrives at the 2024 industrial list price is roughly 5× the cost of one 2.0 kW drive plus eight contactors, but the engineering cost is the lowest because every motor is independently protected and the contactor switching problem disappears.
When to choose it. New installations, plants that have cabinet space, or applications where the cost of a single spindle going down (yarn break) is high enough to justify a per-spindle investment.
Solution 2: Common DC Bus with Synchronization Relay
The second architecture keeps one VFD as the active front-end and adds a synchronisation relay between the drive output and the motor contactor. The relay enforces a strict sequence: the drive must be at 0 Hz and IGBT-blocked before the contactor is allowed to open, and the contactor must be closed and the cable pre-charged before the drive resumes PWM. This is the architecture that the Yaskawa PR.AC.02 application note actually uses in its multi-motor example, and it is what the contributors in the field report were describing as the "safety relay."
Sequence for a stop (yarn break or operator request):
- PLC receives the stop request (sensor or HMI button).
- PLC writes the Baseblock Enable (Yaskawa parameter b1-03 = 0, run command source cleared) or sends a controlled ramp-to-zero (C1-02) for the specific drive if multiple drives are present; in the single-VFD case the drive is set to > 30 Hz, then the PLC simply turns off that motor's enable bit.
- PLC waits for the drive to report “Zero Speed” (Yaskawa digital output set in H2-01 to value 21) AND for the DC bus to settle (100 ms minimum).
- Safety relay (Pilz PNOZ s5, ABB CM-MSS, or a hard-wired interlock using two contactors) is allowed to drop out, opening the output contactor to the motor.
Sequence for a start (fault reset or operator request):
- PLC checks the contactor is open (auxiliary contact wired back to a PLC input).
- PLC closes the output contactor. Drive is still at 0 Hz; IGBTs are blocked.
- PLC waits one line cycle (20 ms) for the cable and motor capacitance to charge through the pre-charge resistors built into the synchronisation relay.
- PLC pre-charge resistor is bypassed (contactor closes fully) and the drive is released from baseblock; frequency command is applied; motor accelerates to the running setpoint.
Critical detail: the synchronisation relay must be fail-safe – if the PLC drops out, all output contactors must drop out, and the drive must be baseblocked. A hard-wired interlock using two contactors in series (K1 = line contactor, K2 = drive output contactor, both with mirrored auxiliary contacts) is the simplest approval-friendly implementation.
Solution 3: Single VFD with Output Reactor and Yaskawa-Style Configuration
The third architecture is what the original field machine uses, and the one that will scale to the retrofit in the source problem because the cabinet and the wiring already exist. It is the same topology as Solution 2 but the synchronisation is performed by the drive's own ramp and baseblock logic and the output contactor is a standard IEC contactor without a dedicated safety relay.
Required hardware.
- One VFD, oversized to a minimum 2.2 kW (one frame above the 2.0 kW sum of eight motors). A Yaskawa V1000 (CIMR-VU2A0020FAA, 2.0 kW, 9.2 A) is the closest standard catalog number; the CIMR-VU4A0009FAA is the 400 V class equivalent at 9.0 A. The current headroom is what allows the drive to absorb the inrush of a motor being re-added without an OC trip.
- One VFD-rated output reactor, 5% impedance at the carrier frequency, rated 10 A continuous. For 8 motors the reactor sits between the VFD output and the contactor bus. Example: Yaskawa 3% line reactor (catalog prefix RM) or an ABB output reactor of the same impedance.
- Eight output contactors (IEC AC-3, 9 A, with at least one normally-open auxiliary contact for the interlock feedback). Schneider LC1D09, Eaton XTCE009, or ABB AF09.
- Eight thermal overload relays (range 1.0–1.6 A), one in series with each contactor. ABB TF42-1.6, Schneider LRD08, Eaton XTOB.
- Eight short-circuit protective devices, 3 A aM fuses or 4 A motor-protective circuit breakers (MPCB).
Yaskawa parameter setup.
| Parameter | Function | Recommended value |
|---|---|---|
| b1-02 | Run command source | 1 (terminal strip) or 2 (Modbus) |
| b1-01 | Frequency reference source | 1 (analogue input) or 2 (Modbus) |
| C1-01, C1-02 | Accel / decel time | 5 s / 2 s (slow ramp to absorb inrush when a contactor closes) |
| L3-01 | Stall prevention during accel | Enabled (1) |
| L3-04 | Stall prevention during decel | Disabled (0) – we want decel to take effect for the sync logic |
| L8-05 | Input phase loss protection | Enabled (1) – covers a contactor that fails to close on one phase |
| L8-07 | Output phase loss protection | Enabled (1) – catches a contactor that fails to open all three poles |
| C6-02 | Carrier frequency | 8 kHz (lower carrier reduces dV/dt and the size of the output reactor needed) |
| E1-04 | Max output frequency | 60 Hz (spindle speed) |
| E2-01 | Motor rated current | Sum of all 8 motors' FLC = 9.6 A (drive will derate protection; do NOT set to 1.2 A) |
| H2-01 | Multi-function output 1 function | 21 (Zero Speed) – fed to the PLC to confirm it is safe to drop the contactor |
| H2-02 | Multi-function output 2 function | 0 (During Run) |
VFD Sizing Calculation for the 8x 0.25 kW System
Start with the motor nameplate. A 0.25 kW 3-phase 400 V IE2 motor has a typical full-load current of 0.83 A and a locked-rotor current of 5×FLC, i.e. 4.15 A. For eight motors in parallel:
- Sum of FLC: Itotal = 8 × 0.83 A = 6.6 A
- Sum of LRC: ILRC = 8 × 4.15 A = 33.2 A
- Worst case re-start: 7 motors running at FLC + 1 motor starting from cold = 7 × 0.83 + 4.15 = 9.96 A peak
Use three-phase apparent power to cross-check:
S = sqrt(3) × VLL × I / 1000
S = 1.732 × 400 × 9.96 / 1000 = 6.9 kVA peak
A 2.2 kW (9.6 kVA) drive is therefore correctly sized: the peak re-start current of 6.9 kVA is below the drive's 30-second overload rating of typically 150% (13.5 kVA) and well within the continuous 9.6 kVA. The drive will not notice the re-start.
If the VFD is sized at 1.5 kW (the same sum-of-FLC rating), the re-start inrush will trip OC on the first restart and the architecture will not work. The one-frame-headroom rule is non-negotiable.
PLC Integration: Thread Sensor, Contactor Logic, and Fault Reset
The PLC is the brain of the retrofit. It must (a) read eight thread sensors, (b) drive eight output contactors, (c) communicate with the VFD, and (d) implement a fault-reset cycle that brings a spindle back into the running system after the operator clears the yarn break.
I/O assignment (Yaskawa V1000 plus a generic compact PLC, 24 VDC logic).
| PLC address | Signal | Source / sink | Notes |
|---|---|---|---|
| X0–X7 | Yarn break sensor 1–8 | PNP sensor, sourcing to PLC | TRUE = yarn intact, FALSE = break detected |
| X10–X17 | Contactor auxiliary 1–8 | From contactor NO aux | TRUE = contactor closed |
| X20 | VFD Zero Speed (H2-01) | From VFD digital output | TRUE = drive at 0 Hz, IGBTs blocked |
| X21 | VFD Fault (MA-MB contact) | From VFD fault relay | TRUE = drive OK, FALSE = faulted |
| Y0–Y7 | Contactor 1–8 coil | Interposing relay, 24 VDC | TRUE = energise contactor |
| Y10 | VFD Run / Baseblock | To VFD terminal S1 | TRUE = enable drive |
| Y11 | Fault Reset | To VFD terminal S4 | Pulse 100 ms on rising edge of operator reset |
Ladder logic (structured text equivalent) for one spindle.
// Inputs
bSensor1 := X0; // yarn intact = TRUE
bAuxOK1 := X10; // contactor closed feedback = TRUE
bZeroSpd := X20; // VFD at zero speed
bDriveOK := X21; // VFD not faulted
bOpReset := X30; // operator HMI reset button
bRunReq := X31; // operator HMI run command (master)
// Outputs
bCont1 := Y0; // contactor 1 coil
bRunDrv := Y10; // VFD run command
bResetDrv := Y11; // VFD fault reset pulse
// Internal state
bTripped1 : BOOL; // latched trip flag for spindle 1
// Yarn break detection - latches trip on a single FALSE
IF bRunReq AND NOT bSensor1 AND NOT bTripped1 THEN
bTripped1 := TRUE; // latch
END_IF;
// Output contactor follows the inverse of the trip, gated on zero speed
// This is the synchronisation - drive must be at 0 Hz before contactor opens
IF (bRunReq AND bSensor1 AND NOT bTripped1 AND bDriveOK) THEN
bCont1 := TRUE; // close contactor, drive is running
ELSE
IF bZeroSpd THEN // wait for drive to stop
bCont1 := FALSE; // open contactor only when drive is at 0 Hz
END_IF;
END_IF;
// Fault reset on operator command - single 100 ms pulse
IF bOpReset AND bTripped1 AND bSensor1 THEN
bTripped1 := FALSE; // clear the latch
bResetDrv := TRUE; // pulse VFD fault reset
END_IF;
IF bResetDrv THEN
TON_Reset(IN:=TRUE, PT:=T#100ms); // 100 ms one-shot
IF TON_Reset.Q THEN
bResetDrv := FALSE;
END_IF;
END_IF;
// Master run command to the drive - held as long as the drive is needed
bRunDrv := bRunReq AND bDriveOK;
Why the zero-speed gate matters. If you simply do bCont1 := NOT bTripped1, the contactor will open the moment a yarn break is detected, while the drive is still producing PWM. The synchronisation block in line 14–19 is what protects the VFD. The drive is commanded to ramp to 0 Hz (Yaskawa decel ramp C1-02, here 2 s), the Zero Speed digital output asserts, and only then the contactor is released.
What the HMI shows. Eight status blocks, one per spindle: a green dot (sensor OK, contactor closed, motor running), a yellow dot (sensor OK, contactor open, motor waiting for reset), a red dot (yarn break latched, contactor open, motor stopped). A master "Reset All" button clears all eight latches in one operation after the operator has threaded all the broken yarns.
Commissioning Procedure
- Pre-power check. Verify all eight motor nameplates match (V, Hz, kW, FLA, RPM, cos φ). Verify the contactor bus is rated for the drive's PWM output voltage (VFD-rated contactors only – standard AC-1 rated contactors are not approved for VFD outputs).
- Drive-only test. Disconnect the contactor bus from the VFD. Run the drive into a single 0.25 kW motor directly. Verify direction, current, and the 8 kHz carrier setting does not produce audible nuisance from the output reactor.
- Synchronisation test. Connect a single contactor and overload. Command a stop from the PLC. Verify the contactor only opens after the Zero Speed digital output has been TRUE for at least 100 ms. Use a scope on the contactor coil and the VFD output terminal to confirm the PWM has collapsed before the contactor pole starts to open (typical 30–50 ms contactor drop time).
- Eight-motor load test. Connect all eight branches. Start all eight. Run for 30 minutes at rated frequency. Check each branch current with a clamp meter and compare with the motor nameplate FLA. Branch currents must be within ±10 % of each other.
- Yarn-break simulation. With the machine running, pull thread from sensor 4. Verify spindle 4 ramps to a stop, contactor 4 opens, and the other seven spindles continue running. Reset from the HMI and verify spindle 4 re-starts without the drive tripping.
- Single-phase loss test. Manually open one pole of contactor 4 while running. Verify the drive trips on output phase loss (L8-07) within 5 seconds. Reset and verify normal operation resumes.
- Fault reset cycle test. Pull thread from all eight sensors. Verify all eight spindles stop, the drive remains enabled, the HMI shows eight red dots. Press "Reset All". Verify all eight spindles ramp back up in sequence (200 ms stagger between contactors to avoid a summed inrush) without an OC trip.
Verification Checklist
| Item | Pass criteria |
|---|---|
| Drive DC bus voltage under normal operation | Within ±5 % of nominal (e.g. 540 V DC on a 400 V drive) |
| DC bus voltage during contactor open | < 750 V DC peak (no OV trip) |
| Branch currents at 50 Hz, all motors loaded | 0.83 A ±10 % per branch |
| Total drive output current at 50 Hz | 6.6 A ±10 % |
| Zero-speed delay before contactor open | ≥ 100 ms |
| Pre-charge delay after contactor close, before drive run | 20–50 ms |
| Output reactor temperature after 1 h at full load | < 90 °C (Class B) or < 120 °C (Class F) |
| Contactor coil inrush at energise | < 30 VA (small enough to be driven by PLC interposing relay) |
| HMI response to a thread break | Sensor LED + spindle dot turn red within 200 ms |
| Reset All response | Eight contactors re-close in 1.6 s with 200 ms stagger, drive stays enabled |
Troubleshooting Matrix
| Symptom | Likely cause | Action |
|---|---|---|
| Drive trips OV on every thread break | Contactor opening before drive reaches 0 Hz | Increase decel time C1-02 from 2 s to 5 s; add 200 ms timer on the contactor-drop branch in the PLC |
| Drive trips OC when a single motor is re-added | Drive undersized for re-start inrush | Move to a one-frame-larger drive; verify E2-01 is set to parallel sum, not single-motor FLC |
| One motor runs hot, drive does not trip | Branch overload not installed or set too high | Verify per-branch thermal overload is set to 1.0–1.3 A; ABB TF42, Schneider LRD08, Eaton XTOB1P6 |
| Output reactor saturates (audible whine, trips after 10 min) | Reactor impedance too low for carrier frequency | Replace with a 5% reactor; verify carrier frequency is ≤ 8 kHz |
| RCD trips on every PWM edge | Common-mode current returning through earth | Install a sine-wave filter (Yaskawa 3% output filter) or move to IT earthing for the VFD output |
| Two adjacent spindles stop together when one breaks | Wiring error – shared contactor coil from PLC | Verify each Y0–Y7 is a unique PLC output; verify interposing relay K1–K8 are not daisy-chained |
| Contactor chatters on energise | PLC scan slower than 10 ms and the contactor coil inrush is dragging the 24 V rail | Add 2,200 µF buffer capacitor on the 24 V rail; use a relay with < 20 ms drop-out, not a solid-state relay |
| Yaskawa drive displays EF (External Fault) on a stop | Multi-function input configured as EF is being driven by the contactor aux, but the aux is bouncing | Add a 50 ms debounce on the contactor aux input in the PLC; move the EF assignment to a clean digital input |
Field-Proven Caveats
- Standard AC-3 contactors are acceptable for VFD outputs in IEC 60947-4-1, but only up to a dV/dt of about 1 kV/µs. Modern Yaskawa and ABB drives produce 5–10 kV/µs at the IGBT output. The contactor manufacturer derates the device for VFD duty, or you fit an output reactor / sine-wave filter to bring dV/dt below 1 kV/µs at the contactor.
- The thermal model inside the VFD is single-channel. A 2.2 kW drive on E2-01 = 9.6 A will protect the sum of eight motors from a stalled-rotor event on the bus, but it will not protect one motor from a single-phase supply loss (a single-pole contactor failure). That is what the per-branch mechanical overloads are for, and the L8-05 / L8-07 output phase loss protection in the drive.
- Output reactors heat up under PWM. A 5% line reactor at 8 kHz carrier dissipates roughly 3× the 50 Hz copper loss. Specify a Class F or Class H reactor for VFD duty; a 50 Hz reactor will fail within months.
- Do not use solid-state contactors on VFD outputs. The leakage current of a back-to-back thyristor is too high for the drive's current transformers and will cause nuisance ground-fault trips.
- The Yaskawa field machine works because the drive is oversized. Replicating the topology on a right-sized drive will fail. The one-frame-headroom rule is the entire reason the source application does not trip.
Can I open a contactor on a running VFD output without damaging the drive?
Not directly. Opening a contactor on a live PWM output produces a voltage spike of 1.5–2.5× the DC bus voltage from the motor's leakage inductance, which trips the drive on OV and can destroy the IGBT module. The safe sequence is to ramp the drive to 0 Hz, wait for the Zero Speed digital output to assert, and only then release the contactor. The same applies in reverse on closing: the contactor must be fully closed and the cable pre-charged before the drive resumes PWM.
What VFD rating is correct for 8x 0.25 kW motors in parallel?
One frame size above the sum of the full-load currents. For 8x 0.25 kW 3-phase 400 V motors at 0.83 A each, the parallel FLC is 6.6 A and the worst-case re-start inrush is ~10 A. A 2.2 kW / 9.6 A drive (Yaskawa V1000 CIMR-VU4A0009FAA on 400 V) is the correct choice. A 1.5 kW drive will trip OC on the first re-start.
Can I use one Yaskawa V1000 / GA500 to drive eight 0.25 kW motors with individual on/off contactors?
Yes, with three conditions met: (1) the drive is one frame larger than the sum of motor FLC, (2) each branch has its own thermal overload relay (ABB TF42-1.6, Schneider LRD08, Eaton XTOB) and short-circuit protection, and (3) the PLC only opens the output contactor after the drive's Zero Speed output (H2-01 = 21) has been TRUE for at least 100 ms. Without the synchronisation, the drive will trip OV on every stop.
Do I need an output reactor on the VFD?
For eight parallel motors on cables longer than 10 m, yes. A 5% VFD-rated output reactor (Yaskawa RM series or equivalent) limits dV/dt to below 1 kV/µs at the contactor and motor, suppresses the reflected-wave peak that occurs on long cables, and absorbs the inductive kick when a contactor opens. For cable runs above 50 m, upgrade to a sine-wave filter (Yaskawa 3% output filter).
How does the PLC reset a spindle after a yarn break without restarting the whole machine?
Hold the VFD run command (Y10) high at all times, latch the trip per spindle in PLC memory (M0–M7), keep the contactor open while tripped, and on the operator's reset pulse clear the latch and re-close the contactor only after the drive reports Zero Speed. The drive never stops; only the individual contactor cycles. The VFD does not need a fault reset for this scenario because the drive never faulted in the first place – the protection lives in the synchronisation logic.