SINAMICS G120C 87Hz Configuration: Parameters and Commissioning

David Krause18 min read
SiemensTutorial / How-toVFD / Drives
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Overview: What 87Hz Operation Is and When to Use It

The 87Hz characteristic is a constant-torque operating mode that allows a standard 50Hz induction motor to deliver 1.73 times its nameplate power without exceeding its rated current. It achieves this by reconnecting a 400V/50Hz motor in Delta (so its phase voltage is 230V), then driving it from a 400V inverter that has been programmed to ramp the output up to 87Hz. The 87Hz limit is not arbitrary; it is the frequency at which the inverter's output V/Hz ratio (400V / 87Hz = 4.6 V/Hz) equals the motor's Delta-connected V/Hz ratio (230V / 50Hz = 4.6 V/Hz), preserving constant flux.

This mode is heavily used in:

  • Conveyor systems where a single oversized drive must power multiple small motors in parallel
  • Centrifugal pumps and fans where increased speed delivers more flow at the same mechanical envelope
  • Mixers, extruders, and machine tool spindles where the operator needs headroom above 50Hz for process tuning
  • Replacement of older pole-changing Dahlander motors

Two factors make this mode attractive. First, the motor delivers the same continuous torque as it would in standard 50Hz Star operation, but at up to 1.73x the speed, so mechanical power scales by 1.73x. Second, a 230V Delta motor driven from a 400V DC bus system can be fed from a 400V drive without an output transformer. The trade-off is that the drive must be sized to deliver the higher current, and the motor must be wired in Delta at the terminal box, not Star.

Critical constraint: 87Hz operation is only valid with linear U/f control (P1300 = 0 or 2 with Eco disabled). Flux monitoring, sensorless vector, and slip compensation are incompatible because the drive interprets motor data as the 50Hz rating while the operating flux is held at the same 50Hz value above 50Hz instead of being weakened.

The 87Hz Theory: V/Hz, Delta Connection, and the √3 Relationship

A three-phase induction motor's electromagnetic torque is proportional to V/Hz. Above base frequency, the supply voltage is capped at the DC bus limit, so V/Hz falls and torque falls proportionally with speed (the field-weakening region). The 87Hz trick preserves V/Hz above 50Hz by changing the motor's geometry:

Configuration Phase voltage at 50Hz V/Hz ratio Maximum useful frequency
400V motor in Star 400V / √3 = 230V 8.00 V/Hz 50Hz (then field-weakening)
230V motor in Delta 230V 4.60 V/Hz 87Hz (V/Hz held constant to 400V drive ceiling)

The 1.73 (√3) factor appears twice:

  1. Voltage ratio: 400V line-to-line ÷ 230V phase = √3
  2. Frequency ratio: 87Hz ÷ 50Hz = 1.74 ≈ √3

Mechanical consequences:

  • Speed: 1.73× the nameplate 50Hz speed (e.g., a 4-pole 1450 rpm motor at 50Hz runs at ~2500 rpm at 87Hz)
  • Torque: equal to nameplate torque (because V/Hz is preserved and current is preserved)
  • Power: torque × speed = 1.73× nameplate (e.g., a 4kW Delta motor delivers ~6.9kW at 87Hz)

The slip at 87Hz also rises, which is why motor cooling matters. A TEFC (totally enclosed fan-cooled) motor at 2500 rpm is being cooled by a fan that is moving 1.73× the air mass but the motor surface heat is now 1.73× the dissipation. A separately force-ventilated (IC416) motor is recommended for continuous 87Hz duty, or duty cycle must be reduced.

Prerequisites and Site Audit Checklist

Before changing any parameters, gather the following on site. Most 87Hz installations fail because one of these is overlooked.

  1. Motor nameplate data for every motor on the drive, with photo of each plate. Capture kW, V, A, Hz, rpm, cos φ, insulation class, and IP rating.
  2. Terminal box wiring photo and re-identification of the bridge links. A 400V/690V motor typically has links for Star; a 230V/400V motor has links for Delta. Confirm against the motor's data sheet, not just the rating plate.
  3. Number of motors in parallel, cable run from drive to each motor junction box, and any output reactors, dU/dt filters, or sine-wave filters in the line.
  4. Drive part number including the Control Unit suffix (e.g., 6SL3210-1KE18-8AF1) and firmware version (read with r0018 or via the BOP-2 / IOP status screen).
  5. Total motor current: sum of rated currents in the Delta connection. This is the figure the drive's current limit must be set against, not the Star rating.
  6. Mechanical load envelope: max speed, max torque, duty cycle, and any gearbox ratio. Operating above 50Hz may push the load past its design limit.
  7. Cooling: standard TEFC at 1.73× speed generates 1.73× windage loss in the rotor and 1.73× iron loss; verify TENV or IC416 ventilation is sufficient.
  8. Cable capacitance: long motor cables (>50m) cause high dV/dt charging currents that can trip the drive or destroy the motor insulation. For 87Hz installations with long cables, add a dU/dt filter (e.g., Siemens 6SL3202-0AE...) or sine-wave filter (6SL3202-0BE...).
Document source: The official Siemens procedure for parameterizing the 87Hz characteristic on the G120 / G120D / G120P / G120C family with Control Unit CU230P-2 / CU240E-2 / CU240S-2 from firmware V4.6 is described in Siemens support entry 88963613. Use this as the canonical reference for firmware-specific behavior on the G120C platform.

Drive Sizing Rule: The "Two Sizes Up" Constraint

For a 87Hz installation, the inverter must deliver 1.73 times the motor's rated current continuously. If the drive is rated at exactly the sum of motor nameplate currents, the I²t thermal model will trip on F07901 within minutes because the drive cannot source enough current to feed all parallel motors at their Delta rating while the motor voltage is held to 400V at 87Hz.

The field-proven rule is:

Drive continuous current rating ≥ 1.3 × sum of motor Delta rated currents (for single motor, this is the motor's own Delta current).

For parallel motors where the mechanical load is balanced, Siemens and most drive integrators recommend oversizing the drive by at least one frame size, and often two frame sizes. For example, three 4kW Delta motors (each ~17A at 230V) draw ~51A together. A drive rated at 62A (typically 30kW / 400V) is borderline; a 75A drive is the practical minimum, and 90A (37kW) is preferred for headroom.

Total motor power (Delta) Total motor current Minimum drive rating Recommended drive rating
5.5 kW 21 A 11 kW (25A) 15 kW (32A)
11 kW 42 A 22 kW (50A) 30 kW (62A)
22 kW 84 A 37 kW (90A) 45 kW (110A)
45 kW 170 A 75 kW (178A) 90 kW (210A)

If the drive is already installed at the sum-of-motors rating, the practical resolution is to add a bypass circuit so a smaller subset of motors runs at 87Hz, or to add active current sharing between drives.

Motor Wiring: Confirming Delta Connection at the Terminal Box

The motor terminal box must be rewired from Star to Delta. This is the single most common source of overload trips on 87Hz retrofits because the motor is left in Star while the drive is set for 87Hz, drawing 1.73× the expected current.

For a typical IEC low-voltage motor terminal box with six studs labelled U1, V1, W1, U2, V2, W2:

Connection Link configuration Phase voltage at 400V line Phase current at 50Hz
Star (Y) Short U2-V2-W2; feed U1-V1-W1 400V / √3 = 230V I_line / √3
Delta (Δ) Short U1-W2, V1-U2, W1-V2; feed U1-V1-W1 400V I_line

Re-check the nameplate. If the motor shows 230/400V, the nameplate's 400V rating is for Star operation; the motor must be Delta. If the motor shows 400/690V, it is already wound for Star at 400V and is not suitable for 87Hz without rewinding.

Warning: A motor with 400/690V windings run from a 400V supply in Star is a normal 50Hz motor. If the drive is then reconfigured for 87Hz, the motor will accept the 87Hz frequencies but will saturate magnetically and draw excessive current because the phase voltage (230V) is correct for 50Hz Star, not for the lower V/Hz curve of the 87Hz configuration. Trip on F07901 motor overload typically follows within a few minutes. Do not change drive parameters without first confirming the motor winding.

Parameter Map for the SINAMICS G120C

The following parameters must be entered for correct 87Hz operation on a G120C with CU230P-2, CU240E-2, or CU240S-2 (FW V4.6 or higher). All parameters reside in Drive Data Set 0 (DDS0) unless multi-motor Data Set switching is used. The procedure below is consistent with Siemens support entry 88963613.

Parameter Name 87Hz value Comment
P0300[0] Motor type selection 1 Induction motor (asynchronous)
P0301[0] Motor code number 0 Use free parameter entry (not from motor list)
P0304[0] Motor rated voltage 230 V Delta connection phase voltage, NOT 400V
P0305[0] Motor rated current I_motor,Delta (A) Nameplate value in Delta configuration
P0307[0] Motor rated power P_motor (kW) Same as nameplate; 87Hz does not change the nameplate power figure, only the operating point
P0308[0] Motor rated cos φ 0.80-0.90 Nameplate value
P0309[0] Motor rated efficiency 0.85-0.95 Nameplate value; auto-calculated if 0
P0310[0] Motor rated frequency 50 Hz Stays at 50Hz; this is the corner-point frequency
P0311[0] Motor rated speed nameplate rpm Speed at 50Hz, before slip
P0314[0] Motor pole pair number auto Calculated from P0310 and P0311
P0320[0] Motor magnetizing current auto Auto-calculated from P0305 × ~0.6
P1080[0] Minimum frequency 0 Hz Lower operating limit
P1082[0] Maximum frequency 87 Hz Critical: do not enter 100 or 50 here
P1120[0] Ramp-up time 10-30 s Adjust to load inertia; 87Hz loads accelerate fast
P1121[0] Ramp-down time 10-30 s Match to P1120 or load-dependent
P1300[0] Open-loop control mode 0 Linear U/f without voltage boost — mandatory
P1310[0] Voltage boost continuous 0 % Must be 0; any boost saturates the motor above 50Hz
P1311[0] Voltage boost accel 0 % Must be 0
P1312[0] Voltage boost starting 0 % Must be 0
P1320[0] Slip compensation 0 % Must be 0; not used in 87Hz mode
P1321[0] Slip compensation limit 0 % Must be 0
P1335[0] Slip compensation V/f 0 % Must be 0
P2000[0] Reference frequency 87 Hz Sets 100% reference for analog/PID
P2001[0] Reference voltage 400 V 100% voltage reference
P2002[0] Reference current P0305 100% current reference
P0640[0] Current limit 150 % Default; raise to 200% if motor transient demands
P0290[0] Power unit overload response 0 or 1 0 = reduce frequency, 1 = trip. Choose by load
P0292[0] Power unit overload warning 95 % Threshold for I²t warning

After entering these values, run a motor identification (P1900 = 2) and accept the calculated motor data, then verify the new P0320 magnetizing current is reasonable (typically 0.4-0.6 × P0305).

STARTER and TIA Portal Commissioning Procedure

Siemens support entry 88963613 specifies commissioning via STARTER. For TIA Portal (used on G120C firmware V4.7+ and on all projects configured in TIA V13 SP1 or later), the same parameter set applies but the navigation is different.

Procedure with STARTER (classic)

  1. Open STARTER, go online with the G120C, and create a new project offline if needed.
  2. In the configuration tree, double-click Control Unit → Commissioning → Configuration wizard.
  3. Select the appropriate power unit, set the line supply (3-ph 400V), and choose the motor standard (IEC).
  4. Enter motor data, leaving P0304 at 230V for the Delta connection, P0305 at the motor's Delta current, and P0310 at 50Hz.
  5. Set the application class to Standard Drive Control (SDC) (linear U/f) — do not select Dynamic Drive Control or vector modes.
  6. In the Setpoint channel page, set P1082 = 87Hz and P2000 = 87Hz.
  7. Skip the function module selection (no safety, no Braking Module unless required).
  8. Click Finish and execute RAM to ROM (copy RAM to ROM) before going online.
  9. Connect online, perform Motor identification with P1900 = 2 (still) and run the drive with a no-load ramp to 87Hz. Confirm the actual frequency reaches 87Hz and the current is within P0305.
  10. Save the project to the drive's MMC card (if fitted) and to the PG/PC.

Procedure with TIA Portal (HSP for G120C)

  1. Open TIA Portal, install the G120C Hardware Support Package if not already present (HSP for SINAMICS G120C V4.7 SP3 or later).
  2. Insert the G120C into the device configuration with the correct order number (e.g., 6SL3210-1KE21-7AF1 for a 7.5kW 400V unit with PROFINET).
  3. Open Device view → Parameters, switch to the Parameter view (not the wizard).
  4. Navigate to Motor data and enter P0304 = 230, P0305 = motor Delta current, P0307 = nameplate kW, P0310 = 50.
  5. In the Setpoint / ramp-function generator area, set P1082 = 87, P1120 = 20, P1121 = 20.
  6. Under V/f control, set P1300 = 0 and explicitly zero out P1310, P1311, P1312, P1320, P1321.
  7. Compile and download to the drive's non-volatile memory.
  8. Execute a motor identification run and a 5-minute loaded test, monitoring r0027 (actual current), r0024 (output frequency), and r0034 (motor thermal load).
STARTER vs TIA Portal: For firmware V4.6 and earlier, STARTER is the only commissioning tool. For V4.7 and later, both STARTER and TIA Portal (with the G120C HSP) are supported. TIA Portal does not include the dedicated 87Hz commissioning wizard that STARTER provides, so all parameters must be entered manually from the table above.

Multi-Motor Configuration: Parallel Motors on One Drive

The original enquiry on the Siemens support thread concerns multiple motors on a single G120C. The drive has no concept of "parallel motors" in the parameter set; it sees one equivalent motor with an equivalent current. The commissioning engineer must aggregate motor data:

  1. Equivalent current P0305 = sum of all motor Delta-rated currents. For three 5.5kW Delta motors each rated 21A, P0305 = 63A.
  2. Equivalent power P0307 = sum of all motor nameplate kW. 16.5 kW for the above example. This is what the drive's I²t model uses to scale thermal capacity.
  3. Total cable length = sum of all branch cables to the furthest motor for purposes of the output filter selection. Above 50m total, add a dU/dt filter. Above 100m, add a sine-wave filter.
  4. Current limit P0640 must be raised to the sum of the motors' stall currents (typically 6× rated for an induction motor inrush) to allow cold starts. For a single 21A motor, P0640 = 150% means 31.5A limit; for three motors summed, P0640 = 200% means 126A, which is within the headroom of a 30kW drive (62A) — confirming the need to oversize the drive by 2 frames as described above.
  5. Single motor data set only. Do not use DDS switching for parallel motors, because the thermal model is a single accumulator. If individual motor protection is required, install a thermal overload relay (e.g., Sirius 3RB22) at each motor.
Configuration P0304 P0305 P0307 P0310 P1082 P1300
Single 5.5kW motor at 50Hz, Star 400 11.3 5.5 50 50 0
Single 5.5kW motor at 87Hz, Delta 230 21 5.5 50 87 0
Three 5.5kW motors at 87Hz, Delta in parallel 230 63 16.5 50 87 0

Verification, Commissioning Tests, and Oscilloscope Checks

After commissioning, perform the following verification steps in order. If any step fails, return to the parameter table and re-check.

  1. No-load ramp test: with the motor uncoupled, ramp from 0 to 87Hz over 30s. Confirm the drive output voltage tracks 4.6 V/Hz throughout (e.g., at 30Hz, expect ~138V line-to-line). The IOP or BOP-2 should display output frequency r0024, output voltage r0025, and output current r0027.
  2. Loaded run at 50Hz: with load applied, measure r0034 (motor thermal model utilization). At rated current, this should be 80-100% after 30 minutes. If it climbs above 100% and trips, P0305 is set too low or the motor wiring is still in Star.
  3. Loaded run at 87Hz: hold for 15 minutes at full load. Watch r0034 and r0035 (drive thermal utilization). Both should stabilize below 100%. If r0035 climbs, the drive is undersized and a larger frame is required.
  4. Insulation check: with the drive disconnected, megger the motor windings phase-to-phase and phase-to-ground at 500V. A 230V Delta motor should show >100 MΩ.
  5. Vibration survey: 87Hz operation puts a 4-pole motor at ~2500 rpm, which is often above the first lateral critical of standard motor frames. If vibration exceeds 4.5 mm/s RMS per ISO 10816, re-balance the rotor or constrain the operating window to 70-75Hz.
  6. Acoustic check: 87Hz operation is typically 6-8 dBA louder than 50Hz due to higher switching harmonics and 1.73× magnetostriction. Confirm the noise is within the site's environmental permit.
Verification value - r0034: If r0034 climbs above 100% and the drive trips with F07901 within 5 minutes of a loaded run, do not increase P0290 (overload response) to suppress the trip. The correct fix is to (a) verify the motor is wired in Delta at the terminal box, (b) verify P0304 is 230V not 400V, and (c) verify the drive is sized to deliver P0305 continuously.

Fault and Warning Code Reference

The most relevant G120C fault codes for 87Hz installations:

Code Meaning 87Hz root cause Resolution
F07901 Motor overload (thermal model) Motor wired in Star; P0304 = 400V instead of 230V; drive undersized for parallel motors Re-wire motor in Delta; correct P0304 to 230V; oversize drive
F07902 Motor stalled Load torque exceeds available torque at 87Hz; voltage boost left non-zero (P1310/P1311/P1312) Reduce maximum frequency; set P1310=P1311=P1312=0
F07910 Motor overtemperature (PTC/KTY) TEFC motor at 87Hz with blocked or restricted airflow Add external ventilation or reduce P1082 to 75-80Hz
A07910 Motor overtemperature warning Same as F07910, but warning threshold not trip Same
F07801 Inverter overcurrent Output filter not configured correctly; long cable charging current Add dU/dt filter; check cable length P0230
F30002 DC link overvoltage Ramp-down time too short; regenerative load at 87Hz Extend P1121; add braking resistor; enable DC-link controller
F30003 DC link undervoltage Supply dip on heavy load step Check line quality; increase P0295 (line dip response time)
F30011 Line phase failure One phase lost on supply; motor runs on two phases Check fuses; verify line monitor P0280
F30017 Power unit overload Drive I²t model tripped; drive undersized for the total motor current Oversize drive; reduce P0292 threshold to 80% and raise alarm
F08501 PROFINET communication failure PLC stopped; 87Hz drive lost setpoint Check PLC state; configure P2040 watchdog

For each fault, capture the diagnostic buffer (read r0947 indexed 0-7) and the timestamp r0949 before acknowledging, because the buffer is overwritten on the next fault.

Troubleshooting Matrix

Symptom Probable cause Diagnostic Corrective action
Trips F07901 within 5 minutes of loaded run Motor in Star, not Delta Power down, check terminal box links with multimeter on continuity Rewire motor to Delta (short U1-W2, V1-U2, W1-V2)
Trips F07901 with motor in Delta P0304 set to 400V instead of 230V Read P0304 on BOP-2 / IOP Set P0304 = 230
Trips F07901 with P0304 correct Drive undersized; sum of motor currents exceeds drive rating Read r0027, compare to P0305. If r0027 ≈ P0305, drive is at limit Oversize drive by 1-2 frame sizes; reduce number of parallel motors
Motor stalls at 60-80Hz under load Voltage boost left enabled (P1310, P1311, P1312) Read P1310-P1312 Set all three to 0%
Motor runs at 50Hz instead of 87Hz maximum P1082 not changed from 50Hz Read P1082 on BOP-2 Set P1082 = 87
Overcurrent trip F07801 at high frequency Long motor cable causing capacitive current Measure cable length, check P0230 Add dU/dt filter (Siemens 6SL3202-0AE...) or sine-wave filter (6SL3202-0BE...)
Motor winding failure after weeks of running Voltage boost saturating motor above 50Hz Check nameplate; verify P1310 = 0 Reset P1310 = 0; megger test windings; replace motor
Drive runs but won't accept speed reference above 50Hz P2000 not raised; analog input scaled to 50Hz Read P2000 and analog input scaling P0757-P0760 Set P2000 = 87; verify analog scaling 0-10V = 0-87Hz
Vibration above 4.5 mm/s at 87Hz First lateral critical of motor frame Vibration FFT analysis Restrict P1082 to 75-80Hz; balance rotor
High acoustic noise at 87Hz (8+ dBA above 50Hz) Magnetostriction and PWM harmonics Sound level meter; PWM frequency read in P1800 Acceptable if below site limit; otherwise reduce P1800 to 4kHz for lower loss at cost of torque ripple

What does P0304 have to be set to for 87Hz operation on a SINAMICS G120C?

Set P0304 to 230 V, the Delta-connected phase voltage of the motor. Do not enter 400 V; if P0304 is left at 400 V, the drive applies 400 V at 50 Hz, doubling the motor's flux, saturating the iron, and tripping F07901 motor overload within minutes. The 400 V line voltage is the drive's output ceiling, not the motor's nameplate.

Why does my drive trip F07901 motor overload on 87Hz even with P0304 set to 230 V?

Three common causes: (1) the motor is still wired in Star at the terminal box — confirm with a continuity check on the bridge links, (2) P0305 is set to the Star current rather than the Delta current (the Delta current is 1.73 times the Star current), or (3) the drive is undersized for the total current of all parallel motors. For parallel motors, the drive must be sized to deliver the sum of the motors' Delta rated currents continuously, typically one or two frame sizes above the sum of motor nameplate kW.

Can I use 87Hz mode with vector control (P1300 = 20 or 21) on the G120C?

No. 87Hz operation requires linear U/f control with P1300 = 0 (or 2 with Eco mode disabled). Vector control, sensorless vector, and Flux Current Control are incompatible because the field model assumes a 50 Hz corner-point with a 400 V phase voltage. Running vector control on a 230 V Delta motor with 87 Hz corner frequency produces flux errors and unstable current. Siemens' official 87Hz commissioning document for the G120C family (support entry 88963613) specifies linear U/f as a hard requirement.

How do I parameterize the 87Hz characteristic on a G120C with firmware V4.6 or higher?

Use the procedure in Siemens support entry 88963613 with STARTER, or manually enter the parameter table in TIA Portal using the G120C Hardware Support Package. The key values are: P0304 = 230 V, P0305 = motor Delta current, P0310 = 50 Hz, P1082 = 87 Hz, P1300 = 0 (linear U/f), and P1310, P1311, P1312, P1320, P1321 = 0 (no boost, no slip compensation). Then perform a motor identification (P1900 = 2) and verify with a no-load ramp to 87 Hz.

Is a 400/690V Star motor suitable for 87Hz operation on a G120C?

No. A 400/690V motor is wound for Star at 400V (690V for Star on 690V systems). Reconnecting it in Delta would apply 400V to a winding rated for 230V phase voltage, destroying the insulation. The 87Hz characteristic requires a 230/400V motor (i.e., a motor with 230V Delta and 400V Star ratings) reconnected in Delta. Verify the nameplate shows 230/400V (or 220/380V, the legacy IEC standard) before commissioning.

Back to blog