Troubleshooting Motoman XRC Alarm 4303: Converter Ready Signal Error
Problem Details
Alarm 4303 – Converter Ready Signal Error on Motoman XRC, DX, and YRC1000 controller families latches during the servo ON handshake. The controller asserts the servo ON request, but the converter (or a downstream axis servo pack) never returns a valid charge-completion / servo-ready acknowledgment within the controller's polling window. The fault typically appears during mode transitions (manual → automatic, teach → play, or remote → auto) when contactors re-close and the DC bus recharges.
Three operational signatures are documented in the Yaskawa alarm help text and reproduce the fault field reports describe:
- The servo-ready signal is intercepted while servo ON is being asserted.
- The servo-ready signal is not intercepted during servo OFF commanded by an emergency stop.
- While turning servo OFF (at E-stop), the servo-ready signal is incorrectly turned back ON.
The same alarm code is published for the XRC, DX100, DX200, and YRC1000micro platforms. See the official Yaskawa Motoman knowledge base entries for the cross-platform definitions:
- YRC1000micro Alarm Code 4303 – Converter Ready Signal Error
- DX100 Alarm Code 4303 – Converter Ready Signal Error
- DX200 Alarm Code 4303 – Converter Ready Signal Error
Root Cause Analysis
Four root causes are catalogued in the controller alarm help text:
| Cause # | Failure Mode | Mechanism |
|---|---|---|
| 1 | Primary-side power supply voltage too low | DC bus cannot reach the converter's charge-complete threshold before the controller's watchdog expires. |
| 2 | Primary cable voltage drop at servo ON | Cable too small (high gauge) or too long; inrush current from the capacitor bank pulls the line below the 220 V +10% tolerance window. |
| 3 | Defective WRCA01 / WRCF01 circuit board | The interface board between the controller and the converter fails to relay the ready handshake. |
| 4 | Defective converter (SRDA, SJDE, or equivalent axis pack) | Internal charge circuit or gate-drive section fails to assert the ready output. |
Why the Alarm Latches at Mode Change
The mode transition is the most common trigger because the controller momentarily drops the servo-on request to re-initialize axis groups, then re-asserts it. This re-energizes the main contactor(s), which closes the three-phase path to the converter. The converter's soft-charge resistors are bypassed, and the bulk DC bus climbs from the pre-charge level to the full rectified line voltage. Any of the following during that 200–600 ms transition causes the ready handshake to drop:
- Chattering main contactor (mechanically worn, coil voltage marginal, aux contact failing).
- Voltage sag under capacitor inrush.
- Phase imbalance that prevents the converter's three-phase rectifier from achieving rated DC link.
- Stale WRCA firmware that does not match the system version, causing the ready-line debounce to misfire.
Affected Hardware and Signal Path
The ready handshake travels the following physical path on an XRC system:
- Controller backplane (CPU board) → WRCA01 board (backplane I/O).
- WRCA01 → WRCF01 (E-stop / converter interface) board.
- WRCF01 → Converter SRDA-COA series (main axis) or external-axis servo pack.
- Converter → AC contactor coil (K1, K2) which closes the three-phase feed.
- Converter → Ready output contact closes → WRCF01 reads it → WRCA01 → CPU.
Any single open in this chain causes 4303. The fault is most often attributed to the converter, but in field experience a significant fraction of 4303 events trace back to:
- Contactor timing mismatch. Main contactors (often Cutler-Hammer/Westinghouse or Yaskawa-branded) that pull in asynchronously. The phase that closes last briefly back-feeds the DC bus through the rectifying diodes of the other phases, producing a brief imbalance and a momentary ready-signal drop.
- Auxiliary contact oxidation. The contactor's NO aux contact that signals "contactor closed" oxidizes and develops resistance, slowing the rising edge of the ready signal below the controller's debounce time.
- WRCA board firmware revision mismatch. After board swaps the new WRCA carries a different firmware revision that interprets the ready signal with a different debounce constant.
Diagnostic Procedure
Step 1 – Capture Alarm History and Subsystem Tag
From the teach pendant:
- Navigate to
{SYSTEM} → {ALARM} → {HISTORY}. - Record the date/time, the subsystem tag (e.g.,
S1,S2,S3, orR1), and the motion program that was active. - Open the system version screen and capture the controller type, software version, and the WRCA board software version.
The subsystem tag narrows the search to a specific servo pack. S1–S3 typically point to the robot's three axes; an external-axis-only system (where the manipulator is electrically disconnected but its servo pack remains in the cabinet) usually shows the alarm on the tag of the external-axis pack.
Step 2 – Verify Primary Voltage Under Load
Measure phase-to-phase voltage at the converter input terminals with a true-RMS meter while the alarm is active:
| Measurement Point | Nominal | Tolerance | Action |
|---|---|---|---|
| Phase-to-phase, no load | 220 / 380 / 480 V (per nameplate) | +10% / -10% | Read reference baseline. |
| Phase-to-phase, during servo ON | Same | +10% / -10% | Capture inrush sag; values below -10% trip the converter's undervoltage lockout and 4303 latches. |
| Phase-to-phase, phase-to-neutral (if 220 V single-phase derived) | 220 V | +10% / -10% | Detect transformer imbalance. |
Step 3 – Inspect Cable Sizing and Length
For the primary feed, use the following guidance (verify against the controller's installation manual):
| Current Draw (per phase or single-phase line) | Minimum Copper Conductor | Maximum Recommended Length |
|---|---|---|
| ≤30 A | 5.5 mm² (10 AWG) | 15 m |
| 30–60 A | 8 mm² (8 AWG) | 15 m |
| 60–100 A | 14 mm² (6 AWG) | 20 m |
| 100–150 A | 22 mm² (4 AWG) | 20 m |
| >150 A | 38 mm² (2 AWG) or paralleled | Engineering review required |
Voltage drop under inrush must remain below 3% of nominal. Use:
Vdrop = Iinrush × Rcable × L × 2 (round-trip)
where Iinrush is the peak capacitor charging current (typically 2–3× the steady-state input current for 100–300 ms), Rcable is resistance per meter at 20 °C, and L is the one-way cable length.
Step 4 – Inspect the Main Contactor
- De-energize and lock-out the controller.
- Locate the main contactor(s) feeding the converter input. On XRC systems this is typically inside the Yaskawa Power Unit (YPU) cabinet, often labelled
K1/K2. - Measure contact resistance across each pole: >50 mΩ indicates pitting and replacement is justified.
- Inspect the coil for discoloration, swelling, or burnt varnish.
- Apply control voltage and listen/feel for simultaneous pull-in. Asynchronous pull-in is the most common field finding for a 4303 that only appears at mode transitions.
Step 5 – Inspect the WRCA01 / WRCF01 Boards
With power removed:
- Pull the WRCA01 board and inspect the PCB for burnt traces near the converter interface connector (typically
CN-series). - Inspect the WRCF01 board for capacitor leakage, especially electrolytic capacitors in the E-stop and converter interface sections.
- Verify the firmware sticker on the new board (if a spare is available) matches the system version in
{SYSTEM} → {VERSION}.
Step 6 – Isolating External-Axis vs. Robot Converter
On systems with three external axes where the manipulator servo pack remains in the cabinet but the manipulator is mechanically disconnected, isolate the failing converter:
- Disconnect the robot's main axis servo pack from the backplane and the DC bus.
- Power the controller with only the external-axis converter and packs connected.
- Repeat the manual → automatic transition 20 times.
- If 4303 still fires, the converter or interface in the external-axis path is the source.
- If 4303 clears, restore the robot pack and disconnect the external-axis pack; repeat.
This isolation procedure is essential because the alarm help text directs you to "the converter" but does not distinguish robot vs. external-axis. The subsystem tag captured in Step 1 confirms which path.
Solution Tree
Apply the following remediation in order of cost and invasiveness. Each step includes the verification check that confirms you can move to the next.
Solution A – Reset and Re-arm
From the pendant: {ALARM} → {RESET} → {SERVO ON}.
Verification: If the alarm does not recur within ten mode transitions, treat it as a transient and document the time/conditions. Persistent recurrence proceeds to Solution B.
Solution B – Tighten Primary Power Tolerance
- Measure and log the no-load and inrush voltages per Step 2.
- Adjust the upstream transformer tap if a sag is detected.
- Replace undersized primary cabling per the table in Step 3.
- Verify the building's supply transformer is rated for the inrush of the controller plus all other loads on the same feeder.
Verification: Re-run the voltage measurement under load. Voltage must remain within +10% / -10% of nominal throughout the inrush window.
Solution C – Replace Main Contactor(s)
- Replace K1 (and K2 if present) with the OEM-specified equivalent. Yaskawa typically uses Sprecher+Schuh CA7 or equivalent; verify by the cabinet wiring diagram inside the door.
- Replace the contactor's aux contact block if it is separately available.
- Tighten all power lugs to the manufacturer's torque spec (typically 26–35 in-lb for 10 AWG terminations).
Verification: Use a clamp-on ammeter on each phase of the contactor output during a servo ON cycle. The three phases must reach steady-state current within 50 ms of each other. Asymmetry beyond 10% indicates contact wear and the contactor must be replaced again.
Solution D – Replace the WRCA01 Board
- Order the WRCA01 with the firmware revision matching the existing system version. Reference: Yaskawa spare-part catalog.
- Power down and remove the WRCA01 from the backplane.
- Install the replacement; verify seating is fully latched.
- Power up and verify
{SYSTEM} → {VERSION}shows the same revision.
See the published DX100 Alarm Code 4303 Converter Ready Signal Error entry for additional board-replacement context applicable to XRC and DX200 systems.
Verification: Perform 50 manual → automatic mode transitions with a representative motion program loaded. Zero 4303 alarms is the acceptance criterion.
Solution E – Replace the Converter
- Identify the converter part number from the system nameplate (typical XRC converters: SRDA-COA series for the main axis pack).
- Replace as a unit; do not attempt component-level repair of the IGBT module.
- Re-flash or reload the converter parameters from the controller's backup file before servo ON.
Verification: Run the system through the full motion envelope for four hours, including repeated E-stop and reset cycles. Monitor for any ready-signal glitches on the pendant's diagnostic screen.
Verification Procedure
After applying any solution, perform the following comprehensive check:
- Reset the alarm history.
- Cycle the controller power (cold start).
- Run a no-motion program that asserts servo ON, holds for 5 s, then de-asserts. Repeat 10 times. Monitor the ready signal with a scope or the pendant's I/O monitor.
- Run a representative motion program in
{AUTO}mode for at least 30 minutes, including a minimum of five E-stop → reset cycles. - Switch between
{TEACH}and{AUTO}modes 20 times. This is the highest-stress transition and the most likely to expose intermittent contactor or WRCA faults. - Confirm zero 4303 events in
{ALARM} → {HISTORY}after the test sequence.
Troubleshooting Matrix
| Symptom | Most Likely Cause | First Check | Remediation |
|---|---|---|---|
| 4303 only at manual → auto transition | Chattering main contactor | Listen for asynchronous pull-in; measure aux contact resistance | Replace contactor |
| 4303 immediately after board replacement | WRCA01 firmware revision mismatch | Compare board sticker to {SYSTEM} → {VERSION} | Source board with matching firmware revision |
| 4303 plus visible LED flicker on YPU at servo ON | Primary voltage sag under inrush | Measure phase voltage during servo ON | Reduce cable length, increase conductor size, adjust transformer tap |
| 4303 plus E-stop chain intermittently open | WRCF01 board fault | Inspect WRCF01 capacitors; check E-stop loop resistance | Replace WRCF01 |
| 4303 on external-axis tag after reconfiguration to ext-only operation | External-axis converter or its interface | Use isolation procedure (Step 6) | Replace identified converter |
| 4303 plus 4002 / 4009 memory alarm | Backplane communication fault | Re-seat WRCA01 and CPU boards; check ribbon cables | Replace ribbon, re-seat, then replace WRCA01 if persistent |
Related Alarm Codes
4303 frequently appears in conjunction with or is misdiagnosed alongside the following codes. Treat them as a fault cluster:
| Code | Meaning | Relationship to 4303 |
|---|---|---|
| 4002 | Memory error (SV MON signal file) | Same WRCA / backplane path; investigate firmware revision |
| 4009 | Memory error (ARC AUX COND file) | Indicates corrupted system file, often post-board-swap |
| 4107 | Encoder error | May latch during the same servo ON drop as 4303 |
| 4310 | Converter overcurrent | Indicates converter hardware fault distinct from 4303 |
| 1314 | Verify error | Software consistency check failure; verify after WRCA replacement |
Preventive Maintenance
- Quarterly: Measure and log the primary voltage under load. Compare against the baseline; drift >2% triggers a transformer tap review.
- Semi-annually: Inspect the main contactor aux contacts for oxidation; clean or replace as required.
- Annually: Pull and inspect the WRCA01 and WRCF01 boards for capacitor leakage and burnt traces.
- On every WRCA replacement: Document the firmware revision of the board removed and installed. Keep a board-firmware history per controller.
- After any cabinet modification: Re-run the verification procedure (50 mode transitions) before returning the cell to production.
Safety Notes
What does Motoman XRC alarm 4303 mean?
Alarm 4303 indicates the converter's servo-ready signal did not arrive within the controller's expected window during a servo ON transition. It is triggered by low primary voltage, undersized primary cabling, a defective WRCA01 or WRCF01 interface board, or a defective converter.
Does alarm 4303 apply to DX100, DX200, and YRC1000micro controllers?
Yes. The same alarm code (4303, Converter Ready Signal Error) is published for XRC, DX100, DX200, and YRC1000micro controllers. The remediation tree is essentially identical; only board part numbers and converter part numbers differ. Reference the official Yaskawa Motoman knowledge base entries for each platform.
Why does 4303 appear only when switching from manual to automatic mode?
The manual-to-automatic transition momentarily drops and re-asserts the servo ON request, which re-closes the main contactor(s). Asynchronous contactor pull-in, aux-contact oxidation, and DC-bus inrush sag are the three most common field causes of 4303 at this transition.
How do I isolate a 4303 to the robot vs. external-axis converter?
Use the subsystem tag from {ALARM} → {HISTORY} first. Then physically disconnect one converter at a time and repeat the manual-to-automatic transition 20 times. The path that fails when isolated is the failing converter.
Can a WRCA01 board firmware mismatch cause 4303?
Yes. The WRCA01 board carries firmware that interprets the ready signal with a specific debounce constant. If a replacement WRCA01 carries a different firmware revision than the controller's system version, persistent 4303 alarms can result. Always match the board's firmware sticker to {SYSTEM} → {VERSION} before installation.