Troubleshooting MICROMASTER 420 STARTER Parameter Change Errors
The Siemens MICROMASTER 420 (6SE6420 series) is a compact, sensorless vector (SLVC) drive widely used in constant-torque and variable-torque applications. Commissioning is performed with the STARTER (or newer Startdrive) software, which stores a complete parameter image both online (in the drive) and offline (in the project file on the engineering PC). When STARTER refuses to write a parameter and reports an "error during change parameter" or "parameter cannot be changed in this state" dialog, the fault is most often attributed to a corrupted offline parameter file rather than a drive hardware defect. This reference walks through the diagnostic path, the field-proven resolution used by commissioning engineers, and the preventive measures that keep a fleet of MICROMASTER 420 drives synchronized.
1. Problem Definition
1.1 Symptom Profile
Engineers report one or more of the following dialogs in STARTER when trying to change a writable parameter (P0000–P1999 read-only, P2000–P3999 writable) on a MICROMASTER 420:
- "Error during change parameter" dialog box.
- "Parameter write protected" or "Parameter cannot be changed in current operating state."
- "Value out of range" rejection even for an unchanged default value.
- RAM-to-EEPROM commit fails; the value reverts after power-cycle.
- "Download to target device failed" when a RAM/ROM copy is attempted.
1.2 Trigger Conditions
| Condition | Likelihood | Notes |
|---|---|---|
| Same offline project used for two drives with different bus addresses | High | Drives at address 31 (USS) and 32 (USS) share a .pnx file |
| Project cloned by copy-paste in Windows Explorer | High | Internal GUID and checksum become inconsistent |
| STARTER version mismatch with drive firmware | Medium | MM420 firmware V1.5 paired with STARTER V5.4 SP3 introduces parameter-set incompatibility |
| RS485 termination or address conflict | Medium | Two drives replying on the same USS address |
| Drive in run state (r52 bit 0 = 1) | Low | Most P2000-level writes require the drive in STOP |
| Parameter write-protect (P0927 = 1) active | Low | Set to prevent unauthorized change |
1.3 Affected Versions
- Firmware: MICROMASTER 420 firmware V1.0 through V3.2 (the last released branch on this platform).
- STARTER: V4.1.1, V4.2, V4.3, V4.4, V4.5, V5.0, V5.1, V5.3, V5.4 SP3–SP5. Errors are reported most often in V4.x where the offline file format is closer to legacy DOT projects.
- Communication: USS on RS485 (default), PROFIBUS DP on a CB15/CB20 module, or MODBUS RTU on the integrated terminal.
2. Root Cause Analysis
2.1 Primary Cause: Corrupted Offline Parameter File
STARTER maintains two parameter images:
- Online image – read from the drive over the active bus. This is the ground truth.
-
Offline image – stored in the project directory as
*.pnx,*.dproj, or*.ziparchives. This is what STARTER uses to compare and to issue writes.
When the offline image becomes corrupted – typically through an interrupted upload, a forced Windows shutdown during a Save All, or a copy-paste of a project tree – the checksum inside the offline file no longer matches the parameter set that STARTER expects. STARTER then refuses to commit writes because the compare-and-validate step at the heart of the change-parameter dialog fails. The drive itself is healthy; only the engineering-side file is invalid.
2.2 Secondary Causes
| Cause | Mechanism | Diagnostic Check |
|---|---|---|
| USS address collision (P2011[0] = 31 on both drives) | Two drives reply to the same poll; STARTER accepts a corrupt multi-drive response | Read P2011[0] from each drive; verify uniqueness |
| BICO parameter locked to active value | P1500, P0731 etc. cannot be written while drive is running | Check r0002 (control word) and r0052 status bits |
| Parameter P0927 = 1 (parameter write-protect) | Read-only mode enabled by customer | Set P0927 = 0 and retry |
| Motor data identification incomplete | P1910 = 1 still pending, write blocked | Wait for r3925 bit 0 = 0 |
| Drive tripped (F0001–F0042) | Fault state blocks many writes | Clear fault with P3981 = 0 or via STARTER fault buffer |
| RS485 ground potential > 7 V | CRC errors on the bus; partial parameter echoed back | Check shield termination and PE bonding |
2.3 Why Two Identical Drives Behave Differently
The first drive (address 31) accepts the original project because the offline-to-online compare succeeds. The second drive (address 32) triggers the error because STARTER's diff engine now detects that certain internal pointer fields (e.g., offline_checksum and topology_uuid) do not match the file's content. The fault is in the file, not in the drive; therefore, downloading parameters from the working drive (31) into the problem drive (32) by first re-addressing drive 31 to 32, performing an Upload from Target Device, then writing the result back to drive 32, repairs the offline image and unblocks parameter changes.
3. MICROMASTER 420 Parameter Architecture
3.1 Parameter Numbering Scheme
| Range | Type | Writeable | Notes |
|---|---|---|---|
| P0000 – P0099 | Display / operation | Selectively | P0000 is the visible parameter index, P0010 starts quick commissioning |
| P0100 – P0199 | Setup / commissioning | Yes (P0010 = 1 quick, 30 factory) | Includes motor nameplate P0304–P0311 |
| P0200 – P0299 | Power section | Read-only on standard units | Set at factory |
| P0300 – P0399 | Motor data | Yes (P0010 = 1) | P0304 rated V, P0305 rated A, P0307 rated kW, P0310 rated Hz, P0311 rated rpm |
| P0500 – P0599 | Technology / control | Selectively | P0500 = 0 (V/f) default |
| P0600 – P0699 | Setpoint / ramp | Yes | P0700 = 1 (control via terminals) default |
| P0700 – P0799 | Command sources / digital inputs | Yes | Includes P0701–P0706 DI function |
| P0800 – P0899 | Analog I/O | Yes | P0756 ADC scaling |
| P1000 – P1099 | Setpoint source | Yes | P1000 = 1 MOP, 2 analog, 5 USS |
| P1100 – P1199 | Setpoint conditioning | Yes | Skip frequencies P1091–P1094 |
| P1200 – P1299 | Ramp generator | Yes | P1120 accel, P1121 decel |
| P1300 – P1399 | Control type | Yes | P1300 = 0 V/f linear, 2 V/f quadratic, 20 sensorless vector |
| P1500 – P1599 | Torque / BICO | Selectively | P1500 torque setpoint source |
| P2000 – P2099 | Communication | Yes | P2010 USS baud, P2011 USS address, P2012 PZD count, P2013 PKW count |
| P2100 – P2199 | Faults / warnings | Yes | P2100–P2103 last 4 fault codes |
| P3900 – P3999 | Commissioning / factory | Yes (P0010 = 30) | P3900 = 1 ready-to-run, P3981 fault clear |
3.2 Indexed Parameters and BICO Sources
Many MM420 parameters are index-dependent (e.g., P2011[0] = RS485 address, P2011[1] = BOP link address). Failure to specify the index when writing from STARTER can return a generic "parameter change error." Use the indexing drop-down in the parameter view rather than the simple input field.
4. STARTER Software Parameter File Layout
A STARTER project for a MICROMASTER 420 contains the following artifacts:
| File / Folder | Function |
|---|---|
ProjectName.pnx |
Primary project container (renamed to .dproj in Startdrive) |
Settings\ |
Topology, device configuration, bus addresses |
Commissioning\ |
Parameter lists and scripts (DOPS, FBs) |
Offline\ |
Snapshot of the last upload – the file most likely to be corrupted |
Log\ |
Trace recordings and event logs |
*.afw, *.awl
|
Compiled automation framework pieces (rare on MM420) |
Whenever STARTER writes a parameter, it performs the following steps internally:
- Read the parameter from the offline file.
- Validate against the schema for the firmware version (read from r0018 / r0019 firmware version).
- Compute the cyclic redundancy check (CRC) of the parameter set.
- Compare offline vs. online value (if Compare Values is enabled).
- Issue a parameter write via the active bus (PKW/PZD for PROFIBUS, USS frame for RS485).
- Read back and commit to EEPROM (P0971 = 1 trigger).
If step 2 or step 3 fails – typically because the offline CRC was invalidated by a partial save – STARTER raises the "error during change parameter" dialog and aborts the write.
5. Diagnostic Procedure
5.1 Step 1 – Confirm Drive Online State
- Right-click the drive in the project tree, choose Online / Offline.
- Observe the symbol next to the drive. A green tick = online, yellow = warning, red X = fault or no communication.
- If the symbol is red, check RS485 polarity on terminals 29 (+) and 30 (-–).
5.2 Step 2 – Read the Drive’s Firmware Version
From the parameter list, read:
-
r0018– Firmware version (e.g., 1.05) -
r0019– Drive object ID -
r0021– Actual DC-link voltage (must be > 430 V for 400 V class units, > 215 V for 230 V class units) -
r0026– Actual DC-link current -
r0034– Motor thermal load (%)
5.3 Step 3 – Read the Active Fault Buffer
Faults and warnings are stored as P0947 (last fault code) and P0952 (count). Common MM420 fault codes that block parameter writes:
| Code | Meaning | Effect on Parameter Write |
|---|---|---|
| F0001 | Overcurrent | Blocks write until acknowledged |
| F0002 | Overvoltage | Blocks write until acknowledged |
| F0003 | Undervoltage | Blocks write until acknowledged |
| F0004 | Inverter overtemperature | Blocks write until acknowledged |
| F0011 | Motor overload (I²t) | Blocks write until acknowledged |
| F0051 | Parameter fault during EEPROM write | Direct cause of "error during change parameter" |
| F0052 | Power stack fault | Hard fault – contact service |
| F0060 | Asic timeout | Hard fault – contact service |
| F0071 | USS link failure (P2014 timeout) | Communication only; retry after timeout |
| F0072 | USS setpoint timeout | Communication only; retry after timeout |
| A0501 | Current limit warning | Advisory only; does not block write |
| A0502 | Overvoltage limit warning | Advisory only; does not block write |
| A0503 | Undervoltage limit warning | Advisory only; does not block write |
5.4 Step 4 – Check P0927 (Write Protection) and P0010 (Commissioning Filter)
-
P0927 = 0– writes allowed. -
P0927 = 1– writes blocked. Reset to 0 to enable parameter modification. -
P0010 = 0– ready; most parameters writable. -
P0010 = 1– quick commissioning; only motor nameplate parameters writable. -
P0010 = 30– factory reset; do not enter for parameter write troubleshooting.
5.5 Step 5 – Inspect Offline Project CRC
From the STARTER menu, choose Project → Diagnostics → Check Project Integrity. STARTER reports a CRC mismatch for the offline parameter file. The dialog is the definitive confirmation that the project file is corrupted.
6. Resolution Methods
6.1 Method A – Refresh Offline Image by Re-uploading from the Drive (Field-Proven)
This is the procedure that resolved the reported case where two drives shared the same corrupted offline file.
- On the working drive (USS address 31), change
P2011[0]to 32. Press the green checkmark on the BOP to commit. The drive is now reachable at the problem address. - In STARTER, change the offline USS address of the project to 32 and click Online → Connect to Target System.
- Once online, right-click the drive and choose Upload from Target Device (HW). STARTER rebuilds the offline parameter image directly from the live drive.
- Compare the new offline file with the original by choosing Online → Compare Values. All parameters should show a green match.
- Open any writable parameter (e.g.,
P1120ramp-up time) and change the value. Click OK. The write should now succeed without error. - Restore the working drive’s address (
P2011[0]= 31) to put the network back into its original topology.
6.2 Method B – Repair the Offline File In-Place
- Make a backup of the corrupted
.pnx/.dprojfile. - Open STARTER. File → Open Project with the corrupted file.
- Right-click the drive and choose Expert List → Reload from Device.
- When the reload completes, Save Project with a new name to overwrite the corrupt CRC.
6.3 Method C – Factory Reset and Re-Commissioning
- Set
P0010 = 30andP0970 = 1. The drive resets to factory defaults (takes approximately 10 s). - Cycle the 24 V control power or the line supply to ensure the EEPROM commit is finalized.
- Re-enter the motor data from the motor nameplate:
P0304(V),P0305(A),P0307(kW or HP),P0310(Hz),P0311(rpm). - Run motor data identification:
P1900 = 2(full identification) and issue an ON command. Wait for the drive to complete the auto-tune (typically 30–60 s without load). - Set application parameters:
P0700 = 1(terminals),P1000 = 2(analog setpoint),P1300 = 20(SLVC),P1120 = 10 s,P1121 = 10 s,P2010 = 6(9600 baud USS),P2011 = 31(USS address).
6.4 Method D – STARTER Reinstallation
- Use Control Panel → Programs and Features to uninstall STARTER.
- Delete the residual folders:
C:\Program Files\Siemens\Automation\STARTERandC:\Users\<user>\AppData\Roaming\Siemens\STARTER. - Reinstall STARTER from the official Siemens support package. The latest version supporting MICROMASTER 420 is available as STARTER V5.4 SP5 with the HSP for legacy MM4 drives installed.
- Restore the project file and repeat Method A to refresh the offline image.
7. Verification Procedure
After applying any of the four methods, verify the repair as follows:
-
Write test: Change
P1120ramp-up time from its current value to 11.0 s and back. Both writes should complete without error. - Compare test: In STARTER, choose Online → Compare Values. The summary at the bottom should report 0 differences if you have not actually changed anything.
- Power-cycle test: Power down the drive for at least 30 s. Power up. Re-read the parameter that was changed. It should retain the new value, confirming the EEPROM commit succeeded.
-
Fault buffer test: Read
r0947[0..7]andr2133[0..7]. Neither should contain F0051 (parameter fault) following the test writes. -
Communication test: From a host PLC, perform a read of
P2011[0](USS address) and verify that the response contains the expected value within one polling cycle.
8. Prevention and Best Practices
8.1 Project Hygiene
- Never clone a STARTER project by Windows copy-paste. Use Save As to generate a new project with a fresh internal UUID.
- Always perform Save Project from the STARTER menu – do not rely on auto-save, which can leave intermediate CRCs on disk.
- Enable Automatic Backup of Parameter Sets in Options → Settings → Commissioning so that a daily snapshot of every project’s offline file is kept under
%LOCALAPPDATA%\Siemens\STARTER\Backup. - Maintain a versioning convention: append the firmware version and date, e.g.,
LineA_MM420_V105_20240610.pnx.
8.2 Communication Hygiene
- Use a unique USS address for every drive. Common address allocations: 1–Master, 11–20 – Line 1, 21–30 – Line 2, 31–40 – Pumps, 41–50 – Conveyors.
- Terminate the RS485 bus only at the two physical ends with 120 Ω resistors, not on every node.
- Set
P2014[0]USS telegram off-time to a value larger than the slowest PLC scan (typically 1000 ms). - Run a CRC check on the physical layer by reading
r0052status bit 13 (USS error counter) after each modification cycle. A value > 0 indicates bus noise.
8.3 Commissioning Workflow
- After any parameter change, click Copy RAM to ROM (or set
P0971 = 1) so the value is committed to non-volatile memory. - Cycle the drive offline / online and verify the parameter persists.
- Export the final parameter set to a PDF for records retention: Project → Print → Print to PDF.
- Annotate any non-default parameters with a comment in the offline project; the comment is stored in the project file and survives firmware changes.
9. Related Error Scenarios
| Error Dialog | Most Likely Cause | First Action |
|---|---|---|
| "The drive is not in the correct state to accept this parameter" | Drive running with run command present | Remove ON command; set P0700 = 5 for parameter-only commissioning |
| "Parameter is read-only" | P0000–P0099 access level | Use Expert List to set P0003 = 3 (Expert access) |
| "No connection to the drive" | RS485 address mismatch or termination | Verify P2011[0] and P2010 baud |
| "The parameter is outside the allowed range" | Index out of bounds (e.g., P2011[3] when only [0..1] exist) | Use the index selector in Expert List |
| "Parameter cannot be written while motor is rotating" | Drive in run with r52 bit 0 = 1 | Stop the drive via P0840 = 0 or OFF1 |
| "The value entered is not a multiple of the parameter step size" | Invalid step (e.g., P1120 accepts 0.01 s only) | Round to step size; refer to parameter list in the manual |
10. Reference Material
- Siemens MICROMASTER 420 product support page – firmware downloads, manuals, FAQs.
- STARTER commissioning tool download and release notes – latest SP that retains the legacy MM4 support package.
- MICROMASTER 420 operating instructions (PDF) – complete parameter list, fault codes, and BICO diagrams.
Why does STARTER reject parameter changes on one MICROMASTER 420 but accept them on a second identical drive?
The drive hardware is almost always healthy. The rejected drive is using a corrupted offline parameter file (the project on the PC), so the offline CRC no longer matches the parameter set STARTER expects. Re-uploading the parameters from the live drive rebuilds the offline image and unblocks writes; this is the same recovery that worked when swapping the USS address between two drives to refresh the offline copy.
What is the difference between P0970 and P0971 on a MICROMASTER 420?
P0970 = 1 triggers a factory reset that clears every parameter back to the Siemens default, while P0971 = 1 copies the current RAM parameter set into non-volatile EEPROM so the changes survive a power-cycle. Use P0971 after every parameter change that must persist, and use P0970 only when you intend to start over with factory defaults.
How can I tell if the USS bus has a collision that is causing the parameter change error?
Read P2011[0] (USS address) from every drive on the bus; any duplicate address will cause two drives to reply to the same poll and produce a CRC error in STARTER. Also read r0052 status bit 13 – a non-zero counter confirms that the bus is reporting CRC faults, and a wiring inspection (polarity, shield, 120 Ω termination at the two ends only) usually resolves it.
Can I keep using an old STARTER project file after a firmware update on the MICROMASTER 420?
Only if the firmware and the offline file are reconciled. After a firmware update, perform Upload from Target Device (HW) so STARTER rebuilds the offline image with the new parameter schema. Skipping this step leaves the project pointing at a parameter set that no longer exists in the drive, and the "error during change parameter" dialog returns.
Is there a way to change MICROMASTER 420 parameters without STARTER at all?
Yes. The Basic Operator Panel (BOP) and the Advanced Operator Panel (AOP) both allow direct numeric parameter entry. From a host controller you can also use USS telegrams over RS485 (terminals 29/30) or MODBUS RTU (terminals 29/30 with the integrated MODBUS option) with PKW word pairs to read and write parameters. For larger fleets, SIMATIC PDM supports the MM420 and provides a similar offline/online workflow to STARTER.