WinCC V7.3: Configuring Engineering and Operator Stations

David Krause16 min read
SiemensTutorial / How-toWinCC
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Overview: WinCC V7.3 ES/OS Architecture with STEP 7 V5.5

This technical reference describes how to commission a SIMATIC WinCC V7.3 (Classic) Engineering Station (ES) and Operator Station (OS) that share one STEP 7 V5.5 project targeting a fault-tolerant SIMATIC S7-400H station (CPU 412-5H). The ES is the development host: it runs SIMATIC Manager (STEP 7 V5.5), SIMATIC NET PC software, and WinCC V7.3 with the AS/OS Engineering installation option, which embeds the WinCC project as a sub-object of the STEP 7 project. The OS runs WinCC V7.3 Runtime plus the matching SIMATIC NET version; it does not host SIMATIC Manager and does not receive WinCC source files.

WinCC V7.x is the Classic SCADA line that pre-dates TIA Portal. The "AS/OS Engineering" install option is the standard mechanism for integrating WinCC projects into STEP 7's project tree (SIMATIC Station → WinCC OS). Without this option the WinCC project exists only as a standalone file and cannot share symbols, area pointers, or configuration data with STEP 7. The official guide "WinCC V7.3: Working with WinCC" is published on Siemens Industry Online Support (entry ID 102754925).

System Topology and Component Roles

The physical and logical layout consists of two PC stations plus the redundant S7-400H station, all on the same plant Ethernet LAN. The standard on-board Ethernet port of each PC handles S7 communication; no CP (communications processor) card is required.

Engineering Station (ES) STEP 7 V5.5 + WinCC V7.3 AS/OS Engineering license Operator Station (OS) WinCC V7.3 Runtime SIMATIC NET + RT license S7-400H Station CPU 412-5H #1 (R0/S2) CPU 412-5H #2 (R0/S3) H-Sync fiber / PN ring Plant LAN 192.168.0.0/24

Component Inventory

Component Engineering Station Operator Station
Hardware platform PC with x86 CPU, 4 GB+ RAM, 100 GB free disk, Gigabit Ethernet Same platform or industrial panel PC (e.g., SIMATIC IPC)
Operating system Windows 7 Professional / Ultimate 64-bit SP1 (or Windows Server 2008 R2) Windows 7 Professional / Ultimate 64-bit SP1
STEP 7 V5.5 + SPx Required (SIMATIC Manager) Not installed
WinCC V7.3 + Update Required, install mode "AS/OS Engineering" Required, install mode "WinCC Runtime"
SIMATIC NET PC software Required (S7 Protocol Suite / OPC) Required
Microsoft Message Queuing (MSMQ) Optional, recommended for redundancy Optional, recommended
WinCC license RC (Runtime + Configuration) or AS/OS Engineering bundle RT (Runtime only)
STEP 7 license STEP 7 V5.5 floating or single Not required
Ethernet interface On-board 1 Gbit/s On-board 1 Gbit/s

The S7-400H station contains two redundant CPU 412-5H modules in rack 0, slots 2 and 3. H-Sync modules occupy slots 4 and 5. The Ethernet interfaces of both CPUs share one logical IP address (the H-system virtual address) so the WinCC client connects transparently to whichever CPU is currently MASTER; on a failover the connection re-routes inside the H-system without re-establishing the TCP session.

License Models for WinCC V7.3

WinCC V7.3 distinguishes three license types that determine which install components and operations are enabled. Misalignment between license and usage causes silent demo-mode operation, missing graphic objects, or alarm-paging failures.

License Install mode Capabilities Typical host
WinCC RT (Runtime) WinCC Runtime Operator interface only; runs the activated project; no editor, no project creation Operator Station
WinCC RC (Runtime + Configuration) WinCC Runtime + Configuration Full WinCC Explorer, Graphics Designer, Alarm Logging, Tag Logging, script editor, project open / save Engineering Station
WinCC AS/OS Engineering WinCC Runtime + Configuration + AS/OS bundle Adds the ability to insert and configure an OS sub-object inside a STEP 7 project, automatic symbol import, area pointer generation Engineering Station (only)
License server. WinCC V7.3 uses the Automation License Manager (ALM). The ALM service runs on every licensed host and supports a network license: a license held on one PC can be borrowed by another PC across the LAN, but the lending PC must be reachable when the borrowed runtime starts. If the lending PC is offline, the borrowed runtime continues until the next ALM probe (default 30 s). A USB hardware dongle can be moved between hosts manually, but only the host currently holding the dongle can run Runtime.

Prerequisites and Compatibility Matrix

Operating System

WinCC V7.3 supports Windows 7 Professional, Ultimate, and Enterprise (32-bit and 64-bit) with SP1, plus Windows Server 2008 R2. Windows XP and Vista are not supported. Confirm the latest WinCC V7.3 readme for any added Windows 8 / Server 2012 support via the update package.

End-of-life notice. Microsoft ended Windows 7 mainstream support on 13 January 2015 and extended support on 14 January 2020. Siemens WinCC V7.3 continues to operate on Windows 7 but the platform no longer receives security patches from Microsoft. For new deployments choose a supported OS and WinCC V8.x or TIA Portal WinCC Professional.

STEP 7 V5.5 / WinCC V7.3 Compatibility

STEP 7 V5.x WinCC V7.x AS/OS Engineering Notes
V5.5 + SP4 (or higher) V7.3 + Update 4 (or higher) Required and supported Recommended for S7-412-5H projects
V5.5 + SP2 / SP3 V7.3 base Supported; verify readme Older service packs may limit S7-400H features
V5.4 or earlier V7.3 Not supported Upgrade STEP 7 first

Hardware Minimums (per Siemens readme)

  • CPU: Intel Core i3-2120 or comparable. WinCC V7.3 base runs on Atom but graphic editing is sluggish.
  • RAM: 4 GB minimum, 8 GB recommended for projects with more than 5 000 tags.
  • Disk: 10 GB free for WinCC base plus approximately 5 GB per engineering project.
  • Ethernet: 100 Mbit/s minimum, 1 Gbit/s recommended with auto-negotiation.
  • Graphics: DirectX 9 compatible adapter, 128 MB video memory minimum.

Network Pre-Configuration

Define static IPv4 addresses for every node before installation. The S7-400H station exposes one logical IP plus one or two physical IPs per CPU for diagnostics.

Node IP address Subnet mask Default gateway
Engineering Station 192.168.0.10 255.255.255.0 192.168.0.1 (only if router access required)
Operator Station 192.168.0.20 255.255.255.0 192.168.0.1
S7-400H logical (virtual) 192.168.0.100 255.255.255.0 —
S7-400H CPU1 physical 192.168.0.101 255.255.255.0 —
S7-400H CPU2 physical 192.168.0.102 255.255.255.0 —

All five addresses must be in the same subnet. Disable DHCP on the Engineering and Operator PCs to avoid address drift; the S7-400H does not support DHCP. Use a managed switch with port-based VLAN if you need to isolate the S7 LAN from the office network.

Engineering Station Installation Procedure

The install order is mandatory: the WinCC setup searches for STEP 7 registry keys and refuses to enable the AS/OS Engineering mode if STEP 7 is missing.

  1. Insert the STEP 7 V5.5 DVD or mount the ISO. Right-click Setup.exe and choose Run as administrator. The SIMATIC Manager setup installs SIMATIC Manager, HW Config, S7-PLCSIM, and the NetPro / SFC / SFB editors.
  2. Apply every released Service Pack (SP1, SP2, ... up to SP4 for V5.5) and the latest hotfix. Restart the PC between service packs.
  3. Insert the SIMATIC NET PC software DVD. Required components: SIMATIC NET PC Software with the Communication Services feature. Confirm the install includes the S7DOS driver and the Station Configuration Editor.
  4. Insert the WinCC V7.3 DVD. When the setup asks for installation type, choose AS/OS Engineering. The choice is greyed out if STEP 7 is not detected, confirming the install order. The installer copies the WinCC Explorer, Graphics Designer, Alarm Logging, Tag Logging, and the integration add-ins for SIMATIC Manager.
  5. Apply WinCC V7.3 Update 4 (or current). Restart.
  6. Open the Automation License Manager (Start → Siemens Automation → Automation License Manager). Plug in the USB license dongle or activate the software license. Verify that WinCC AS/OS Engineering is visible in the license tree.
  7. Open SIMATIC Manager. Confirm the menu Options → AS/OS is present; its presence confirms the integration DLL is registered.
  8. Open the WinCC Explorer from Start → SIMATIC → WinCC → WinCC Explorer. It should start without a license warning.
User account. Always run the WinCC setup, SIMATIC Manager, and the ALM from a local Administrator account. The WinCC Runtime Service logs in with the SIMATIC HMI system account; that account must exist and have access to the project folders.

Operator Station Installation Procedure

  1. Disable UAC on Windows 7 (Control Panel → User Accounts → Change User Account Control settings → Never notify).
  2. Install SIMATIC NET PC software with the same Communication Services feature as on the ES. Matching versions are required; mismatched SIMATIC NET between ES and OS causes the S7 connection to fail silently at runtime.
  3. Install WinCC V7.3 with the install mode WinCC Runtime. Do not select Configuration unless the OS doubles as a backup engineering station.
  4. Apply the same WinCC V7.3 update level as the ES.
  5. Install the Runtime license (RT) via the Automation License Manager. A USB dongle plugged into the OS is the simplest deployment; a network license works only while the lending PC is reachable.
  6. Confirm the WinCC service CCAgent is set to Automatic startup and that the SIMATIC HMI Windows account exists with the same SID on ES and OS if you copy the project by file share.

AS/OS Engineering Integration in SIMATIC Manager

Once both stations are installed, the WinCC project lives as a child object of the STEP 7 project. Open SIMATIC Manager on the ES and follow the procedure below.

  1. Open or create the S7 project (e.g., Plant_Pumps.S7P). Insert a SIMATIC H station or use an existing SIMATIC 400 station.
  2. Configure the H station in HW Config: insert the UR2-H rack, two CPU 412-5H modules in slots 2 and 3, the two H-Sync modules in slots 4 and 5, and any DI / DO / AI / AO modules. Download HW Config to the station. The H-system downloads both CPUs automatically once one CPU is in MASTER.
  3. Right-click the station and choose Insert New Object → OS. SIMATIC Manager adds a child node OS(1). Right-click it and choose Rename if you want a project label such as Plant_Pumps_OS.
  4. Open the OS object. WinCC Explorer launches. The left-hand tree contains Computer, Tag Management, Graphics Designer, Alarm Logging, Tag Logging, Report Designer, and User Administrator.
  5. Add the S7 connection: in Tag Management, right-click and choose Add New Driver → SIMATIC S7 Protocol Suite → TCP/IP. Right-click TCP/IP and select New Connection. Enter the S7-400H logical IP (192.168.0.100), Rack 0, Slot 2 (CPU1). The H-system virtual IP routes the connection automatically to whichever CPU is currently MASTER.
  6. Generate tags from STEP 7 symbols: choose Options → Symbol Table Import to publish shared DBs and I/O symbols as WinCC tags without retyping addresses.
  7. Configure area pointers: Tag Management → SIMATIC S7 Protocol Suite → TCP/IP → Connection → Properties → Area Pointer. Activate Date/Time (clock synchronization), Coordinator (system diagnostics), PDiag if you use process tag diagnostics, and Project ID for redundancy.
  8. Design the process pictures in Graphics Designer, configure alarms in Alarm Logging, and configure archives in Tag Logging.

SIMATIC NET PC Software Configuration

SIMATIC NET supplies the OPC server and the S7 protocol that WinCC uses internally. The PC station is configured through the Station Configuration Editor and indexed into the OS / WinCC project.

  1. Open Station Configuration Editor (Start → SIMATIC → SIMATIC NET → Configuration → Station Configuration Editor).
  2. Add a module of type OPC Server on Index 1 and a module of type IE General on Index 2. Map the IE General module to the physical Ethernet adapter by selecting Properties → Network Adapter.
  3. Save the configuration. The Configuration Console service (S7IESRV) restarts to apply the change.
  4. Open WinCC Explorer → Tag Management → SIMATIC S7 Protocol Suite → TCP/IP → System Parameters. Confirm Unit name matches the Station Configuration Editor station name (default WinCC).
  5. Right-click the connection and choose Connection Status. The state should report Established once the S7-412-5H has been reached on the plant LAN.
Firewall. Windows Firewall blocks the SIMATIC NET ports by default. Add inbound rules for S7DOS, OPC.EXE, and the WinCC binaries (CCAgent.exe, WCCRT.exe, WCCILdata.dll). The S7 protocol uses TCP port 102 by default; OPC uses the COM/DCOM dynamic range. Disabling the firewall on a closed plant LAN is acceptable; never do it on an office network.

Downloading the WinCC Project to the Operator Station

There are three deployment paths. Pick the one that matches project size and operational policy.

Path 1 - File Share (Small Projects)

  1. On the ES, compile the OS in WinCC Explorer (menu File → Compile → OS). The compiler produces a binary project under <project>\<OS>\<computer>\.
  2. Share the project folder with read/write access for the SIMATIC HMI Windows account.
  3. On the OS, open WinCC Explorer and choose File → Open. Browse to the shared path and open the project.
  4. Activate the project (File → Activate). Runtime starts automatically the next time the service reboots.

Path 2 - WinCC Project Duplicator (Recommended)

  1. On the ES, use SIMATIC Manager → Options → OS → Project Duplicator to package the OS as a stand-alone project.
  2. Copy the resulting folder to the OS via USB stick or network share.
  3. On the OS, open the duplicated project in WinCC Explorer and assign the OS computer name with Computer → Properties → Computer Name. The license binds to the computer name; changing the name invalidates the RT license check.

Path 3 - SIMATIC Manager Remote Download

  1. On the ES, in SIMATIC Manager, right-click the OS and choose OS → Download to Target System. The downloader transmits the compiled project over the LAN using the S7DOS service on the OS.
  2. The OS service CCAgent must be running and listening on TCP 102 (or the configured S7 download port).

After download, restart the WinCC Runtime on the OS (Start → Programs → SIMATIC → WinCC → Runtime) and observe the status window. Successful startup prints Runtime started; a license failure prints License missing; a connection failure prints S7 connection not established.

Verification and Acceptance Test

Before sign-off, run a structured acceptance test that exercises every WinCC subsystem.

  1. Tag connection test. In WinCC Explorer → Tag Management, right-click a tag and choose Update. The status icon shows green (OK), yellow (substituted), or red (bad quality). For a deeper check use the WinCC Channel Diagnosis tool (Start → SIMATIC → WinCC → Tools → Channel Diagnosis).
  2. Picture test. Open each process picture in Runtime. Confirm inputs (faceplates, sliders, buttons) write to the PLC and outputs (motor status, valve position, level) read back correctly.
  3. Alarm test. Force a known alarm in the PLC (set the trigger bit). Confirm it appears in Alarm Logging with the correct timestamp, priority, and acknowledgement state. Clear the bit and confirm the alarm returns to gone.
  4. Archive test. Tag Logging writes to \ArchiveManager database files under the project path. Verify the .ldf files grow during a forced data change and that the WinCC Trend Control displays the curve.
  5. Time synchronization. Force a time change on the ES clock and observe whether the S7-400H CPU time follows. The Date/Time area pointer must be enabled on the S7 connection for this to work.
  6. H-system failover. Pull the MASTER CPU or its H-Sync fiber. Within approximately 1 s the backup CPU takes over. The WinCC connection should remain Established and no operator action is required.
  7. OS license failover. Disconnect the ES if it lends the license over the network. Within the ALM probe period (default 30 s) the OS Runtime prints a warning but continues; after the probe period it may exit to demo mode.

Troubleshooting Matrix

Symptom Probable cause Action
"AS/OS Engineering" greyed out in WinCC setup STEP 7 V5.5 not installed or wrong service pack Install STEP 7 V5.5 SP4 first; rerun WinCC setup
S7 connection shows "Disconnected" in WinCC Explorer Subnet mismatch, firewall blocking TCP 102, wrong rack/slot ping from OS to 192.168.0.100; open TCP 102; verify Rack 0 / Slot 2
Runtime starts then exits to demo mode after 30 s Missing or unreachable RT license Confirm ALM shows valid license; reconnect dongle or fix network license host
Tag value freezes after H failover Connection points to one CPU physical IP instead of logical IP Change connection to the H-system logical IP 192.168.0.100
"DLL not found" when opening WinCC Explorer SIMATIC NET version mismatch between ES and OS Install identical SIMATIC NET service pack on both hosts
Alarm Logging shows < 1 minute clock skew Date/Time area pointer disabled Open connection properties → Area Pointer → enable Date/Time and Coordinator
Operator Station project cannot open the ES project path SIMATIC HMI account missing or password mismatch Create SIMATIC HMI account on OS with same SID; grant Read/Modify on the share
Engineering Station cannot find Operator Station for remote download CCAgent service stopped or firewall blocks download port Start CCAgent (Automatic); add firewall inbound rule for S7DOS
Graphics Designer crashes on screen open Video driver older than DirectX 9 or locked DLL Update driver; run Graphics Designer as administrator once
Channel Diagnosis returns "Cannot load S7DOS" SIMATIC NET install corrupted Repair install via Control Panel → Programs and Features → SIMATIC NET → Repair

Operating Mode and Lifecycle Notes

The ES / OS split shown here is one of several WinCC topologies. Other options in the WinCC V7.3 setup include:

  • Single-User Project. One PC with both RT and RC license. Used in small machines or test rigs.
  • Multi-User Project (Server / Client). One or more WinCC Servers host the project and the archive database; clients run Runtime only and connect to a server via TCP. Useful for plants with multiple operator desks.
  • Distributed Server. Several servers each own a subset of tags and pictures; a higher-level server aggregates them.

For new deployments, Siemens recommends TIA Portal WinCC Professional as the strategic successor to WinCC V7.3. TIA Portal provides WinCC Professional equivalent to WinCC V7.3 RC; the SIMATIC Migration Tool converts a STEP 7 V5.5 + WinCC V7.3 ES project into a TIA Portal project. The S7-412-5H remains compatible because TIA Portal supports S7-300/400 stations through the "Migrate S7-300/400 station" option. For guidance on the broader WinCC options landscape see the TIA Portal system overview for WinCC Engineering and Runtime options.

Engineering Station disconnected. The Operator Station continues to operate as long as its license and its connection to the S7-400H are intact. If the Operator Station holds its own RT license (recommended) the Engineering Station is needed only for project changes and diagnostics; pulling its network cable does not interrupt production.

FAQ

Does WinCC V7.3 require a separate CP card to talk to the S7-412-5H?

No. The standard on-board Ethernet port of the PC combined with SIMATIC NET PC software supports up to 8 S7 connections via the S7-Protocol Suite over TCP/IP. CP cards such as CP 1613 or CP 1623 are only needed for hard real-time, IRT, or PROFINET IO controller scenarios that do not apply to this WinCC-to-S7-400H monitoring use case.

Which license should the Engineering Station hold?

WinCC RC or WinCC AS/OS Engineering. The AS/OS Engineering license includes the RC scope plus the integration component that allows the OS to be embedded inside the STEP 7 project. The OS needs only an RT license.

Can the Operator Station keep running if the Engineering Station is shut down?

Yes, provided the OS has its own RT license (locally installed or on a dedicated license server). If the OS borrows a network license from the ES, Runtime continues until the next ALM probe period (default 30 s) and may then switch to demo mode.

How many PLCs can one PC talk to over standard Ethernet?

WinCC V7.3 S7-Protocol Suite over TCP/IP supports up to 8 S7 connections per channel unit from a single PC. Each connection targets one logical PLC address (or one H-system virtual address for the S7-400H). Adding more PLCs requires additional channel units or additional OPC servers.

Is Windows 7 still supported for WinCC V7.3?

WinCC V7.3 officially supports Windows 7 Professional / Ultimate / Enterprise SP1. Microsoft ended extended support for Windows 7 on 14 January 2020, so security patches are no longer issued. Siemens recommends upgrading the OS and WinCC version for any new deployment, especially in IEC 62443 environments.

Does the WinCC project need to be recompiled when the H-CPU fails over?

No. Failover is transparent at the S7 protocol level because WinCC connects to the H-system logical IP. The compiled OS binary remains valid; only the tag qualities may briefly report "uncertain" during the sub-second switch.

Back to blog