Problem Overview
The Siemens MICROMASTER 420 (MM420) inverter with firmware release V1.3 cannot establish a reliable commissioning link to DriveMonitor V5.05 on a laptop using the legacy Micromaster /PC inverter connection kit (order number 6SE6400-1PC00-0AA0). Other MM420 drives on the same bench running firmware V1.2 connect without issue. In the DriveMonitor "Establish USS Connection" dialog, the MM420 V1.3 is detected by its USS node address but the firmware version field is left blank, and parameter upload either hangs or terminates with a protocol error.
This is a classic firmware / tool version mismatch symptom. DriveMonitor V5.05 (build 5.05.02.00) was released against the MM4 parameter set baseline that shipped with firmware V1.x through V1.2.x. The V1.3 firmware introduced object-table revisions and additional parameter scaling on the MM420 that V5.05 of DriveMonitor does not fully recognise, which is why the version is reported as empty and the parameter read returns partial / corrupted data.
Affected Products and Versions
| Component | Identified Version | Status |
|---|---|---|
| MICROMASTER 420 (6SE6420-2xx) | Firmware V1.3 (build 1.3.x.x) | New shipment |
| MICROMASTER 420 (6SE6420-2xx) | Firmware V1.2 (build 1.2.x.x) | Working |
| DriveMonitor | V5.05 (5.05.02.00) | Limited / no V1.3 support |
| DriveMonitor | V5.5 / V5.5 HF1 | Recommended for MM4 V1.x |
| STARTER | V4.3 / V4.4 / V4.5 | Recommended for V1.3 and later |
| STARTER (SINAMICS Startdrive) | V15 / V16 / V17 in TIA Portal | Recommended for V2.x and later |
| PC inverter connection kit | 6SE6400-1PC00-0AA0 | RS232-to-RS485, opto-isolated |
Root Cause Analysis
Three independent factors converge in this fault signature. Each must be ruled out before replacing hardware.
1. DriveMonitor V5.05 Firmware Descriptor Limitation
DriveMonitor V5.05 ships with a parameter descriptor database (*.dva / *.ddb) that targets the MM420 parameter set as it existed at V1.0 / V1.1 / V1.2. The blank version field in the "Establish USS Connection" dialog confirms that V5.05's drive identification routine receives a firmware identifier string it cannot parse. The drive is visible because the USS broadcast poll (address 0 or 31, depending on configuration) is transport-level and does not require descriptor knowledge. The moment DriveMonitor tries to read the parameter description, the request either times out or returns an error block because the V1.3 firmware responds with a different object dictionary layout.
2. USS Protocol Parameter Mismatch
Both sides of the link must agree on baud rate, parity, number of stop bits, and the PKW / PZD frame length. MM420 firmware V1.3 defaults to:
- P2010 = 6 (baud rate 9600 bit/s) — parameter
P2010[0] - P2011 = 2 (USS PZD length = 2 words)
- P2012 = 127 (USS PKW length = variable, 4-word max)
- P2013 = 2 (USS telegram off-time = 2 ms)
- P2014 = 1000 (USS telegram failure time = 1000 ms)
- P2015 = 1 (USS PKW stop bits / parity = 1 stop bit, no parity is set by P2015; parity is fixed at none on the MM420)
If DriveMonitor is configured for 19200 bit/s (P2010 = 7) while the drive is at 9600, the drive still appears in the search dialog (because search uses a slower fallback scan) but parameter read/write fails silently.
3. PC Interface Hardware / Driver Layer
The 6SE6400-1PC00-0AA0 kit contains a USB-to-RS485 or RS232-to-RS485 isolator depending on the revision. Driver issues, COM-port renumbering after a Windows update, or a power-state change in the USB hub all produce the intermittent behaviour reported ("sometimes I have to restart the computer").
Pre-Change Compatibility Matrix
| Drive Firmware | DriveMonitor 5.05 | DriveMonitor 5.5 / HF1 | STARTER 4.3 | STARTER 5.x / Startdrive |
|---|---|---|---|---|
| MM420 V1.0 – V1.2 | Supported | Supported | Supported | Limited |
| MM420 V1.3 | Not supported | Partial / intermittent | Supported | Supported |
| MM420 V2.0 and later | Not supported | Not supported | Partial | Supported |
| MM430 / MM440 V1.x | Supported | Supported | Supported | Supported |
| MM430 / MM440 V2.x and later | Not supported | Not supported | Supported | Supported |
Hardware: Building the USS Link
The MM420 exposes its USS / RS485 interface on terminals 29 (P+) and 30 (N-) on the control terminal block. The 6SE6400-1PC00-0AA0 PC inverter connection kit terminates to the same two pins.
- Power down the MM420. Verify the DC bus is discharged before opening the terminal cover.
- Strip 8 mm of insulation from the USS conductors. The MM420 terminals are caged-clamp / screw-less; insert a 2.5 mm flat-blade screwdriver to open the cage.
- Connect the kit's
P+lead to terminal 29 andN-to terminal 30. Maintain polarity throughout the bus. - For a point-to-point laptop connection, leave the kit's bus terminator (typically a jumper marked
TERMor a 120 Ω resistor across 29/30) in the ON position. - If the drive is the last device on a multi-drop USS bus, the on-board terminator must be enabled via DIP switch / jumper (refer to the MM420 Operating Instructions for the exact location per frame size).
- Connect the kit's USB / RS232 end to the PC. Allow Windows to enumerate the COM port; record the assigned
COMxnumber.
Software: Configuring DriveMonitor V5.05
If you must remain on DriveMonitor V5.05 because of a legacy install base, the configuration below is the only one that can establish a usable V1.3 link. Most users should, however, migrate to STARTER.
- Launch DriveMonitor V5.05 with administrator rights. On Windows 10 / 11, the tool requires elevated rights to access the COM port.
- Select Online → Establish USS Connection.
- Set the COM port to the value Windows assigned to the 6SE6400-1PC00-0AA0 kit (Device Manager → Ports).
- Set baud rate to
9600 bit/s(matches P2010 = 6). Do not auto-scan; DriveMonitor's auto-scan can lock the bus when V1.3 firmware is present. - Set the USS node address to
0for first contact, then refine to the drive's P2011 / address parameter once the drive is identified. - Click Read Drive Parameters. If the read returns an error, the firmware is incompatible — proceed to the STARTER section below.
Software: Configuring STARTER V4.3 or Later (Recommended)
STARTER is the supported commissioning tool for all MM4 firmware releases from V1.0 through V2.x. The recommended path for an MM420 V1.3 is STARTER V4.3 with service pack SP3 or later, or STARTER V5.x. Newer TIA Portal versions ship SINAMICS Startdrive as the equivalent plugin.
- Install STARTER from the Siemens support portal. Accept the default installation path; do not change the
starterworking directory if multiple versions are present. - Launch STARTER. Create a new project (Project → New → with navigator).
- Insert a new drive object: Insert → Drive → MICROMASTER 420. STARTER will prompt for the order number (for example
6SE6420-2UD17-5AA1). - Open Set PG/PC interface (menu: Options → Set PG/PC interface). Select the
S7ONLINEaccess point and the correct COM-port device driver for the 6SE6400-1PC00-0AA0 adapter. - Set the bus address to the value stored in drive parameter
P2011(default 0 for point-to-point). - Click Connect to target system (the icon shows a plug and socket). The status bar should read Online.
- Right-click the drive → Upload to PG. This populates the offline project with the V1.3 parameter set, including any V1.3-only parameters.
Parameter-by-Parameter Verification
After the link is up, verify the following parameters via STARTER or DriveMonitor. Values shown are the MM420 V1.3 factory defaults relevant to USS communication.
| Parameter | Name | Default | Required Value | Notes |
|---|---|---|---|---|
| P0003 | User access level | 1 | 3 (Expert) | Some V1.3 parameters are gated to level 3. |
| P0010 | Commissioning parameter filter | 0 | 30 (factory reset) or 0 (ready) | Set to 0 before online edit. |
| P0700 | Source of command | 2 (terminal) | 5 (USS on COM link) | Set to 5 for full PC control. |
| P1000 | Source of setpoint | 2 (analog) | 5 (USS) | Set to 5 for full PC control. |
| P2010[0] | USS baud rate | 6 (9600) | 6 or 7 (19200) | Must match PC. |
| P2011[0] | USS node address | 0 | 0–31 | Unique per bus segment. |
| P2012[0] | USS PKW length | 127 | 127 (variable) | Variable length is required for V1.3 descriptor reads. |
| P2013[0] | USS telegram off-time | 2 ms | 2 ms | Lower = faster fault detection. |
| P2014[0] | USS telegram failure time | 1000 ms | 100–200 ms for bench commissioning | Triggers F0071 on timeout. |
| P2015[0] | USS PZD stop bits / parity | 1 | 1 | No parity, 1 stop bit — fixed on MM420. |
| P2023 | RS485 bus terminator | 0 | 1 (only on last device) | Hardware + parameter must agree. |
Fault Code Reference
The MM420 reports the following faults when the USS link is broken at runtime. The fault word is held in r0947[0..7] and the fault value in r0949[0..7].
| Code | Name | Trigger Condition | Action |
|---|---|---|---|
| F0001 | Overcurrent | Drive tripped during remote command | Check ramp, current limit P0640. |
| F0021 | Ground fault | Output earth leakage | Inspect motor cable. |
| F0035 | Auto restart after n attempts | P1210 restart count exceeded | Clear and inspect root cause. |
| F0041 | Motor data identification failure | Motor ID run aborted | Re-run P1910 = 1. |
| F0051 | Parameter checksum (EEPROM) | Internal CRC mismatch | Power cycle; if persistent, factory reset. |
| F0060 | Asic timeout | Internal hardware watch | Replace drive. |
| F0070 | USS / MODBUS setpoint fault | No setpoint within P2014 | Verify PC transmitting control word 1. |
| F0071 | USS / MODBUS telegram failure | No valid PZD within P2014 | Check COM port, baud, wiring, terminator. |
| F0072 | USS / MODBUS setpoint < P2012 | PKW length violation | Set P2012 = 127. |
Troubleshooting Matrix
| Symptom | Likely Cause | Verify | Fix |
|---|---|---|---|
| Drive visible in "Establish USS Connection" but version blank | DriveMonitor V5.05 cannot parse V1.3 ID string | Check drive nameplate firmware sticker | Switch to STARTER V4.3+ or DriveMonitor V5.5 HF1 |
| Drive not visible at all | COM port / wiring / address mismatch | Loopback test on COM port; check 29 / 30 wiring | Reconnect kit, set correct COM port, restore P2010 = 6 |
| Drive found once, fails after restart | USB enumeration / Windows COM port remap | Device Manager → Ports → check stable COM number | Disable COM-port power management, fix COM number in advanced settings |
| Parameter read returns timeout | P2012 = 0 (single-word PKW) on V1.3 | Read P2012 in expert mode | Set P2012 = 127 (variable) |
| F0071 during runtime | Off-time too short or bus noise | Increase P2013 to 5 ms; inspect shield | Use twisted pair, ground shield at one end only |
| F0072 on first write | PKW length mismatch | Read P2012 | Set P2012 = 127 |
| Control word accepted but motor does not run | P0700 / P1000 not on USS | Read P0700 and P1000 | Set P0700 = 5 and P1000 = 5 |
| STARTER shows drive as "unknown" | Missing device description in STARTER | Insert correct order number | Right-click drive → Properties → enter 6SE6420-... |
| STARTER "Set PG/PC interface" missing COM port | Adapter driver not installed | Device Manager → Ports | Install manufacturer driver for the 6SE6400-1PC00-0AA0 adapter revision |
Step-by-Step Recovery Procedure
- Confirm drive firmware: read
r0018via the operator panel (BOP / AOP). If r0018 reads1.30or higher, DriveMonitor V5.05 will not reliably read parameters. - Back up parameters from the V1.2 drive on the same bench that does communicate. Use DriveMonitor's Parameter → Upload from drive to capture the V1.2 parameter set as a
.dnxfile. - Install STARTER V4.3 SP3 (or later) on the same laptop. The installation can coexist with DriveMonitor; they use independent working directories.
- Configure Set PG/PC interface to the COM port assigned to the 6SE6400-1PC00-0AA0 kit. Test the interface with Diagnostics → Test.
- Create a STARTER project, insert an MM420, enter the exact order number printed on the drive data label.
- Click Connect to target system → Upload to PG. The project navigator should now show the V1.3 parameter set.
- Compare against the saved V1.2 backup. New V1.3 parameters will appear, typically under
P10xxextended setpoint andP20xxUSS extended telegram. - Apply the new project to the drive with Download to target. Tick Copy RAM to ROM if the changes must survive a power cycle.
- Cycle the drive's 24 V control supply (do not short the DC link) and re-verify
r0018shows the same firmware version.
Verification Checklist
- STARTER status bar shows Online with the drive's USS node address.
-
r0018matches the nameplate firmware. -
P0003is reachable at expert level (3) and write-able. - A round-trip parameter read / write completes in < 200 ms at 9600 bit/s.
- Motor accelerates to a 50 Hz reference issued from the PC control word 1 (bit 0 = ON/OFF1, bit 1 = OFF2, bit 2 = OFF3, bit 3 = enable pulse, bit 4 = ramp enable, bit 5 = ramp start, bit 6 = setpoint enable).
- Disconnecting the USS cable with the drive running produces F0071 within 1 s (P2014 default).
- Reconnecting the cable clears F0071 automatically if P1210 = 1 (auto restart enabled).
Long-Term Recommendation
The MM420 reached end of production in 2018 and the recommended successor is the SINAMICS V20 (frame sizes A–E, 1AC 230 V and 3AC 400 V). For new installations using a TIA Portal engineering environment, the V20 with SINAMICS Startdrive provides the same USS-on-RS485 connection profile plus PROFINET. The 6SE6400-1PC00-0AA0 PC inverter connection kit is mechanically compatible with the V20 and the V20 firmware descriptor is fully supported in Startdrive V15 and later.
.dnx file. STARTER and Startdrive can both import the same .dnx file and convert it to a V20 project with minor parameter mapping (P0700/P1000 reset, P2000 default changes).Why does DriveMonitor 5.05 find my MM420 V1.3 but show no version?
DriveMonitor V5.05's drive-identification routine uses a parameter descriptor database built for MM420 firmware V1.0–V1.2. The V1.3 firmware returns an identification string the V5.05 parser does not recognise, so the version field is left blank. The bus-level USS poll still succeeds, which is why the drive is listed.
What is the correct replacement tool for the MM420 V1.3?
Use STARTER V4.3 SP3 (or later) for Windows 7 / 10 environments, or SINAMICS Startdrive V15 or later inside TIA Portal. Both tools fully describe the V1.3 parameter set and can upload directly to the PG.
Can I keep using the 6SE6400-1PC00-0AA0 PC inverter connection kit with STARTER?
Yes. The kit provides a standard RS232 (or USB on later revisions) to RS485 isolated link. STARTER supports any COM port that Windows enumerates, so the kit can be selected under Set PG/PC interface → COMx → Properties.
Which parameters must match between the PC and the drive?
At minimum, P2010 (baud rate), P2011 (USS node address), P2012 (PKW length, set to 127 for V1.3), and P2013 (telegram off-time). Default values of 9600 bit/s, address 0, variable PKW length, and 2 ms off-time work for a point-to-point bench link.
Why does my F0071 fault appear after only a few seconds of cable disconnect?
P2014 sets the telegram-failure time. The default is 1000 ms, but reducing it to 100–200 ms gives faster bench-commissioning diagnostics. Increase it back to 1000 ms before deploying the drive in production to avoid nuisance trips from normal bus latency.
Is the MM420 V1.3 still supported by Siemens?
Spare-parts support for the MM420 was discontinued; the active product is the SINAMICS V20. Service notes and parameter manuals remain available in the Siemens Industry Online Support, but new commissioning should use STARTER or Startdrive.