Troubleshooting LED Errors on SIMODRIVE 610 6SC6901 Drives

David Krause11 min read
Motion ControlSiemensTroubleshooting
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

1. System Identification: SIMODRIVE 610 versus 650/690

The Siemens SIMODRIVE 610 family (Siemens order designation 6SC610 series) is a digital three-phase servo drive system intended for use with feed and main spindle motors in CNC machine tools. It is commonly paired with SINUMERIK 810, SINUMERIK 820 and SINUMERIK 840C controls, and accepts resolver or encoder feedback from 1FT5, 1FT6, and 1PH series motors.

The order number 6SC6901 reported by the user is, however, ambiguous. The order-number root 6SC6901 belongs to the SIMODRIVE 650/SIMODRIVE 690 families used with the SINUMERIK 805 control, NOT the SIMODRIVE 610 line. The 610 line uses roots such as 6SC6101, 6SC6102, and 6SC6108. Before any LED diagnosis, verify the data plate MLFB on the side of the module to determine which family is actually in the cabinet.

MLFB Root Family Paired Control DC Bus Notes
6SC610x SIMODRIVE 610 SINUMERIK 810/820/840C ~600 V DC from 3×400 V AC line Modular 2-axis feed/spindle drive
6SC650x SIMODRIVE 650 SINUMERIK 805 ~600 V DC from 3×400 V AC line Compact single-axis drive
6SC6901 SIMODRIVE 690 SINUMERIK 805 ~600 V DC from 3×400 V AC line Higher-current 690 module
Field experience shows that cabinets built before 1995 sometimes mix 610 and 690 modules. Always read the data plate MLFB before swapping firmware or replacing a module, because the LED patterns and parameter sets differ.

2. LED Panel Layout on SIMODRIVE 6SC6901 Modules

The front panel of the 6SC6901 module exposes a vertical column of status LEDs. The exact count depends on the variant suffix (for example 6SC6901-0AA02 versus 6SC6901-2AB01), but the canonical five-LED layout from top to bottom is:

LED Position Color Function Normal State
H1 (top) Green Power / Ready Solid ON when 5 V logic and DC bus are healthy
H2 Green Encoder track A activity Flickers at motor rotation
H3 Green Encoder track B activity (quadrature) Flickers at motor rotation; interlocks with H2
H4 Yellow Enable / Speed-zero reached ON when n < n_min and drive enabled
H5 (bottom) Red Write protection / Fault latch OFF in normal run, ON with parameter lock
6SC6901 front panel H1 - Power/Ready H2 - Track A H3 - Track B H4 - n=0 / Enable H5 - Write-Protect Healthy run: H1 ON solid H2/H3 flicker H4 ON at standstill H5 OFF FAULT: H1 OFF, H5 ON = bus or logic fault

The figure above shows the typical LED arrangement on a 6SC6901 front panel. The two green LEDs dedicated to encoder tracks must change state when the motor shaft is rotated by hand with the drive disabled; if they remain dark or solid, the encoder cable, the encoder itself, or the receiver circuit on the module is at fault.

3. Encoder Track LED Diagnostics (H2 / H3)

The middle LEDs indicate activity on the two quadrature channels (typically channel A and channel B, sometimes labelled SpA / SpB or Track I / Track II) coming from the motor's incremental encoder. Normal behaviour:

  • Motor stationary: both H2 and H3 dark (logic-low state).
  • Motor rotated by hand, drive disabled: H2 and H3 alternate flickering.
  • Frequency of flicker is proportional to shaft speed; at very slow rotation the LEDs appear to blink alternately.

Abnormal patterns and their likely causes:

Symptom Likely Cause Action
Both H2 and H3 dark, motor turns freely Encoder cable open or shielded Check D-sub connector, pin continuity X411 / X412
H2 dark, H3 flickers Broken track-A wire, encoder half-failed Replace encoder or test with oscilloscope
Both LEDs solid ON regardless of rotation Encoder cable shorted, +5 V or GND short Disconnect encoder at module, re-measure
LEDs flicker but drive reports F-11 / F-31 Signal noise, ground loop, low amplitude Check shield bonding at cabinet entry
LEDs dim, irregular pulse +5 V supply weak, encoder ageing Measure 5 V at encoder connector, >4.85 V under load
Never hot-plug the encoder cable on a powered SIMODRIVE module. The 5 V encoder supply rail is fused internally; a hot-plug event can latch the red H5 LED and require a power-cycle reset.

4. Write-Protection LED (H5, Red, Lower Position)

The red LED at the lower position of the LED column indicates the state of the internal parameter write-protection flip-flop. It is also used as a fault latch indicator on certain firmware revisions.

H5 State Meaning Recovery
OFF during run Parameters can be written from PCIN / HMI No action
ON solid Parameters locked via MD bit or hardware strap Toggle bit in MD or remove jumper at X34
Slow blink (1 Hz) Latched fault, see SINUMERIK alarm log Acknowledge with RESET on NC keyboard
Fast blink (4 Hz) Module in download/initialization mode Wait or re-flash firmware

On older 6SC6901-0AAxx modules the write-protect LED shares its driver with the watchdog output. A continuously-on H5 LED combined with a dark H1 LED is, in many cases, the watchdog having tripped — which can be caused by:

  1. Loss of one phase on the 3-phase 400 V supply (the module powers down its internal logic but the DC bus capacitor retains charge).
  2. Overtemperature on the heatsink (PTC > 110 °C) latched.
  3. I²C / serial EEPROM error during parameter load.

5. Power and DC-Bus Status LEDs (H1)

The top green LED reflects the health of the internal 5 V logic supply derived from the DC bus. The drive generates its own DC link from the 3-phase 400 V AC input; nominal DC bus voltage is approximately 540 V DC for a 400 V AC line (peak × √2 × rectified, minus diode drop), reaching about 565 V DC under no-load conditions.

Voltage expectations during commissioning:

Test Point Nominal Min Acceptable Max Acceptable
DC bus (P600 / N600) 540 V DC 470 V DC 620 V DC (regen clamp)
5 V logic (test pin) 5.00 V DC 4.85 V DC 5.15 V DC
24 V control (X11) 24 V DC 20 V DC 30 V DC
±15 V analog ±15.0 V DC ±14.5 V DC ±15.5 V DC
If the line input is single-phase rather than three-phase, the DC bus will only reach ~310 V DC and the module will either refuse to enable or trigger an undervoltage alarm within 200 ms. Confirm the supply topology before further diagnosis.

6. Common LED Error Patterns and Root Causes

The following matrix aggregates the most frequent LED combinations observed on 6SC6901 modules in CNC retrofit projects. Use it as the first decision tree before opening PCIN.

H1 H2 H3 H4 H5 Most Probable Cause Recommended Action
OFF x x x ON No DC bus / phase loss Measure L1/L2/L3 at main contactor
OFF x x x OFF Logic 5 V supply failed Check internal fuse F1
ON OFF OFF OFF OFF Encoder cable/encoder fault Inspect X411 connector
ON blink blink OFF blink Latched alarm, see NC Read PLC FB1 / alarm buffer
ON blink blink ON OFF Drive ready, axis at standstill No fault
ON OFF blink ON ON One channel lost, latch set Reset and check encoder
blink x x x OFF Module in boot-loader mode Reflash via PCIN 4.7
ON x x x ON solid Watchdog tripped / write-protect Cycle 24 V control power only

7. Step-by-Step Diagnostic Procedure

Use the following sequence to isolate an LED fault on a 6SC6901 module. Always work with the main breaker open and confirm zero energy at the bus capacitors before touching connectors.

  1. Confirm the data plate. Record the full MLFB (for example 6SC6901-2AB01-Z), serial number, and firmware sticker. The firmware suffix matters: a 6SC6901 with FW V3.x reports different LED behaviour than a V5.x unit.
  2. Power up with no enable. Apply 3-phase 400 V AC and 24 V DC control. Observe H1. If H1 is OFF, measure DC bus voltage at P600 / N600 before assuming a module failure.
  3. Rotate motor shaft by hand. H2 and H3 must alternate-flicker. If they do not, lift the encoder connector X411 (or X412 depending on variant) and measure 5 V supply between pins 1 and 2. Replace cable if the supply is missing at the motor end.
  4. Check SINUMERIK alarm history. On the 805 operator panel press MENU SELECT > ALARM. Note any alarm numbers such as 6020, 6040, 6042, 16830, or 300613. Cross-reference with the SINUMERIK 805 diagnostics manual.
  5. Establish PCIN 4.7 link. Use a Siemens RS-232 cable (6FC9341-1AA) on COM1 of the 805 and the operator PC. Start PCIN 4.7, set 9600 8N1, and request READ OUT DATA. If the link fails, the module's red H5 LED may be latched and require a 24 V control-power cycle.
  6. Clear latched faults. Cycle only the 24 V DC control supply (leave the 400 V AC main breaker on) for at least 10 seconds, then re-apply. Watch the LED pattern transition during power-up.
  7. Verify enable chain. The drive will refuse to enable if terminals 63 and 64 (drive enable) are not at 24 V and 9 (NE) is referenced to 19 (NE). Verify at the terminal block before suspecting the module.
  8. Run a no-load reference move. In PCIN 4.7, load the original backup file (*.TEA), set MD bit 0 (write-protect) to 0, and perform a 1 mm reference move. Confirm H4 yellow lights at standstill and H2/H3 flicker in proportion to commanded velocity.

8. PCIN 4.7 Backup, Restore and Parameter Handling

Siemens PCIN 4.7 is the standard Windows tool to read and write parameters of SIMODRIVE 6SC6901 modules via the SINUMERIK 805 RS-232 interface. The procedure below is the field-validated workflow.

Step PCIN 4.7 Action Expected Response
Connect Start PCIN, choose RS-232, COM1, 9600 baud, 8 data bits, no parity, 1 stop bit Status "CONNECTED"
Read all data Menu Data > Read out all data Progress bar reaches 100%
Save File > Save as backup_6SC6901_<date>.TEA File size > 30 kB
Modify write-protect Edit parameter MD bit 0 → 0 Red H5 LED must extinguish
Write back Data > Read in data Module acknowledges each block
Verify Compare checksum displayed by PCIN Checksum matches file

PCIN 4.7 reads *.TEA ASCII files. Each parameter line is of the form P<number> = <value>;. Do not edit the file in a non-ASCII-safe editor such as Notepad++ with UTF-8 BOM enabled — the BOM character causes the module to reject the block.

Always save a backup before any modification. Field experience shows that operators frequently toggle the write-protect bit by mistake, which prevents subsequent parameter downloads and latches the red H5 LED until a 24 V power-cycle.

9. Field Commissioning Checks

After replacing or re-flashing a 6SC6901 module, perform the following verification sequence before returning the machine to production.

  1. Insulation test. With the module isolated, megger between P600 and PE at 500 V. Reading must be > 5 MΩ.
  2. Phase rotation. Confirm L1-L2-L3 sequence at the line contactor matches the marking on the module. Reverse sequence will not damage the module but will spin the motor backwards at first command.
  3. DC bus rise time. From 0 V to 540 V DC must occur in < 1.5 s under soft-charge. A slow rise indicates a soft-charge resistor or contactor fault.
  4. Encoder cable shield. Shield must be bonded to cabinet ground at the entry plate only — not at both ends. Use Siemens pre-fabricated cable 6FX5002 series where possible.
  5. Enable response time. From 24 V at terminal 63 to H4 yellow LED ON must be < 50 ms. A delay > 100 ms indicates parameter loading not yet complete.
  6. Speed-loop bandwidth. Run a step response in PCIN 4.7 diagnostic mode. The current loop bandwidth must be > 1 kHz and velocity loop bandwidth > 100 Hz for a healthy 6SC6901.

10. Safety and Replacement Notes

The 6SC6901 module weighs between 18 and 32 kg depending on the variant. The DC bus capacitors retain dangerous voltage for up to 5 minutes after the 400 V AC line is removed. Observe the warning label on the front panel: "DC bus dangerous — wait 5 minutes before opening".

Use only Siemens original spare parts or formally re-qualified substitutes. Compatible Siemens order numbers include:

Function Original MLFB Notes
Power module 25 A 6SC6901-2AB01 Common feed-drive
Power module 50 A 6SC6901-2AB02 Main spindle
Power module 80 A 6SC6901-2AB03 Larger spindle
Control board 6SC6901-2AA00 Swappable in field
Firmware EPROM set 6SC6901-8ABxx Order by installed FW sticker
Confirm the exact 6SC6901 suffix before ordering. Siemens shipped more than 30 variants of the 6SC6901 over the production life, and the connector pin-out for X411 differs between -0A and -2A generations.

11. Frequently Asked Questions

What do the green LEDs in the middle of a SIMODRIVE 6SC6901 indicate?

The two middle green LEDs (H2 and H3) reflect activity on the two incremental encoder channels A and B. With the drive disabled, rotating the motor shaft by hand must produce alternating flickering on both LEDs; if one or both remain dark, suspect the encoder cable, the 5 V encoder supply, or the receiver IC on the module.

Why is the red write-protection LED (H5) permanently lit?

The red H5 LED signals either the parameter write-protect bit is set in machine data, the hardware strap on X34 is in the LOCK position, or the watchdog has latched a fault. Clear the MD bit through PCIN 4.7 and cycle the 24 V control supply for at least 10 seconds. If the LED stays on, inspect the hardware jumper X34 and the heatsink PTC.

Is a 6SC6901 module the same as a SIMODRIVE 610?

No. The order-number root 6SC6901 belongs to the SIMODRIVE 650/690 family used with SINUMERIK 805 controls. SIMODRIVE 610 modules use roots starting with 6SC610x and are paired with SINUMERIK 810/820/840C. The LED semantics are similar but the parameter sets, connector pin-outs, and DC bus characteristics differ.

How do I read parameters from a 6SC6901 with PCIN 4.7?

Connect a Siemens RS-232 cable (6FC9341-1AA) between the SINUMERIK 805 COM1 port and the operator PC, start PCIN 4.7, set 9600 baud, 8N1, choose Data > Read out all data, and save the resulting *.TEA file. Always save a backup before any modification.

After a power outage my drive shows H5 ON and H1 OFF. What should I check first?

Measure the 3-phase 400 V AC supply at the line contactor — a missing phase after a brown-out is the most common cause. Verify the DC bus at P600/N600 reads 540 V DC ± 10%. Then cycle only the 24 V DC control supply; if H5 stays ON with H1 OFF, replace the internal fuse F1 or the control board 6SC6901-2AA00.

Back to blog