Troubleshooting S7-1500H PROFINET Redundancy Loss: Send Clock Fix

David Krause15 min read
Industrial NetworkingSiemensTroubleshooting
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

1. Problem Overview

When an SIMATIC S7-1500H redundant controller (CPU 1518H-4 PN or CPU 1517H-3 PN) is configured with PROFINET IO devices inside a PROFINET ring, the station may intermittently report Loss of Redundancy even though both H-CPUs and both redundancy connections are physically intact. The error is most often observed as:

  • Diagnostic buffer entries of type PROFINET IO: Redundancy loss on the IO controller (H-CPU).
  • Flapping S2/R1 partner port status LEDs on the affected IO device.
  • Temporary station failure of one or more PROFINET IO devices on the ring.
  • Re-establishment of the AR (Application Relationship) every few minutes, even though the physical link and fiber/copper paths show no errors.

The root cause is rarely the cable; it is a mismatch between the Send Clock of the PROFINET IO system and the Update Time / Watchdog assigned to the IO devices. In a default TIA Portal configuration, TIA attempts to run the ring at a 1 ms send clock, which is faster than the redundancy update path inside the H-system can reliably service. The H-controller drops the redundancy AR, the ring partner times out, and the field device briefly disappears from the IO controller.

2. Symptoms and Error Indicators

Before changing parameters, confirm that the symptoms are consistent with a send-clock / update-time mismatch rather than a physical layer fault. Typical indicators are:

Indicator Location Typical Value
PROFINET diagnosis Channel diagnosis IO device web server / TIA Online & Diagnostics 0x0001 (Station failure) or 0x001E (AR lost)
Diagnostic buffer event H-CPU > Online & Diagnostics > Diagnostic buffer "PROFINET IO: Loss of redundancy"
Port statistics DiscardedFrames IO device port statistics Counts incrementing rapidly
Cycle time jitter TIA Portal > PROFINET diagnostics > Cycle Bus cycle time spikes > 2x nominal
OB83 / OB86 calls H-CPU user program OB86 triggered on station failure

If the cable is genuinely broken, the PROFINET ring manager (typically the H-CPU on port 1/2) will report a topology change and the diagnosis will be a hard Link down. A send-clock mismatch produces transient failures with the link staying up — the key discriminator.

3. Root Cause: Send Clock and Update Time Mismatch

The PROFINET real-time channel is driven by a base Send Clock (also called the SendCycleTime) that defines the fundamental transmission period. Every IO device in the system is assigned an Update Time, expressed as an integer multiple of the send clock:

Update Time [ms] = Watchdog Factor × Send Clock [ms]

The Watchdog Time on the IO device must be larger than the worst-case round-trip time of the IO controller, which includes the H-redundancy re-send path. On an S7-1500H, every PROFINET frame on the ring crosses the H-backplane twice (primary CPU → secondary CPU → ring), adding a deterministic latency overhead of typically 1.5–3.0 ms relative to a single CPU 1500.

When the user selects the default 1.000 ms send clock and lets TIA compute the Update Time in Automatic mode, TIA frequently picks a 1× or 2× multiplier. With watchdog factors of 3 (the minimum permitted) the resulting watchdog is 3–6 ms, which is shorter than the H-system's worst-case redundancy latency. The IO controller therefore declares an AR (Application Relationship) loss before the redundancy path has a chance to respond, and the IO device enters station failure.

Key insight: The 1 ms send clock is supported by S7-1500H in theory, but the PROFINET ring (managed by the H-CPU with MRP/MRPD) and the redundancy AR processing add jitter that an S7-1500 single CPU does not see. A 4 ms send clock gives the H-system a comfortable jitter budget and eliminates the spurious redundancy loss events.

4. Affected Hardware and Firmware

The phenomenon is documented for the following configuration range. Confirm your hardware matches before applying the parameter changes.

Component Catalog Number (MLFB) Minimum Firmware Recommended Firmware
CPU 1518H-4 PN 6ES7518-4JP00-0AB0 V2.6 V2.9 or newer
CPU 1518H-4 PN (F) 6ES7518-4JP00-0AB0 V2.6 V2.9 or newer
CPU 1517H-3 PN 6ES7517-3HP00-0AB0 V2.6 V2.9 or newer
ET 200SP IM 155-6 PN HF 6ES7155-6AU00-0CN0 V4.2 V4.4 or newer
ET 200MP IM 155-5 PN HF 6ES7155-5AA00-0AB0 V4.2 V4.4 or newer
SCALANCE XC/XB/XR managed switches (MRP) 6GK5... V6.0 Latest

Verify the exact firmware on the SIMATIC S7-1500H using Online & Diagnostics → Diagnostics → CPU Information and on the IO devices with the device's web server (https://<ip>/index.html) or TIA Online & Diagnostics → PROFINET diagnostics.

5. PROFINET Redundancy Architecture for S7-1500H

The S7-1500H supports two PROFINET redundancy modes defined by the PROFINET specification:

Mode Description Typical Use in S7-1500H
S1 Single interface, no redundancy. One AR between controller and device. Non-critical IO devices on the same ring.
S2 Two ARs from one logical controller (one AR per H-CPU), one shared device interface module. Default for S7-1500H with PROFINET ring and managed switches.
R1 One AR is primary, the second AR is a redundant path. Used with Y-switches or shared device IFs. High-availability IO devices with two interface modules.
R2 Two ARs with two physical ports, full parallel redundancy. Not supported by S7-1500H in TIA V17/18 by default.

For the S7-1500H with PROFINET ring (MRP / MRPD), the controller typically uses S2 to maintain a logical AR with each IO device even if one ring segment is interrupted. When the send-clock / update-time mismatch occurs, the S2 partner port flips rapidly between primary and backup, producing the symptom of loss of redundancy without physical link loss.

6. S7-1500H PROFINET Ring Topology

The reference topology is a single PROFINET ring managed by the two H-CPUs (one ring manager, one ring client) plus a shared device with two ports connected to the ring. The SVG below shows the typical arrangement:

CPU 1518H (Primary) PROFINET X1 / X2 CPU 1518H (Backup) PROFINET X1 / X2 SCALANCE Switch 1 SCALANCE Switch 2 ET 200SP / ET 200MP PROFINET ring client Port 1 / Port 2 redundancy ring

Both H-CPUs participate in the ring with port P1 and P2 of the PROFINET interface. The ET 200SP/MP IM closes the ring on port 1 and port 2. With MRP enabled, the ring manager blocks one port logically to prevent loops; when a single segment fails, MRP re-routes in < 200 ms.

7. Solution Procedure

The fix is performed in TIA Portal (V16 or newer) on the offline project of the S7-1500H station, then downloaded to both H-CPUs.

  1. Open the device configuration of the H-station (Devices & Networks → S7-1500H CPU → Device view).
  2. Select the PROFINET interface (X1 or X2) of the H-CPU and open Properties → PROFINET interface → Advanced options → Real time settings → PROFINET IO system.
  3. Change Send Clock from 1.000 ms to 4.000 ms. The other values to consider are 0.500 ms (not recommended on H), 2.000 ms (still risky with many IO devices), and 4.000 ms (recommended).
  4. Click OK to apply the send clock change. TIA will warn that the update times of the IO devices will be re-calculated. Accept the warning.
  5. Select each IO device in the network view and open Properties → PROFINET interface → Advanced options → Real time settings → Update time.
  6. Set Mode from Automatic to Fixed update time.
  7. Set Update Time to 16.000 ms. This corresponds to a 4× multiplier on the 4 ms send clock. Acceptable values in this configuration are 8 ms (2×), 12 ms (3×), and 16 ms (4×); avoid 4 ms (1×) on H-systems.
  8. Repeat steps 5–7 for every IO device in the ring. Use Ctrl+A in the network view to multi-select, then apply the change in bulk if the firmware is uniform.
  9. Verify the Watchdog Time automatically derived by TIA: it should be at least 48.000 ms (3× the 16 ms update time, the minimum allowed by PROFINET spec).
  10. Compile the project (Hardware) and download the configuration to both H-CPUs in RUN with the redundancy function Download to target device → Consistent download.
  11. After the download, perform a redundancy test: force the primary CPU to STOP or pull the primary fiber. The IO devices should remain reachable via the backup CPU with no diagnostic interruption.
Critical: Always change the Send Clock first. If you change Update Time on the IO device before the Send Clock, TIA will re-compute the Update Time and silently re-apply Automatic mode on the next compile.

8. Parameter Reference Table

The following table summarizes the recommended parameter set for the S7-1500H PROFINET ring. Use these values as a starting baseline for H-systems with 5–64 IO devices.

Parameter Location in TIA Default (problematic) Recommended (H) Acceptable Range
Send Clock PN IO → Real time settings 1.000 ms 4.000 ms 0.5 – 4.0 ms
Update Time Mode IO device → Update time Automatic Fixed Fixed / Automatic
Update Time IO device → Update time 1.000 ms (auto) 16.000 ms 4×–64× Send Clock
Watchdog Time Derived (3× Update Time) 3.000 ms 48.000 ms 3×–192× Update Time
Reduction Ratio PN IO → Real time settings 1 1 1–512
MRP role PN interface → Media redundancy Manager (auto) Manager on H-CPU X1, Client on X2 Manager / Client / Off
MRPD (parallel redundancy) PN interface → Media redundancy Off Off (use MRP + S2) Off
IO device redundancy role IO device → PROFINET interface S1 S2 S1 / S2 / R1

The relationship between these parameters is governed by the PROFINET specification. The minimum allowed watchdog is three update cycles. For an H-system with a 4 ms send clock and a 16 ms update time, the resulting 48 ms watchdog is the smallest value that still gives the H-redundancy re-send path time to recover from a single CPU failover.

9. Verification Steps

After applying the fix, run the following verification sequence. Each check should be logged in the commissioning report.

  1. No spurious diagnostic events — leave the system in RUN for at least 24 hours and verify the H-CPU diagnostic buffer shows no Loss of redundancy entries.
  2. Live cycle time — in TIA Portal, open Online & Diagnostics → PROFINET diagnostics → Cycle. The actual bus cycle should be steady at ~4 ms with jitter < 1 ms.
  3. Forced failover — in the SIMATIC Automation Tool or via the H-CPU display, force the primary CPU to STOP. The backup CPU takes over. The IO devices should report no station failure and process data should resume within 100 ms.
  4. Cable break test — physically disconnect one fiber segment of the ring. MRP should reconfigure the ring in < 200 ms; the IO devices should not generate an AR loss.
  5. Diagnostic OBs — in the user program, evaluate OB83 (pull/plug) and OB86 (rack/IO failure) call counts. They should be zero in steady state.
  6. Web server check — on the IO device web page, the redundancy status should remain Primary or Backup consistently without oscillation.

10. Extended Troubleshooting Matrix

Use this matrix when the symptoms persist after the parameter change. Each row identifies a likely cause and the corresponding diagnostic step.

Symptom Likely Cause Diagnostic Step Action
Redundancy loss every few minutes, link stays up Send clock too fast for H-redundancy path TIA → PN IO → Real time settings Set Send Clock = 4.000 ms, Update Time = 16.000 ms (Fixed)
Redundancy loss after H-CPU STOP/START IO device Update Time in Automatic mode Properties of each IO device → Update Time Set Mode = Fixed, Update Time = 16.000 ms
Intermittent loss with CRC errors on port EMC issue on PROFINET cable Port statistics → CRC errors Replace cable, check grounding, set Send Clock = 4.000 ms
Loss only on S2 partner port S2 AR watchdog too short IO device web server → AR status Increase Update Time to 32 ms or 64 ms
Loss after PLC restart, recovers after 10 s MRP not yet converged Switch log → MRP state Verify MRP manager is on the active H-CPU, not on a switch
Loss only on one specific IO device Firmware mismatch on IO device Web server → Device info Update IM firmware to match recommended version
Loss during heavy PROFINET diagnostics (port stats polling) Diagnostics load interferes with RT TIA → Online & Diagnostics Disable continuous diagnostics polling, use snapshot only
Loss on every H-failover Reduction Ratio too high TIA → PN IO → Real time settings Set Reduction Ratio = 1, lower IO device count per AR

11. Best Practices for Stable PROFINET Redundancy on S7-1500H

  • Always start from the Send Clock and work down to the Update Time. Re-compile the project after each change so TIA re-derives the watchdogs.
  • Use Fixed update time on every IO device. Automatic mode assumes a single-controller path and underestimates the H-redundancy latency.
  • Keep the IO device count per AR reasonable. An S7-1500H comfortably supports 64–128 PROFINET IO devices per PN interface, but heavy I/O density (e.g. many ET 200SP with high-channel-density modules) benefits from a 4 ms send clock.
  • Disable MRPD unless you specifically need parallel redundancy. The default S2 over MRP is the most robust topology for S7-1500H rings.
  • Place the MRP manager on the H-CPU, not on an external SCALANCE. This ensures the ring state is consistent with the H-controller state.
  • Document the chosen values in the network diagram. Future service engineers must not revert to the 1 ms default without understanding the H-redundancy timing budget.
  • Use S2 for the ring and R1 only for true dual-IF devices. Mixing S1, S2, and R1 devices in the same ring is supported but increases the diagnostics complexity.
  • Validate the configuration with the TIA Topology Editor. The Topology Editor in TIA Portal can verify the planned ports and avoid miswiring that masquerades as a redundancy-loss event.
  • Update the H-CPU firmware to V2.9 or newer. Earlier firmware versions have longer redundancy re-send paths and may require a 8 ms send clock for stability.
  • Keep the SIMATIC Automation Tool handy for live diagnostic capture during commissioning. It exports PROFINET cycle time history and AR status logs.

12. Additional S7-1500H Redundancy Considerations

Beyond the send-clock and update-time parameters, the S7-1500H redundancy behavior interacts with PROFINET in two specific ways documented in the official S7-1500R/H system manual:

  • Failure of both redundancy connections and the PROFINET cable in the ring — the H-system maintains the AR with the IO device through the H-backplane, but the IO device itself is no longer reachable on PROFINET. The H-CPU logs a station-failure event. This is the worst-case scenario described in the Siemens S7-1500H redundancy scenarios manual.
  • Redundant PROFINET R1 configuration — when an IO device uses two interface modules, each establishes one application relationship with one H-CPU. This is described in detail in the PROFINET in SIMATIC PCS 7 – Guidelines and Blueprints document.

For general PROFINET specification details, refer to the PROFINET leading communication system document published by PI (PROFIBUS & PROFINET International). The PROFINET specification (IEC 61784-2, IEC 61158) is the normative reference for the Send Clock, Update Time, and Watchdog semantics used throughout this article.

13. Sample SCL Code for H-System Redundancy Diagnostics

Use the following Structured Control Language (SCL) snippet in the H-CPU user program to capture redundancy-loss events and forward them to the operator panel. Place the code in OB1 or in a cyclic interrupt OB (e.g. OB30).

// SCL: Capture PROFINET redundancy loss events on S7-1500H
// Variables in the H-station's global DB
VAR
    RedLossCounter   : DINT;   // Increments on every loss of redundancy event
    LastRedLossTime  : DTL;    // Timestamp of last event
    RedLossActive    : BOOL;   // TRUE while a redundancy loss is latched
END_VAR

// Inside OB1 / OB30:
IF "IO_device_1".PROFINET_IO_Device.Status.Redundancy_Loss = TRUE THEN
    RedLossCounter := RedLossCounter + 1;
    LastRedLossTime := RD_SYS_T;
    RedLossActive := TRUE;
ELSE
    RedLossActive := FALSE;
END_IF;

// Reset on operator command
IF "HMI".ResetRedLoss THEN
    RedLossCounter := 0;
END_IF;

The exact tag path for Redundancy_Loss is generated by TIA from the IO device's diagnostic model. In the default configuration the tag is <DeviceName>.PROFINET_IO_Device.Status.Redundancy_Loss.

What Send Clock should I use for an S7-1500H PROFINET ring?

Use 4.000 ms as the Send Clock. The 1.000 ms default is too aggressive for the H-redundancy re-send path and produces intermittent Loss of Redundancy events. Send Clocks of 2.000 ms or 0.500 ms are not recommended on H-systems with more than a handful of IO devices.

Should I use Automatic or Fixed Update Time on the IO devices?

Use Fixed update time. Set it to 16.000 ms when the Send Clock is 4.000 ms (a 4× multiplier). Automatic mode re-derives the Update Time on every project compile and frequently underestimates the H-redundancy latency, leading to watchdog-triggered AR losses.

How do I verify the fix worked?

Leave the system in RUN for at least 24 hours and check the H-CPU diagnostic buffer for "Loss of redundancy" events — it should be empty. Then perform a forced H-failover (primary CPU to STOP) and confirm that the IO devices remain reachable with no station failure. The PROFINET actual bus cycle should be steady at ~4 ms with jitter below 1 ms.

Which IO devices are affected by this issue?

All PROFINET IO devices configured as S2 in an S7-1500H ring can exhibit the symptom. The most common offenders are ET 200SP IM 155-6 PN HF and ET 200MP IM 155-5 PN HF. Devices configured as S1 (no redundancy AR) are not affected by the redundancy-loss event but still benefit from the 4 ms send clock for jitter reduction.

Does the S7-1500H support PROFINET R1 redundancy?

Yes, R1 (one AR primary, one AR backup) is supported. R1 is used with IO devices that have two interface modules — typically ET 200SP with two IMs in the same station. The S7-1500H establishes one AR through each H-CPU. The same Send Clock = 4.000 ms and Fixed Update Time = 16.000 ms rules apply to R1 devices.

What is the relationship between Send Clock, Update Time, and Watchdog Time?

Update Time is an integer multiple of the Send Clock (typically 2× to 64×). Watchdog Time is automatically set by TIA to three Update Times (the PROFINET minimum) up to 192 Update Times. For an S7-1500H, a 4 ms Send Clock, 16 ms Update Time (4×), and 48 ms Watchdog (3×) is the recommended baseline.

What diagnostic buffer entry identifies this fault?

On the H-CPU, the diagnostic buffer shows an entry of type "PROFINET IO: Loss of redundancy" with the affected IO device name and slot. The IO device's own diagnostic buffer or web server shows "AR lost" or "Station failure" with a channel diagnosis of 0x001E or 0x0001. These entries repeat every few minutes when the send clock is misconfigured.

Back to blog